| 2007-06-27 12:44:14 | |
| | *** UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. |
| | ** PLEASE ALSO SEE THERE SOME NEW COMMENTS BASED ON |
| | CHANGES AND REVISIONS TO PLANS WHICH WERE NOT SUBMITTED |
| | ON THE PREVIOUS REVIEW. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE PLANS (ARCHITECTURAL) INDICATE |
| | THE BUILDING NOW AS A 16 STORY BUILDING HOWEVER THE |
| | ENERGY CALCULATIONS INDICATE 15 STORIES. |
| | PLEASE COORDINATE THESE. |
| | FBC 106.1.2, 13-415.1.AB.1.1 |
| | |
| | 2) NOTE: PLEASE SEE THE COMMENT RESPONSES WHICH STATE |
| | THE PREVIOUS REVIEW COMMENTS FROM EACH REVIEWER AND |
| | THEN THE RESPONSE FROM THE DESIGN TEAM. PLEASE SEE |
| | THERE ARE SEVERAL ELECTRICAL COMMENTS WHICH DO NOT |
| | DELINEATE THE NOTE WHICH WAS TYPED BY THIS REVIEWER. IF |
| | THE NOTES ARE TO BE QUOTED, PLEASE SEE THESE ARE NOT |
| | MATCHING. PLEASE SEE THERE ARE CODE SECTIONS WHICH WERE |
| | INDICATED ON RESPONSE SHEETS WHICH ARE NOT WHAT WAS |
| | TYPED IN THE REVIEW. PLEASE SEE COMMENT #13 FOR |
| | EXAMPLE. |
| | IF THE COMMENT RESPONSES ARE GOING TO INDICATE THE |
| | REVIEWER'S COMMENTS, PLEASE BE SURE TO STATE THE |
| | COMMENT(S) AS MADE. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEAS SEE THE NEW FP SHEETS AS SUBMITTED ARE |
| | MISSING THE PRINTED NAME, PRINTED LICENSE NUMBER AND |
| | THE CERTIFICATE OF AUTHORIZATION NUMBER ON TITLE BLOCKS |
| | AS REQUIRED PER FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002 AND FLORIDA STATUTES 471.023. |
| | IF THE CONTRACTOR AS STATED IS OFFERING ENGINEERING |
| | SERVICES THEN THEY ARE REQUIRED TO BE LICENSED UNDER |
| | THE FLORIDA STATUTES. |
| | ** THIS COMMENT IS MADE AND REQUIRED WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER TRADE(S). |
| | |
| | 4) NOTE: PLEASE SEE NOT ALL TITLE BLOCKS ON SHEETS FOR |
| | THE ARCHITECTURAL FIRM CONTAIN THE PRINTED CERTIFICATE |
| | OF AUTHORIZATION NUMBER. |
| | PLEASE SEE PREVIOUS COMMENTS AS THIS IS REQUIRED ON ALL |
| | SHEETS WHICH CONTAIN THE TITLE BLOCK FOR SAID FIRM. FAC |
| | 61G1-16.004, FS481.219 |
| | ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | ** PREVIOUS REVIEW NOTES* |
| | PLEASE SEE THE MISSING INFORMATION ON THE TITLE BLOCKS |
| | FOR THE ARCHITECTURAL FIRM AS REQUIRED UNDER THE FAC |
| | 61G1-16.004 AND FS 481.219 |
| | * THIS IS REQUIRED FOR ALL SHEETS INCLUDING TRADE |
| | SHEETS WHICH CONTAIN THE SAME TITLE BLOCKS. |
| | |
| | |
| | 5) NOTE: PLEASE SEE THE MEP SHEETS. PLEASE SEE MANY OF |
| | THESE WERE NOT DATED WHEN SIGNED, AND SEALED. PLEASE |
| | SEE NUMEROUS SHEETS WHICH CONTAIN AS MANY AS THREE |
| | COMPLETELY DIFFERENT SIGNATURES FOR THE SAME ENGINEER |
| | OF RECORD. |
| | PLEASE KNOW PLANS ARE BEING RETAINED BY THIS OFFICE FOR |
| | POSSIBLE REVIEW FROM THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS AND LEGAL COUNSEL TO THE BOARD. |
| | PLEASE SUBMIT COMPLETED NOTARIZED LETTER FOR SIGNATURE |
| | VERIFICATION WHICH WILL BE REQUIRED TO BE SIGNED, |
| | DATED, SEALED AND NOTARIZED. |
| | PLEASE ALSO SUBMIT PHOTO-IDENTIFICATION WHICH CONTAINS |
| | THE SIGNATURE OF THE ENGINEER. PLEASE KNOW AT THIS TIME |
| | DUE TO THE MULTIPLE SIGNATURES, THIS OFFICE CAN VERIFY |
| | WHICH ONE IS CORRECT. |
| | PLEASE SEE THE FAC 61G15-23.002 AND FS 471.025 AS THE |
| | ENGINEER OF RECORD SHALL BE THE ONLY ONE TO SIGN |
| | PLANS. |
| | |
| | ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 6) NOTE: PLEASE SEE THE ADDRESS AS LISTED ON TITLE |
| | BLOCKS FOR THE ENGINEERING FIRM AS SHOWN ON THE STATE |
| | WEBSITE. |
| | PLEASE SEE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATION WEBSITE. |
| | ** AS THE MAIN OFFICE IS LISTED ON WEBSITE AND THIS IS |
| | A *SATELLITE OFFICE* PLEASE KNOW THAT THE PRIMARY |
| | ADDRESS WOULD STAY AND BE OK, HOWEVER NEED TO ADD TO |
| | PLANS. |
| | FAC 61G15-23.002 |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH STATED THE |
| | MINIMUM CODES TO BE STATED ON PLANS FOR ARCHITECTURAL |
| | AND ELECTRICAL SHEETS. PLEASE SEE RESPONSE FROM BOTH |
| | FIRMS STATE THIS WOULD BE DONE WHOEVER PLEASE SEE THE |
| | FOLLOWING WHICH WAS NOT CORRECTED. |
| | PLEASE SEE THE ARCHITECTURAL COVER SHEET WHICH STATES |
| | THE FOLLOWING: |
| | A) STATES: 2002 FLORIDA ELECTRICAL CODE NFPA-70. (THIS |
| | SHOULD BE THE NATIONAL ELECTRICAL CODE AND SHOULD BE |
| | THE 2005 EDITION AS PREVIOUSLY STATED. |
| | B) STATES: NATIONAL FIRE ALARM CODE AS 2005 NFPA-70. |
| | (THIS IS THE NEC AND SHOULD BE NATIONAL FIRE ALARM CODE |
| | NFPA-72 AND THE EDITION IS THE 2002. |
| | C) STATES: NATIONAL FIRE ALARM CODE AS THE 2003 |
| | NFPA-101. (THIS IS NOTED IN *B* ABOVE. THE NFPA-101 |
| | 2003 WHICH IS THE LIFE SAFETY CODE IS STATED. PLEASE |
| | SEE THE ELECTRICAL SHEET E-0.1: |
| | A) STATES: THE 2002 NFPA-70 (NEC) ( THIS SHOULD BE THE |
| | 2005 NFPA-70 AS PREVIOUSLY STATED IN PREVIOUS REVIEW |
| | NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE THAT ALL OF THE CODES WHICH PLANS ARE UNDER |
| | DESIGN AND RECORD SHALL BE STATED ON PLANS AS FOLLOWS. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | * PLEASE SEE THE ARCHITECTURAL SHEETS WHICH STATE SOME |
| | OF THE OLDER CODES. |
| | ** THESE ARE REQUIRED FOR THE REVIEWER AT A MINIMUM AND |
| | OTHER CODES WILL BE REQUIRED FOR OTHER TRADES. |
| | |
| | 8) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE STILL |
| | MISSING THE *OWNER AGENT* SIGNATURE. PLEASE ALSO SEE |
| | THESE WERE NOT DATED WHEN SIGNED, AND SEALED. PLEASE |
| | SEE COMMENTS WITH RESPECT TO THE ENGINEER'S SIGNATURE |
| | ALONG WITH COMMENTS WITH RESPECT TO THE ENERGY |
| | CALCULATIONS. PLEASE SEE FBC 13-103.1.1.1, FS471.025, |
| | FS 481.221 |
| | |
| | 9) NOTE:PLEASE SEE THE EMERGENCY LIGHTING IS BEING |
| | SHOWN COMING FROM A PANEL LOCATION WHICH IS NOT SHOWN |
| | AS ACCESSIBLE OR IN THE SAME ELECTRICAL ROOM AS OTHER |
| | ELECTRICAL EQUIPMENT FOR THE SAME TENANT. PLEASE SEE |
| | THE LOCATION OF THIS EQUIPMENT AND PANELS ARE NOT |
| | KNOWN. PLEASE SEE THE LIGHTING NOTES WHICH STATE THESE |
| | ARE BEING FED FROM THE11TH FLOOR AND YET THE RISER |
| | SHOWS THESE BEING FED FROM THE 10TH FLOOR? IN EITHER |
| | CASE IF THE DISCONNECTING MEANS/PANEL (EL212A)/OVER |
| | CURRENT PROTECTION ARE LOCATED ON THE 12TH FLOOR IN THE |
| | ELECTRICAL ROOM THIS WOULD BE ACCEPTABLE. |
| | 240.24, 240.21, ETC. |
| | FBC ADMIN SECTION 104.6 |
| | |
| | 10) NOTE: PLEASE SEE THE BASE BUILDING PLANS INDICATE |
| | THE CIRCUIT AND LIGHTING FOR THE COMMON AREA AND |
| | CORRIDORS DIFFERENT THAN THE BUILD-OUT PLANS. PLEASE |
| | SEE THE BUILD OUT IS NOW INCLUDING THIS COMMON AREA AS |
| | PART OF THE TENANT BUILD-OUT?? PLEASE PROVIDE ALL |
| | INFORMATION ON THE CHANGES OF THESE PROPOSED DESIGNS. |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES. PLEASE |
| | BASE BUILDING PERMITTED PLANS WHICH INDICATE THE COMMON |
| | AREA IS BEING SHOWN AND DONE UNDER THE BASE BUILDING. |
| | PLEASE KNOW THAT ANY AND ALL CHANGES ON THE BUILD-OUT |
| | BEFORE CO OF THE BASE BUILDING WILL REQUIRE THE PLANS |
| | TO BE REVISED ALONG WITH ENERGY CALCULATIONS. |
| | FBC 106.1.2 |
| | |
| | 12) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS |
| | ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS |
| | FOLLOWS. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | * PLEASE SEE THE ARCHITECTURAL SHEETS WHICH STATE SOME |
| | OF THE OLDER CODES. |
| | ** THESE ARE REQUIRED FOR THE REVIEWER AT A MINIMUM AND |
| | OTHER CODES WILL BE REQUIRED FOR OTHER TRADES. |
| | |
| | 13) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS |
| | SUBMITTED DOSO NOT CORRELATE WITH THE PLANS AND THE |
| | FIXTURE LEGEND. |
| | PLEASE SE THE WATTAGE FOR THE SAME TYPE OF FIXTURES ARE |
| | BEING SHOWN AS TWO DIFFERENT LEVELS. |
| | PLEASE SEE THE NUMBER OF FIGURE FOR SPECIFIC ROOMS DO |
| | NOT ALL CORRELATE. |
| | PLEASE PROVIDE THE DESIGNATIONS ON THE ENERGY |
| | CALCULATIONS WHICH COORDINATES WITH PLANS OR THE |
| | DESIGNATIONS ON PLANS TO CORRELATE WITH THE ENERGY |
| | CALCULATIONS. PLEASE SEE THE DESIGNATIONS, AMOUNT OF |
| | ROOMS, AMOUNT OF LUMINARIES ETC FOR THE N.E> ZONE DOES |
| | NOT CORRELATE WITH PLANS. (OTHER AREAS ALSO). PLEASE |
| | PROVIDE MOTE INFORMATION FOR THESE INCLUDING NOTE BELOW |
| | WITH RESPECT TO EMERGENCY LIGHTING AND CIRCUITING. |
| | PLEASE BE SURE THE SQ FT LEVELS COORDINATE BASED ON |
| | AREA USED ON PLANS AND ENERGY CALCULATIONS. |
| | PLEASE SEE 13-415.2, 13-415.1.A |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.PLEASE SEE |
| | SOME AREAS/LOCATIONS WHICH DO NOT SEEM TO INDICATE ANY |
| | LIGHTING CONTROLS. PLEASE SEE MAXIMUM LIGHTING CONTROL |
| | OF 25K SQ FT. PLEASE SEE ONLY ONE LIGHTING CONTROL |
| | PANEL IS BEING NOTED. |
| | PLEASE PROVIDE LOCATIONS AND MORE DETAIL OF THE OVER |
| | RIDES DEVICES AND HOW THEY ARE BEING PART OF THE |
| | *SYSTEM*. |
| | PLEASE PROVIDE ESTIMATED SCHEDULING. |
| | PLEASE SEE THE ENERGY CALCULATIONS INDICATE MANUAL |
| | CONTROLS FOR ALL LIGHTING CONTROL WHERE THIS SHOULD |
| | INDICATE THE ACTUAL DEVICES/SYSTEM ON PLANS. PLEASE SEE |
| | THAT THE LOCATIONS FOR ALL OVER RIDES DEVICES SHALL BE |
| | LOCATED SO THAT THE OCCUPANT CAN VISUALLY SEE THE |
| | LIGHTING WHICH IS BEING CONTROLLED. PLEASE PROVIDE MORE |
| | INFORMATION. |
| | PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. PLEASE SEE |
| | 13-415.1.AB.1; PLEASE SEE ENERGY CALCULATIONS FOR BUILD |
| | OUT OF SPACE WHICH DOES NOT CORRELATE WITH THE LIGHTING |
| | PLANS, FIXTURES, WATTAGES, NUMBER OF FIXTURES ETC. |
| | PLEASE SEE THERE ARE SEVERAL LIGHTING FIXTURES WHICH DO |
| | NOT CORRELATE WITH THE ELECTRICAL PLANS AND FIXTURE |
| | LEGEND. |
| | |
| | PLEASE SEE 13-415.2 AS LIGHTING POWER DENSITIES ARE NOT |
| | INDICATED FOR ALL AREAS. PLEASE BE SURE TO CORRELATE |
| | THIS WITH THE ENERGY CALCULATIONS WHICH ARE TO BE |
| | SUBMITTED. |
| | * PLEASE SEE ALL OF CHAPTER 13. |
| | PLEASE BE SURE ALL TO SEE 13-103.1.1.1 |
| | |
| | 14) NOTE: PLEASE SEE 700.12F OF THE 2005 NEC. PLEASE |
| | PROVIDE MORE INFORMATION ON HOW THIS PROPOSED DESIGN ON |
| | PLANS FOR SINGLE CIRCUIT OR SEPARATE SPACE AREAS MEETS |
| | THIS SECTION OF THE NEC. |
| | |
| | |
| | 15) NOTE: PLEASE SEE ATTACHED SHEET WITH RESPECT TO FS |
| | 553.80(2)(B). THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |