Plan Review Notes
Plan Review Notes For Permit 07030281
Permit Number 07030281
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-15 17:05:02NOTE ADDED:
  
 PLEASE BE SURE TO PROVIDE THE CORRECT PERMIT
 APPLICATION AS THE APPLICATION SUBMITTED IN THE PERMIT
 PACKAGE IS FOR CENTEX CONSTRUCTION. A CHANGE OF
 CONTRACTOR WAS DONE AND IS NOW BALFOUR/BEATLY. THIS
 APPLICATION SHOULD BE IN PACKAGE.
 PLEASE ALSO SEE THE RESUB COVER SHEET WAS FILLED OUT
 AND STILL INDICATES CENTEX CONSTRUCTION. THIS WAS
 CORRECTED ON RESUB COVER SHEET.
2007-09-15 16:57:302007-09-15 16:57:30
  
 *** DENIED 3RD REVIEW ***
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS TWO REVIEWS
 WHICH ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE ALSO SEE THERE SOME NEW COMMENTS BASED ON
 CHANGES AND REVISIONS TO PLANS.
  
  
 1) NOTE: PLEASE SEE SOME OF THE FLORIDA ADMINISTRATIVE
 CODE AND FLORIDA STATUTES COMMENTS BELOW WILL REMAIN AS
 SOME OF THE UPDATED REVISED SHEETS IN THE NEW SETS ARE
 STILL IN NEED OF ADDRESSING.
  
 2) NOTE:PLEASE SEE NOT ALL TITLE BLOCKS ON SHEETS FOR
 THE ARCHITECTURAL FIRM CONTAIN THE PRINTED CERTIFICATE
 OF AUTHORIZATION NUMBER/LICENSE INFORMATION. PLEASE SEE
 THE REVISED MEP SHEETS ARE STILL MISSING THIS
 INFORMATION AS THE TITLE BLOCK FOR THE ARCHITECTURAL
 FIRM IS LISTED. ** PLEASE KNOW ON ANY SHEETS WHICH MAY
 NOT HAVE TO BE REVISED THIS CAN BE PRINTED ON BY HAND.
 PLEASE SEE PREVIOUS COMMENTS AS THIS IS REQUIRED ON ALL
 SHEETS WHICH CONTAIN THE TITLE BLOCK FOR SAID FIRM. FAC
 61G1-16.004, FS481.219
 ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE #3, WITH RESPECT TO
 SIGNATURE OF THE ENGINEER ON ELECTRICAL SHEETS. PLEASE
 SEE THE LETTER SUBMITTED WAS NOT SEALED WITH THE RAISED
 SEAL AS PREVIOUSLY REQUESTED.
 AS THIS OFFICE HOLDS SHEETS WHICH SEEM TO CONTAIN
 DIFFERENT SIGNATURES WE CAN ONLY VERIFY THIS BASED ON
 THE DOCUMENTED LETTER WHICH WILL PLACE IN FILE FOR
 FUTURE REFERENCE.
 PLEASE BE SURE ALL PLANS SUBMITTED FOR THIS PROJECT AND
 ALL PROJECTS ARE SIGNED WITH THE SAME SIGNATURE/MANOR
 TO ALLEVIATE ANY CONFUSION.
 PLEASE SEE THE FAC 61G15-23.002 AND FS 471.025 AS THE
 ENGINEER OF RECORD SHALL BE THE ONLY ONE TO SIGN
 PLANS.
  
 4) NOTE: PLEASE SEE THE DESIGNATIONS ON THE PLANS FOR
 PANELS ON RISER AND PANEL SCHEDULES HAVE BEEN UPDATED.
 PLEASE SEE PANEL DP-11 ON E-.04 WHICH INDICATES FEED TO
 A T7A TRANSFORMER AND THE RISER INDICATES T6A AS BEING
 THE TRANSFORMER.
 PLEASE KNOW DEPENDING ON WHICH TRANSFORMER IS BEING
 USED, THIS COULD CREATE SEPARATE CODE COMPLIANT
 COMMENTS.
 PLEASE SEE 240.21, 250.66, 450.3, 408.36 ETC.
 (TRANSFORMER T4 HAS BEEN NOTED ON OTHER PLANS AS THE
 OVER CURRENT PROTECTION ON THE LINE SIDE IS HIGH,
 450.3) THIS TRANSFORMER DOES NOT AFFECT THIS SPACE,
 HOWEVER AS THE TABLE FOR ALL PLANS SHOULD BE UPDATED,
 THIS SHOULD BE DONE AT THIS TIME. (MAX OPC 125%,
 70AMPS? DEPENDING ON TYPE OF UNIT)
  
 5) NOTE: PLEASE CLARIFY WHERE ON THE A-SHEETS IS THE
 INFORMATION FOR THE REQUIRED RATED WALLS FOR SERVER/IT
 ROOM.
 THIS IS INDICATING CHARACTERISTICS OF AN IT, HOWEVER
 WALL IS NOTED ON SHEET AS *032S* WHICH BY A14.10 DOES
 NOT CONTAIN ANY FIRE RATING?
 PLEASE SEE NFPA-75 CHAPTER 5. THIS INFORMATION IS BEING
 SENT TO THE BUILDING REVIEWER, FIRE MARSHAL AND
 MECHANICAL REVIEWER(S).
 ** PLEASE KNOW ANY INSTALLATIONS OF UPS SYSTEMS WILL
 NOT BE UNDER THIS PERMIT AS NO SYSTEMS ARE SHOWN ON
 PLANS.
  
 6) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO THE ENERGY CODE FOR CONTROLS.
 PLEASE SEE SOME ITEMS ARE STILL NOT CLEAR FOR SYSTEM
 AND CONTROLS.
 PLEASE SEE SEPARATE SPACES, AND IN PARTICULAR ANY
 ADDITIONAL CONTROLS FOR DISPLAY OR ACCENT LIGHTING. FOR
 EXAMPLE: COFFEE ROOM *I* FIXTURE, BREAK ROOM *D*
 FIXTURES.
 PLEASE SEE 13-415.1.ABC.1.3.
 PLEASE BE SURE TO SEE 13-415.1.ABC.1.1 AS THE LIGHTING
 OVER RIDE CONTROLS ARE TO BE LOCATED SO THAT ALL OF THE
 LIGHTING WHICH IS BEING OVER RIDDEN CAN BE SEEM BY THE
 OCCUPANT. THERE IS AN EXCEPTION FOR INDICATOR
 LIGHTS/PILOT LIGHTS. PLEASE VERIFY ALL LOCATIONS ON
 PLANS AS NOTE #4 SEEMS TO BE FOR THE SLV DEVICE WHICH
 MENTIONS IT WILL OVER RIDE MULTIPLE LOCATIONS WHICH MAY
 NOT BE SEEN BY THE OCCUPANT.
  
 7) NOTE: ENERGY CALCULATIONS.
 AS NOTED BELOW IDR WILL REPRESENT THE INPUT DATA REPORT
 ON ALL NOTES:
 A) PLEASE SEE PREVIOUS NOTES WHICH REQUESTED FOR ALL
 INFORMATION ON THE INPUT DATA REPORT/ENERGY
 CALCULATIONS TO CORRELATE WITH *ALL* LIGHTING WHICH IS
 SHOWN ON PLANS.
  
 B) PLEASE SEE THERE ARE 91 +/- ROOMS/AREAS DESIGNATIONS
 ON PLANS, HOWEVER ONLY 65+/- ON THE IDR. IT SEEMS SOME
 OF THESE AREAS MAY BE FIGURED INTO ONE TYPE OF AREA,
 HOWEVER MANY OF THESE NUMBERS DO NOT MATCH FOR THE
 NUMBER OF FIXTURES, THE TYPES OF FIXTURES AND THE
 WATTAGE OF THE FIXTURES.
  
 C) PLEASE SEE AS THE ROOMS/AREA DESIGNATIONS ON THE IDR
 DO NOT CORRELATE WITH THE SAME DESIGNATIONS ON PLANS,
 SOME LOCATIONS CAN ONLY BE ASSUMED.
 PLEASE SEE ONE LOCATION WHICH IS NOT CLEAR IS OFFICE
 A.
  
 IF LOOKING AT THE PLANS AND TRYING TO MATCH UP THE
 NUMBERS OF FIXTURES AND WATTAGES WITH THE FIXTURE
 LEGEND IS THE WAY THIS IS TO BE FIGURED, THIS IS NOT
 CORRELATING.
 ** PLEASE SEE NW SECTION OF PLANS?
 EXAMPLE: THE OFFICE A IN THE NW SECTION OF IDR
 INDICATES 4-84WATT FIXTURES, YET THE OFFICE A IN THE NE
 SECTION OF IDR INDICATES ONLY 1-84 WATT FIXTURE. THIS
 ONE OFFICE A WITH ONLY ONE LIGHT FIXTURE COULD NOT BE
 FOUND ON THE NE SECTION OF THE FLOOR PLAN.
 THIS IS THE SAME FOR SEVERAL OTHER AREAS IN THE NW
 SECTION.
 ** PLEASE SEE NE SECTION OF FLOOR PLANS:
 EXAMPLE: BREAK ROOM WHICH INDICATES A FIXTURE *D* WHICH
 IS 50WATTS ON FIXTURE LEGEND AND NO 50WATT FIXTURE IS
 SHOWN ON THE IDR FOR THIS SAME ROOM.
 ** PLEASE SEE FILES ROOM IN THE IDR, WHICH C, A AND B
 FIXTURES, WATTAGE AND NUMBER OF FIXTURES ON IDR DOE NOT
 CORRELATE.
 ** PLEASE SEE SE SECTION OF PLANS:
 EXAMPLE: CONFERENCE ROOM 1202, 2-C, 5-M, 4-N AND 1-A,
 SEE IDR, SOME OF THESE ARE OK, HOWEVER SOME ARE MISSING
 AND/OR THE TOTAL OF FIXTURES AND WATTAGE ARE NOT THE
 SAME.
 ** PLEASE SEE SW SECTION OF PLANS:
 EXAMPLE: SMALL CONFERENCE? IF THIS IS THE SAME ROOM, IT
 IS UNCLEAR? PLEASE SEE ONLY TWO TYPES OF FIXTURES ARE
 LISTED IN THE IDR, YET PLANS SEEM TO SHOW FIXTURES C, A
 AND M?
  
 ** THESE ARE ONLY A FEW EXAMPLES OF SOME OF THE ROOMS
 WHICH FIXTURES ON PLANS DO NOT CORRELATE WITH THE IDR.
 THIS IS NOT ALL LOCATIONS. PLEASE BE SURE TO GO OVER
 ALL FIXTURES ON PLANS. PLEASE PLACE SOME SORT OF
 DESIGNATION ON THE IDR WHICH CORRESPONDS TO THE PLANS.
  
  
 D) PLEASE SEE THE FIXTURE LEGEND AND IDR CONTAINS
 FIXTURES WHICH DOE NOT MATCH.
 FOR EXAMPLE:
 ** PLEASE SEE THE FIXTURE LEGEND SHOWS 40W, 96W, 75W
 ETC FIXTURES AND IDR DOES NOT INDICATE THESE. PLEASE
 SEE BELOW FOR THE 96W FIXTURE.
 **PLEASE SEE THE IDR WHICH SEEMS TO INDICATE 300W
 FIXTURE(S) YET THE FIXTURE LEGEND DOES NOT.
 ** PLEASE SEE TYPE *S* FIXTURE WHICH IS SHOWN AS A 96W
 FIXTURE ON LEGEND HOWEVER THIS SEEMS TO BE SHOWN AS
 BOTH 84W AND 96W ON IDR. THIS IS SEEN IN TRAINING ROOM
 WHICH ON THE IDR SHOWS THESE AS TYPE *S* FIXTURE WHICH
 IS 96W ON THE IDR, YET THE SAME FIXTURE *S* IN THE
 OFFICES AND ALL OTHER AREAS ON PLANS ARE 84W?? PLEASE
 COORDINATE ALL OF THESE. IF THE FIXTURES ARE 84W,
 ADJUST LEGEND AND IDR, IF THE FIXTURES ARE 96W, PLEASE
 ADJUST FIXTURE LEGEND AND IDR.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 ALSO AFFECT THE METHOD OR ENERGY CALCULATIONS. PLEASE
 SEE 13-415.1.A, 13-415.1.B, 13-415.1.C, 13-415.2
 PLEASE BE SURE ALL FIXTURE TYPES, WATTAGES, NUMBER OF
 FIXTURES, ROOMS AND AREAS ON PLANS COORDINATE WITH THE
 IDR AND FIXTURE LEGEND.
  
 8) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO
 FS 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR
 CODE COMPLIANCE.
 PLEASE KNOW AS THE ENERGY CALCULATIONS COORDINATION
 COMMENT HAS BEEN REPEATED NOW FOR THE THIRD TIME.
 PLEASE KNOW DUE TO THIS COMMENT AND OTHER COMMENTS AS
 NOTED ABOVE ONE SET OF ELECTRICAL PLANS AND ENERGY
 CALCULATIONS ARE BEING RETAINED BY THIS OFFICE FOR PEER
 REVIEW AND WILL BE PLACED WITH PREVIOUS RETAINED
 PLANS.
 PLEASE KNOW THE FEE AS REQUIRED PER FLORIDA STATUTES
 THE FEE OF $18,600.00 HAS BEEN ASSESSED PENDING PEER
 REVIEW. THIS WOULD BE DUE BEFORE RESUBMISSION OF PLANS
 FOR THE 4TH REVIEW.
 IT IS STRONGLY SUGGESTED TO OVER ALL PLANS AND
 CALCULATIONS BEFORE RESUBMITTING PLANS FOR THE
 FOLLOWING REVIEW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]