Plan Review Notes
Plan Review Notes For Permit 07030281
Permit Number 07030281
Review Stop E
Sequence Number 4
Notes
Date Text
2007-11-03 14:54:142007-11-03 14:54:14
  
 ** DENIED 4TH REVIEW **
  
 1) NOTE: PLEASE SEE FAC 61G15-23.002 AS GIVEN ON
 PREVIOUS REVIEWS. PLEASE SEE THE TITLE BLOCKS ARE STILL
 MISSING THE PRINTED NAME OF THE ENGINEER.
 IF THIS WERE THE ONLY COMMENT, THE OWNER REPRESENTATIVE
 COULD PRINT ON ALLS SHEETS.
  
 2) NOTE: NEED TO VERIFY ON LIGHTING CALCULATIONS SHEET
 THE ADDITIONAL WATTAGE BEING SHOWN WHICH EXCEEDS THE
 TABLE ALLOWANCES. IF THERE IS ADDITIONAL WATTAGE IS
 BEING FIGURED FROM THE CODE PLEASE EXPLAIN AND INDICATE
 ON TABLE WHICH LOCATIONS/ROOMS ARE USING THE ADDITIONAL
 WATTAGE WHICH MAY BE PERMITTED UNDER 13-415.2.B.2. ONLY
 ROOMS WHICH CONTAIN THE LIGHTING FOR DECORATIVE
 PURPOSES ARE PERMITTED TO USE THE ADDITIONAL WATTAGE OF
 1.0 PER SQ FT. IF ROOM ONLY CONTAINS GENERAL LIGHTING,
 THEN THE TABLE AS SPECIFIED IN 13-415.2.B MAY ONLY BE
 USED.
 PLEASE EXPLAIN HOW OFFICE/CONFERENCE ROOM HAS LPD AT
 2.4?
 THIS CAN BE DONE WITH A ** NEXT TO THE ROOM DESIGNATION
 ON LIGHTING TABLES.
  
 3) NOTE: PLEASE SEE THE ACCENT/TASK LIGHTING REQUIRES
 ADDITIONAL CONTROLS PER 13-415.1.ABC.1.3. THE RESPONSE
 MENTIONS THESE WILL BE DONE BY A MANUAL ON/OFF SWITCH.
 THESE LIGHTING FIXTURES ARE REQUIRED TO CONTAIN SOME
 SORT OF AUTOMATED CONTROL SO THAT THESE FIXTURES ARE
 NOT INADVERTENTLY LEFT ON. THE INTENT OF CHAPTER
 13-415.41 IS TO AUTOMATICALLY TURN OFF AS MANY LIGHTS A
 POSSIBLE.
 PLEASE SEE ONE AREA IN QUESTION WHERE THE OCCUPANT IS
 REQUIRED TO SEE THE LIGHTING WHICH IS BEING OVER
 RIDDEN. PLEASE SEE ZONE 10 FOR EXAMPLE WHICH IS BEING
 CONTROLLED FROM BOTH THE SOUTH AND NORTH SIDE OF THE
 FLOOR. THIS IS OK, HOWEVER A PILOT/INDICATOR LIGHT OF
 SOME TYPE WILL BE REQUIRED SO THE OCCUPANT CAN TELL
 WHICH SPECIFIC LIGHTS ARE BEING
 CONTROLLED.13-415.1.ABC.1.2 **EXCEPTION?*
 PLEASE SEE WHAT APPEARS TO BE A ROOM DIRECTLY ACROSS
 FROM ELECTRICAL ROOM 1296. DOES THIS AREA CONTAIN FLOOR
 TO CEILING HEIGHT PARTITIONS? THIS AREA DOES SHOW A
 DOOR.
 PLEASE SEE NOTE BELOW WITH MISSING FIXTURE *K* FROM
 AREA 1256 AND CONTROL?
  
 4) NOTE: PLEASE SEE FBC 13-415.2 AS LIGHTING
 PERFORMANCE CALCULATIONS NEED TO BE ADDRESSED. THE
 FOLLOWING ARE SOME EXAMPLES OF REMAINING OUTSTANDING
 ISSUES. THESE ARE IN NO PART ALL POSSIBLE SCENARIOS.
  
 PLEASE CLARIFY WHY SOME ROOMS WHICH ARE SHOWN ON PLANS
 IN WHAT WOULD BE THE SOUTHEAST PORTION OF THE BUILDING
 WHEN THESE ARE LOCATED ON THE NORTHEAST TABLE. *EXAMPLE
 1215. THIS IS NOT AN ISSUE AS LONG AS ALL FIXTURE
 WATTAGE USAGE IS BEING CONSIDERED AND TAKEN INTO
 ACCOUNT HOWEVER COORDINATION IN REVIEW OF TABLES
 COMPARED TO PLANS SHOULD BE CONSIDERED.
  
 PLEASE CLARIFY HOW THE DENSE FILING ROOM 1289 CAN BE
 SHOWN AS A CONFERENCE MEETING ROOM. THIS ROOM DOES NOT
 FALL CLOSEST TO CONFERENCE MEETING ROOM WHICH ALLOWS
 1.3, THIS MAY BE CONSIDERED ACTIVE STORAGE AT 0.8. OR
 POSSIBLY OFFICE AT 1.1. PLEASE VERIFY IF A PERMANENT
 WORK STATION IS IN ROOM.
  
 PLEASE KNOW BASED ON THE LIGHTING POWER TABLES
 SUBMITTED THE DESIGN IS BEING SHOWN AT 13.99 WATTS
 BELOW MAXIMUM ALLOWANCE. PLEASE SEE HOWEVER THERE ARE
 FIXTURE(S) ON PLANS WHICH ARE NOT FIGURED INTO THE
 CALCULATIONS. IF THESE ARE THEN THE TOTAL ALLOWANCE
 WOULD BE EXCEEDED.
  
 N.E. AREA: PLEASE SEE FOR EXAMPLE ROOM 1288 AS THE
 TABLE SHOWS 3-FIXTURES TOTAL, YET PLANS SHOW 4.
  
 S.E. AREA: PLEASE SEE FOR EXAMPLE THE LOBBY/RECEPTION
 AREA 1200 AS TABLE COUNT FOR FIXTURE *D* DOES NOT MATCH
 WITH PLANS. PLEASE ALSO CLARIFY WHERE THE ADDITIONAL
 *E* FIXTURES ARE AS THE FOUR OF THESE FIXTURE *E* ARE
 IN ELEVATOR LOBBY ARE LISTED ON 1293.
  
 S.W. AREA: PLEASE SEE FOR EXAMPLE ROOM/AREA 1277 AS
 THIS AREA IS TAKING INTO ACCOUNT *S* FIXTURES. THIS
 AREA IS INDICATING A TOTAL OF 20 FIXTURES YET TABLE
 INDICATES 19.THERE IS QUESTION ON S FIXTURE DIRECTLY
 ACROSS FROM ELECTRICAL ROOM 1296 AS THIS SEEMS TO BE A
 SEPARATE ROOM HOWEVER AS NO OTHER DESIGNATION IS
 PRESENT THEREFORE THIS IS ASSUMED IN THIS ZONE/AREA
 1277.
  
 N.W. AREA: PLEASE SEE FOR EXAMPLE CORRIDOR 1256 WHICH
 *K* FIXTURE WATTAGE LISTED ON FIXTURE SCHEDULE IS
 HIGHER THAN ON TABLE. THE OTHER QUESTION IS THE FIXTURE
 *K* COULD NOT BE LOCATED IN THE 1256 AREA? CONTROL ETC
 WILL BE NOTED ABOVE.
  
 ** THE ABOVE EXAMPLES ARE SOME ITEMS FROM EACH SECTION
 OF THE FLOOR BEING NOTED ON PLANS AS NE, SE, SW, NW AND
 CORE.
 AS STATED ON PREVIOUS PLAN REVIEWS. PLEASE COORDINATE
 ALL LIGHTING FIXTURES ON PLANS WITH THE *MAXIMUM*
 ALLOWANCE CALCULATIONS. PLEASE COORDINATE TABLES WITH
 THE FIXTURES AND WATTAGES AS INDICATED ON FIXTURE
 LEGEND.
  
 5) NOTE: PLEASE BE SURE WHEN SUBMITTING PLANS TO ATTACH
 COMPLETE SETS TOGETHER WITH STAPLES WHICH GO ALL THE
 WAY THROUGH THE PLANS.
  
 6) NOTE: PLEASE KNOW THAT ONE COMPLETE COPY OF
 ELECTRICAL PLANS IS BEING RETAINED BY THIS OFFICE.
 PLEASE SEE FS 553.80(2)(B). PLEASE KNOW AS THE CODE
 SECTIONS WERE GIVEN FOR THE SAME SECTION OF 13-415.2
 FOR COORDINATION OF LIGHTING ON PLANS WITH CALCULATIONS
 FOR FOUR REVIEWS NOW, THE FEE AS REQUIRED PER FLORIDA
 STATUTE IS ONCE AGAIN ASSESSED.
 PLEASE SEE THAT SPECIFICALLY THE NOTES HAVE STATED ON
 FOUR REVIEWS TO BE SURE AND CORRELATE ALL LIGHTING
 FIXTURES ON PLANS, ALL WATTAGES ON PLANS WITH THE
 CALCULATIONS. THIS INCLUDES THE INPUT DATA AS
 PREVIOUSLY SUBMITTED AS WELL AS THE INPUT DATA TABLES
 NOW ON SHEET E-0.6.
 THE FEE IS REQUIRED BEFORE RESUBMISSION OF PLANS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]