| Plan Review Notes For Permit 07030281 |
| Permit Number |
07030281 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-05-20 15:34:23 | REVISION COMMENTS FOR THE TRANSFORMER CHANGE OF | | | LOCATION. | | | | | | | | | ENGINEER OF RECORD FOR THE BASE BUILDING SHALL SUBMIT | | | STRUCTURAL CALCULATIONS FOR REVIEW. | | | PROVIDE COMPLETE INSTALLATION DETAIL INCLUDING ALL | | | MATERIALS AND HARDWARE. | | | EXPLAIN REFERENCE TO W21, THE 12TH FLOOR FRAMING PLAN | | | CALLS FOR W24, 30, AND 36. | | | ALL SUBMITTALS SHALL BE SIGNED AND SEALED. | | | | | | | | | | | | | | | | | | LUIS MARTINEZ | | | 561-805-6710 |
|