| 2007-07-14 11:15:07 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | WEST PALM BEACH MUNICIPAL CODE |
| | |
| | ****FROM PREVIOUS REVIEW**** |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | |
| | 4. ALL ARCHITECTURAL SHEET SHALL BE SEALED BY AN |
| | IMPRESSION TYPE SEAL THAT SHALL IMPRESS ALL INFORMATION |
| | REQUIRED BY FAC 61G1-16.002 ON EACH SHEET. FAC |
| | 61G1-16.001 AND FS 481.2055. |
| | ****RESPONSE NOTED, BUT PER FAC 61G1-16.003 & |
| | 61G1-16.004(5) THE DATE THE SEAL & SIGNATURE ARE |
| | AFFIXED TO THE PLANS SHALL BE INDICATED BELOW THE |
| | SIGNATURE. FS 481.2055. |
| | |
| | 5. SHT A13.01 ALL 4 SINKS SHALL BE ACCESSIBLE. SHOW |
| | COMPLIANCE WITH THE FOLLOWING: |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | E. OK |
| | NOTE: CLEAR FLOOR SPACE SHALL BE FORWARD APPROACH AND |
| | EXTEND A MAXIMUM 19" UNDERNEATH THE SINK. CABINET DOORS |
| | ARE NOT APPROVED IN THE CLEAR FLOOR SPACE AND SHALL BE |
| | DELETED FROM THE DETAILS FOR EACH SINK. ****RESPONSE |
| | NOTED, BUT DETAIL #11 DOES NOT INDICATE THE WIDTH OF |
| | THE OPENING AND IT SCALES OUT LESS THAN THE REQUIRED |
| | 30" WIDTH. SECTION 11-4.24.5. PLEASE CLARIFY. |
| | |
| | 6. OK |
| | 7. OK |
| | |
| | 8. SHT H-0.3 DETAIL #3 A/C CONDENSATE TO THE FLOOR |
| | DRAIN IS NOT APPROVED TO THE SANITARY SEWER. MUNICIPAL |
| | CODE WWF, ART. III SEWERS AND SEWAGE DISPOSAL SECTION |
| | 90-125(B)(5). CONDENSATE SHALL CONNECT TO A DEDICATED |
| | CONDENSATE LINE OR DISCHARGE SEPARATELY OUT OF THE |
| | BUILDING AND DRAIN INTO A CATCH BASIN, A STORM LINE OR |
| | A DRYWELL. |
| | ****RESPONSE NOTED, BUT THE CONDENSATE SHALL NOT |
| | CONNECT TO THE STORM. CONDENSATE SHALL CONNECT TO |
| | CONDENSATE AS INDICATED. |
| | |
| | 9. SHT P1.1 SHOWS TWO ADDED DRINKING FOUNTAINS NOT |
| | SHOWN ON THE FLOOR PLAN, (A-03.12). PLEASE CORRELATE |
| | INFORMATION BETWEEN THE ARCHITECTURAL SHEETS AND THE |
| | PLUMBING SHEETS. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT ONLY ONE DRINKING FOUNTAIN IS |
| | SHOWN ON THE ARCHITECTURAL SHEETS. |
| | |
| | 10. SUBMIT ISOMETRIC RISER DIAGRAMS FOR THE WATER, DWV, |
| | AND CONDENSATE. SHOW ALL PIPE SIZES, VALVES & WATER |
| | HAMMER ARRESTORS, (REQUIRED BY SECTION 604.9), ON THE |
| | WATER RISER DIATRAM. SHOW ALL PIPE SIZES TRAPS AND |
| | VENTS FOR THE DWV. SHOW THE PIPE SIZE AND THE |
| | TERMINATION POINT FOR THE CONDENSATE. INDICATE THE |
| | LOCATION OF THE POINT OF CONNECTION FOR THE WATER AND |
| | THE SANITARY. SECTION 106.3.5.1.3((3)(4)(6)(19)(13). |
| | ****RESPONSE NOTED, BUT NO WATER HAMMER ARRESTORS WERE |
| | SHOWN. (DISH WASHERS, ICE MAKER REQUIRE WHA'S). |
| | |
| | 11. OK |
| | 12. OK |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. THREE COPIES OF SHT P0.2 HAVE BEEN SUBMITTED WITH |
| | THE PLANS FOR THIS PERMIT APPLICATION. IT APPEARS TO |
| | HAVE A REVISION TO THE BASE BUILDING INDICATED ON THE |
| | SHEETS AS WELL AS THE GAS PLANS FOR THE GENERATORS. THE |
| | PLANS SHALL BE SUBMITTED UNDER THE CORRECT PERMIT |
| | APPLICATION NUMBER AND WITH THE PLANS FOR THOSE |
| | APPLICATION NUMBERS. THE BUILD-OUT FOR THE 12TH FLOOR |
| | IS NOT THE CORRECT NUMBER TO SUBMIT THESE PLANS. |
| | |
| | REVIEW BY KEN STEVENS |