Plan Review Notes
Plan Review Notes For Permit 07030281
Permit Number 07030281
Review Stop P
Sequence Number 2
Notes
Date Text
2007-04-07 16:28:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WEST PALM BEACH MUNICIPAL CODE
  
 1. ALL ARCHITECTURAL SHEETS THE BUSINESS LICENSE FOR
 JOVA/DANIELS/BUSBY INC IS SHOWN AS DELINQUENT. ( SEE
 ATTACHED SHEET ).
  
 2. PLANS SHALL BE SUBMITTED IN TWO COMPLETE BOUND SETS.
 LOOSE SHEETS ARE NOT APPROVED. SECTION 106.1.
  
 3. A00-00 PROJECT INFORMATION INDICATES THIS TO BE A 20
 STORY BUILDING. BUILDING WAS PERMITTED AS A 16 STORY.
 PLEASE CORRELATE INFORMATION. SECTION 106.1.1.
  
 4. ALL ARCHITECTURAL SHEET SHALL BE SEALED BY AN
 IMPRESSION TYPE SEAL THAT SHALL IMPRESS ALL INFORMATION
 REQUIRED BY FAC 61G1-16.002 ON EACH SHEET. FAC
 61G1-16.001 AND FS 481.2055.
  
 5. SHT A13.01 ALL 4 SINKS SHALL BE ACCESSIBLE. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 EXPOSED PIPES & SURFACES
 E. 11-4.24.6 FAUCETS
 NOTE: CLEAR FLOOR SPACE SHALL BE FORWARD APPROACH AND
 EXTEND A MAXIMUM 19" UNDERNEATH THE SINK. CABINET DOORS
 ARE NOT APPROVED IN THE CLEAR FLOOR SPACE AND SHALL BE
 DELETED FROM THE DETAILS FOR EACH SINK.
  
 6. SHT P-0.1 FLOOR DRAINS ARE NOT AN APPROVED INDIRECT
 WASTE RECEPTOR FOR THE WATER HEATER, NOR THE ICE MAKER.
 DETAIL #2 SHALL SHOW A FLOOR SINK OR A HUB DRAIN FOR
 THE INDIRECT WASTE. SECTIONS 802.1.1, 803.2, 802.3 &
 802.3.2.
  
 7. SHT P-0.1 PLUMBING GENERAL NOTES #3 CODE ADOPTED IS
 FBC-2004 WITH AMENDMENTS. SHOWN IN NOTE #3 IS THE 2000
 IPC. PLEASE CHANGE REFERENCE AND DESIGN TO THE CORRECT
 CODE.
  
 8. SHT H-0.3 DETAIL #3 A/C CONDENSATE TO THE FLOOR
 DRAIN IS NOT APPROVED TO THE SANITARY SEWER. MUNICIPAL
 CODE WWF, ART. III SEWERS AND SEWAGE DISPOSAL SECTION
 90-125(B)(5). CONDENSATE SHALL CONNECT TO A DEDICATED
 CONDENSATE LINE OR DISCHARGE SEPARATELY OUT OF THE
 BUILDING AND DRAIN INTO A CATCH BASIN, A STORM LINE OR
 A DRYWELL.
  
 9. SHT P1.1 SHOWS TWO ADDED DRINKING FOUNTAINS NOT
 SHOWN ON THE FLOOR PLAN, (A-03.12). PLEASE CORRELATE
 INFORMATION BETWEEN THE ARCHITECTURAL SHEETS AND THE
 PLUMBING SHEETS. SECTION 106.1.1.
  
 10. SUBMIT ISOMETRIC RISER DIAGRAMS FOR THE WATER, DWV,
 AND CONDENSATE. SHOW ALL PIPE SIZES, VALVES & WATER
 HAMMER ARRESTORS, (REQUIRED BY SECTION 604.9), ON THE
 WATER RISER DIATRAM. SHOW ALL PIPE SIZES TRAPS AND
 VENTS FOR THE DWV. SHOW THE PIPE SIZE AND THE
 TERMINATION POINT FOR THE CONDENSATE. INDICATE THE
 LOCATION OF THE POINT OF CONNECTION FOR THE WATER AND
 THE SANITARY. SECTION 106.3.5.1.3((3)(4)(6)(19)(13).
  
 11. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAIN. SHOW COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS.
  
 12. AHA CONSULTING ENGINEERS SHALL INDICATE THE
 CERTIFICATE OF AUTHORIZATION NUMBER IN THE TITLE BLOCK.
 FAC 61G15-23.002(2) & FS 471.025. CA NUMBER 56959
 WRITTEN IN UNDER THE SEAL DOES NOT INDICATE AS A CA
 NUMBER FOR THE ENGINEERING FIRM. PLEASE CLARIFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]