| Plan Review Notes For Permit 07030281 |
| Permit Number |
07030281 |
|
| Review Stop |
M |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2007-11-30 15:08:52 | THE FOLLOWING PAGES WERE DENIED WITH COMMENTS: | | | H-1.1 REV.4 | | | | | | COMMENT: PG A03.12 SHOWS THE WALLS WHICH FORM ROOM | | | 1296A ARE TYPE 132S. PG A14.10 SHOWS WALL TYPE TO BE | | | 1-HOUR RATED FROM FLOOR TO UNDERSIDE OF DECK. THEREFORE | | | THE NEW SUPPLY, TRANDFER AND EXHAUST PENETRATIONS OF | | | THESE WALLS SHALL HAVE OPENING PROTECTIVES IN | | | ACCORDANCE WITH FBC, M 607.5. SHOW THESE PENETRATIONS | | | TO BE PROTECTED IN ACCORDANCE WITH THIS SECTION AND | | | RESUBMIT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | |
|