2007-03-23 13:00:18***APPROVED***
  
 1) PULL STATIONS SHALL BE LOCATED AT EXIT DOORS NOT TO
 EXCEED 200'. IT WOULD APPEAR THAT EXTRA PULL STATIONS
 HAVE BEEN PROVIDED.
  
 2) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS IF
 COMPATIBLE WITH EXISTING FIRE ALARM SYSTEM.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW