Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-08-09 13:40:03*****DENIED*****
  
 PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED;HOWEVER THE COMMENTS BELOW ARE BASED UPON
 THE THE NEW FIRE PROTECTION SHEETS SUBMITTED.
  
  
 NEW COMMENTS
  
 A.ON DRAWING NUMBER A00-00 UNDER THE APPLICABLE CODES
 AND REFERENCES SECTION, THE 2002 EDITION OF NFPA 72 IS
 TO BE REFERENCED AS THE NATIONAL FIRE ALARM CODE.
  
 B.NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
 SYSTEMS, 2002 EDITION -SHALL BE REFERENCED.
  
 C.PLEASE SEE THE ELECTRICAL PLAN REVIEWER COMMENT #3
 IN REFERENCE TO TITLE BLOCK INFORMATION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-6722