Plan Review Notes
Plan Review Notes For Permit 07030281
Permit Number 07030281
Review Stop P
Sequence Number 3
Notes
Date Text
2007-07-14 11:15:07DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WEST PALM BEACH MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW****
  
 1. OK
 2. OK
 3. OK
  
 4. ALL ARCHITECTURAL SHEET SHALL BE SEALED BY AN
 IMPRESSION TYPE SEAL THAT SHALL IMPRESS ALL INFORMATION
 REQUIRED BY FAC 61G1-16.002 ON EACH SHEET. FAC
 61G1-16.001 AND FS 481.2055.
 ****RESPONSE NOTED, BUT PER FAC 61G1-16.003 &
 61G1-16.004(5) THE DATE THE SEAL & SIGNATURE ARE
 AFFIXED TO THE PLANS SHALL BE INDICATED BELOW THE
 SIGNATURE. FS 481.2055.
  
 5. SHT A13.01 ALL 4 SINKS SHALL BE ACCESSIBLE. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 NOTE: CLEAR FLOOR SPACE SHALL BE FORWARD APPROACH AND
 EXTEND A MAXIMUM 19" UNDERNEATH THE SINK. CABINET DOORS
 ARE NOT APPROVED IN THE CLEAR FLOOR SPACE AND SHALL BE
 DELETED FROM THE DETAILS FOR EACH SINK. ****RESPONSE
 NOTED, BUT DETAIL #11 DOES NOT INDICATE THE WIDTH OF
 THE OPENING AND IT SCALES OUT LESS THAN THE REQUIRED
 30" WIDTH. SECTION 11-4.24.5. PLEASE CLARIFY.
  
 6. OK
 7. OK
  
 8. SHT H-0.3 DETAIL #3 A/C CONDENSATE TO THE FLOOR
 DRAIN IS NOT APPROVED TO THE SANITARY SEWER. MUNICIPAL
 CODE WWF, ART. III SEWERS AND SEWAGE DISPOSAL SECTION
 90-125(B)(5). CONDENSATE SHALL CONNECT TO A DEDICATED
 CONDENSATE LINE OR DISCHARGE SEPARATELY OUT OF THE
 BUILDING AND DRAIN INTO A CATCH BASIN, A STORM LINE OR
 A DRYWELL.
 ****RESPONSE NOTED, BUT THE CONDENSATE SHALL NOT
 CONNECT TO THE STORM. CONDENSATE SHALL CONNECT TO
 CONDENSATE AS INDICATED.
  
 9. SHT P1.1 SHOWS TWO ADDED DRINKING FOUNTAINS NOT
 SHOWN ON THE FLOOR PLAN, (A-03.12). PLEASE CORRELATE
 INFORMATION BETWEEN THE ARCHITECTURAL SHEETS AND THE
 PLUMBING SHEETS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT ONLY ONE DRINKING FOUNTAIN IS
 SHOWN ON THE ARCHITECTURAL SHEETS.
  
 10. SUBMIT ISOMETRIC RISER DIAGRAMS FOR THE WATER, DWV,
 AND CONDENSATE. SHOW ALL PIPE SIZES, VALVES & WATER
 HAMMER ARRESTORS, (REQUIRED BY SECTION 604.9), ON THE
 WATER RISER DIATRAM. SHOW ALL PIPE SIZES TRAPS AND
 VENTS FOR THE DWV. SHOW THE PIPE SIZE AND THE
 TERMINATION POINT FOR THE CONDENSATE. INDICATE THE
 LOCATION OF THE POINT OF CONNECTION FOR THE WATER AND
 THE SANITARY. SECTION 106.3.5.1.3((3)(4)(6)(19)(13).
 ****RESPONSE NOTED, BUT NO WATER HAMMER ARRESTORS WERE
 SHOWN. (DISH WASHERS, ICE MAKER REQUIRE WHA'S).
  
 11. OK
 12. OK
  
 **********NEW COMMENT**********
  
 1B. THREE COPIES OF SHT P0.2 HAVE BEEN SUBMITTED WITH
 THE PLANS FOR THIS PERMIT APPLICATION. IT APPEARS TO
 HAVE A REVISION TO THE BASE BUILDING INDICATED ON THE
 SHEETS AS WELL AS THE GAS PLANS FOR THE GENERATORS. THE
 PLANS SHALL BE SUBMITTED UNDER THE CORRECT PERMIT
 APPLICATION NUMBER AND WITH THE PLANS FOR THOSE
 APPLICATION NUMBERS. THE BUILD-OUT FOR THE 12TH FLOOR
 IS NOT THE CORRECT NUMBER TO SUBMIT THESE PLANS.
  
 REVIEW BY KEN STEVENS