| 2007-09-18 19:40:57 | CARLTON FIELDS |
| | CITY PLACE OFFICE TOWER |
| | SEPT 18, 2007 |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07030281 |
| | ADD: 525 OKEECHOBEE BLVD/SUITE 1200 |
| | CONT: CENTEX CONSTRUCTION |
| | TEL: (954)214-9415 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 3RDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS |
| | NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE |
| | OF COMMENCEMENT |
| | AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)IT APPEARS THE ARCHITECTURAL SHEETS ARE CODE |
| | COMPLIANT, THE STRUCTURAL SHEET S00-01 INDICATES |
| | TESTING AND INSPECTIONS ARE TO BE MADE BY AN APPROVED |
| | TESTING LABORATORY SELECTED BY AND PAID BY THE OWNER. |
| | THIS IS WHERE DOCUMENTS FOR A THRESHOLD INSPECTOR ARE |
| | TO SIGNED AND SUBMITTED TO HAROLD PISKURA BEFORE A |
| | PERMIT WILL BE ISSUED. WPB AMENDMENT 105.13.6. |
| | W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561) 805-6711 FOR FURTHER INFORMATION AND |
| | APPOINTMENT BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 3A)105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A "STRUCTURAL |
| | INSPECTION PLAN" |
| | PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 3B) THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE |
| | OF COMPLETION, THE STRUCTURAL PLANS FOR THIS TENANT |
| | SPACE SHALL BE REVIEWED BY THE ENGINEER OF RECORD FOR |
| | THE " BASE BUILDING" |
| | AND BE STAMPED WITH THEIR SHOP DRAWING STAMP THEY ARE |
| | APPROVING THE PLANS AND WORK TO BE COMPLETED UNDER THIS |
| | PERMIT BEFORE THEIR CERTIFICATE OF COMPLETION HAS BEEN |
| | ISSUED. |
| | |
| | 3C) THE SAME HOLDS TRUE FOR THE ARCHITECTURAL SHEETS, |
| | THE DESIGNER OF RECORD FOR THE BUILDING SHALL REVIEW |
| | AND AFFIX THEIR SHOP DRAWING STAMP TO THESE PLANS WITH |
| | THEIR APPROVAL. |
| | |
| | 3D) SINCE THERE WILL NEED TO BE A THRESHOLD INSPECTOR |
| | ON SITE, A THIRD SET OF PLANS, SUBMITTALS AND OR OTHER |
| | DOCUMENTS WILL NEED TO BE SUBMITTED BEFORE ISSUANCE OF |
| | THIS PERMIT. |
| | |
| | 3E) SINCE THE STEEL BEAMS ARE NEW ELEMENTS AND NEED TO |
| | INDICATE FIRE PROOFING AS TO TABLE 601 FLOOR AND BEAM 3 |
| | HR RATING SEE FOOTNOTE "G" 1 HR REDUCTION FOR FIRE |
| | SPRINKLED BUILDINGS. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |