Plan Review Notes
Plan Review Notes For Permit 07030281
Permit Number 07030281
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-27 12:44:14 
 *** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE ALSO SEE THERE SOME NEW COMMENTS BASED ON
 CHANGES AND REVISIONS TO PLANS WHICH WERE NOT SUBMITTED
 ON THE PREVIOUS REVIEW.
  
  
  
 1) NOTE: PLEASE SEE THE PLANS (ARCHITECTURAL) INDICATE
 THE BUILDING NOW AS A 16 STORY BUILDING HOWEVER THE
 ENERGY CALCULATIONS INDICATE 15 STORIES.
 PLEASE COORDINATE THESE.
 FBC 106.1.2, 13-415.1.AB.1.1
  
 2) NOTE: PLEASE SEE THE COMMENT RESPONSES WHICH STATE
 THE PREVIOUS REVIEW COMMENTS FROM EACH REVIEWER AND
 THEN THE RESPONSE FROM THE DESIGN TEAM. PLEASE SEE
 THERE ARE SEVERAL ELECTRICAL COMMENTS WHICH DO NOT
 DELINEATE THE NOTE WHICH WAS TYPED BY THIS REVIEWER. IF
 THE NOTES ARE TO BE QUOTED, PLEASE SEE THESE ARE NOT
 MATCHING. PLEASE SEE THERE ARE CODE SECTIONS WHICH WERE
 INDICATED ON RESPONSE SHEETS WHICH ARE NOT WHAT WAS
 TYPED IN THE REVIEW. PLEASE SEE COMMENT #13 FOR
 EXAMPLE.
 IF THE COMMENT RESPONSES ARE GOING TO INDICATE THE
 REVIEWER'S COMMENTS, PLEASE BE SURE TO STATE THE
 COMMENT(S) AS MADE.
 FBC 106.1.2
  
 3) NOTE: PLEAS SEE THE NEW FP SHEETS AS SUBMITTED ARE
 MISSING THE PRINTED NAME, PRINTED LICENSE NUMBER AND
 THE CERTIFICATE OF AUTHORIZATION NUMBER ON TITLE BLOCKS
 AS REQUIRED PER FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 AND FLORIDA STATUTES 471.023.
 IF THE CONTRACTOR AS STATED IS OFFERING ENGINEERING
 SERVICES THEN THEY ARE REQUIRED TO BE LICENSED UNDER
 THE FLORIDA STATUTES.
 ** THIS COMMENT IS MADE AND REQUIRED WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE(S).
  
 4) NOTE: PLEASE SEE NOT ALL TITLE BLOCKS ON SHEETS FOR
 THE ARCHITECTURAL FIRM CONTAIN THE PRINTED CERTIFICATE
 OF AUTHORIZATION NUMBER.
 PLEASE SEE PREVIOUS COMMENTS AS THIS IS REQUIRED ON ALL
 SHEETS WHICH CONTAIN THE TITLE BLOCK FOR SAID FIRM. FAC
 61G1-16.004, FS481.219
 ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 ** PREVIOUS REVIEW NOTES*
 PLEASE SEE THE MISSING INFORMATION ON THE TITLE BLOCKS
 FOR THE ARCHITECTURAL FIRM AS REQUIRED UNDER THE FAC
 61G1-16.004 AND FS 481.219
 * THIS IS REQUIRED FOR ALL SHEETS INCLUDING TRADE
 SHEETS WHICH CONTAIN THE SAME TITLE BLOCKS.
  
  
 5) NOTE: PLEASE SEE THE MEP SHEETS. PLEASE SEE MANY OF
 THESE WERE NOT DATED WHEN SIGNED, AND SEALED. PLEASE
 SEE NUMEROUS SHEETS WHICH CONTAIN AS MANY AS THREE
 COMPLETELY DIFFERENT SIGNATURES FOR THE SAME ENGINEER
 OF RECORD.
 PLEASE KNOW PLANS ARE BEING RETAINED BY THIS OFFICE FOR
 POSSIBLE REVIEW FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS AND LEGAL COUNSEL TO THE BOARD.
 PLEASE SUBMIT COMPLETED NOTARIZED LETTER FOR SIGNATURE
 VERIFICATION WHICH WILL BE REQUIRED TO BE SIGNED,
 DATED, SEALED AND NOTARIZED.
 PLEASE ALSO SUBMIT PHOTO-IDENTIFICATION WHICH CONTAINS
 THE SIGNATURE OF THE ENGINEER. PLEASE KNOW AT THIS TIME
 DUE TO THE MULTIPLE SIGNATURES, THIS OFFICE CAN VERIFY
 WHICH ONE IS CORRECT.
 PLEASE SEE THE FAC 61G15-23.002 AND FS 471.025 AS THE
 ENGINEER OF RECORD SHALL BE THE ONLY ONE TO SIGN
 PLANS.
  
 ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADES.
  
 6) NOTE: PLEASE SEE THE ADDRESS AS LISTED ON TITLE
 BLOCKS FOR THE ENGINEERING FIRM AS SHOWN ON THE STATE
 WEBSITE.
 PLEASE SEE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION WEBSITE.
 ** AS THE MAIN OFFICE IS LISTED ON WEBSITE AND THIS IS
 A *SATELLITE OFFICE* PLEASE KNOW THAT THE PRIMARY
 ADDRESS WOULD STAY AND BE OK, HOWEVER NEED TO ADD TO
 PLANS.
 FAC 61G15-23.002
  
 7) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH STATED THE
 MINIMUM CODES TO BE STATED ON PLANS FOR ARCHITECTURAL
 AND ELECTRICAL SHEETS. PLEASE SEE RESPONSE FROM BOTH
 FIRMS STATE THIS WOULD BE DONE WHOEVER PLEASE SEE THE
 FOLLOWING WHICH WAS NOT CORRECTED.
 PLEASE SEE THE ARCHITECTURAL COVER SHEET WHICH STATES
 THE FOLLOWING:
 A) STATES: 2002 FLORIDA ELECTRICAL CODE NFPA-70. (THIS
 SHOULD BE THE NATIONAL ELECTRICAL CODE AND SHOULD BE
 THE 2005 EDITION AS PREVIOUSLY STATED.
 B) STATES: NATIONAL FIRE ALARM CODE AS 2005 NFPA-70.
 (THIS IS THE NEC AND SHOULD BE NATIONAL FIRE ALARM CODE
 NFPA-72 AND THE EDITION IS THE 2002.
 C) STATES: NATIONAL FIRE ALARM CODE AS THE 2003
 NFPA-101. (THIS IS NOTED IN *B* ABOVE. THE NFPA-101
 2003 WHICH IS THE LIFE SAFETY CODE IS STATED. PLEASE
 SEE THE ELECTRICAL SHEET E-0.1:
 A) STATES: THE 2002 NFPA-70 (NEC) ( THIS SHOULD BE THE
 2005 NFPA-70 AS PREVIOUSLY STATED IN PREVIOUS REVIEW
 NOTES.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THAT ALL OF THE CODES WHICH PLANS ARE UNDER
 DESIGN AND RECORD SHALL BE STATED ON PLANS AS FOLLOWS.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 * PLEASE SEE THE ARCHITECTURAL SHEETS WHICH STATE SOME
 OF THE OLDER CODES.
 ** THESE ARE REQUIRED FOR THE REVIEWER AT A MINIMUM AND
 OTHER CODES WILL BE REQUIRED FOR OTHER TRADES.
  
 8) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE STILL
 MISSING THE *OWNER AGENT* SIGNATURE. PLEASE ALSO SEE
 THESE WERE NOT DATED WHEN SIGNED, AND SEALED. PLEASE
 SEE COMMENTS WITH RESPECT TO THE ENGINEER'S SIGNATURE
 ALONG WITH COMMENTS WITH RESPECT TO THE ENERGY
 CALCULATIONS. PLEASE SEE FBC 13-103.1.1.1, FS471.025,
 FS 481.221
  
 9) NOTE:PLEASE SEE THE EMERGENCY LIGHTING IS BEING
 SHOWN COMING FROM A PANEL LOCATION WHICH IS NOT SHOWN
 AS ACCESSIBLE OR IN THE SAME ELECTRICAL ROOM AS OTHER
 ELECTRICAL EQUIPMENT FOR THE SAME TENANT. PLEASE SEE
 THE LOCATION OF THIS EQUIPMENT AND PANELS ARE NOT
 KNOWN. PLEASE SEE THE LIGHTING NOTES WHICH STATE THESE
 ARE BEING FED FROM THE11TH FLOOR AND YET THE RISER
 SHOWS THESE BEING FED FROM THE 10TH FLOOR? IN EITHER
 CASE IF THE DISCONNECTING MEANS/PANEL (EL212A)/OVER
 CURRENT PROTECTION ARE LOCATED ON THE 12TH FLOOR IN THE
 ELECTRICAL ROOM THIS WOULD BE ACCEPTABLE.
 240.24, 240.21, ETC.
 FBC ADMIN SECTION 104.6
  
 10) NOTE: PLEASE SEE THE BASE BUILDING PLANS INDICATE
 THE CIRCUIT AND LIGHTING FOR THE COMMON AREA AND
 CORRIDORS DIFFERENT THAN THE BUILD-OUT PLANS. PLEASE
 SEE THE BUILD OUT IS NOW INCLUDING THIS COMMON AREA AS
 PART OF THE TENANT BUILD-OUT?? PLEASE PROVIDE ALL
 INFORMATION ON THE CHANGES OF THESE PROPOSED DESIGNS.
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES. PLEASE
 BASE BUILDING PERMITTED PLANS WHICH INDICATE THE COMMON
 AREA IS BEING SHOWN AND DONE UNDER THE BASE BUILDING.
 PLEASE KNOW THAT ANY AND ALL CHANGES ON THE BUILD-OUT
 BEFORE CO OF THE BASE BUILDING WILL REQUIRE THE PLANS
 TO BE REVISED ALONG WITH ENERGY CALCULATIONS.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS
 ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS
 FOLLOWS.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 * PLEASE SEE THE ARCHITECTURAL SHEETS WHICH STATE SOME
 OF THE OLDER CODES.
 ** THESE ARE REQUIRED FOR THE REVIEWER AT A MINIMUM AND
 OTHER CODES WILL BE REQUIRED FOR OTHER TRADES.
  
 13) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED DOSO NOT CORRELATE WITH THE PLANS AND THE
 FIXTURE LEGEND.
 PLEASE SE THE WATTAGE FOR THE SAME TYPE OF FIXTURES ARE
 BEING SHOWN AS TWO DIFFERENT LEVELS.
 PLEASE SEE THE NUMBER OF FIGURE FOR SPECIFIC ROOMS DO
 NOT ALL CORRELATE.
 PLEASE PROVIDE THE DESIGNATIONS ON THE ENERGY
 CALCULATIONS WHICH COORDINATES WITH PLANS OR THE
 DESIGNATIONS ON PLANS TO CORRELATE WITH THE ENERGY
 CALCULATIONS. PLEASE SEE THE DESIGNATIONS, AMOUNT OF
 ROOMS, AMOUNT OF LUMINARIES ETC FOR THE N.E> ZONE DOES
 NOT CORRELATE WITH PLANS. (OTHER AREAS ALSO). PLEASE
 PROVIDE MOTE INFORMATION FOR THESE INCLUDING NOTE BELOW
 WITH RESPECT TO EMERGENCY LIGHTING AND CIRCUITING.
 PLEASE BE SURE THE SQ FT LEVELS COORDINATE BASED ON
 AREA USED ON PLANS AND ENERGY CALCULATIONS.
 PLEASE SEE 13-415.2, 13-415.1.A
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.PLEASE SEE
 SOME AREAS/LOCATIONS WHICH DO NOT SEEM TO INDICATE ANY
 LIGHTING CONTROLS. PLEASE SEE MAXIMUM LIGHTING CONTROL
 OF 25K SQ FT. PLEASE SEE ONLY ONE LIGHTING CONTROL
 PANEL IS BEING NOTED.
 PLEASE PROVIDE LOCATIONS AND MORE DETAIL OF THE OVER
 RIDES DEVICES AND HOW THEY ARE BEING PART OF THE
 *SYSTEM*.
 PLEASE PROVIDE ESTIMATED SCHEDULING.
 PLEASE SEE THE ENERGY CALCULATIONS INDICATE MANUAL
 CONTROLS FOR ALL LIGHTING CONTROL WHERE THIS SHOULD
 INDICATE THE ACTUAL DEVICES/SYSTEM ON PLANS. PLEASE SEE
 THAT THE LOCATIONS FOR ALL OVER RIDES DEVICES SHALL BE
 LOCATED SO THAT THE OCCUPANT CAN VISUALLY SEE THE
 LIGHTING WHICH IS BEING CONTROLLED. PLEASE PROVIDE MORE
 INFORMATION.
 PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. PLEASE SEE
 13-415.1.AB.1; PLEASE SEE ENERGY CALCULATIONS FOR BUILD
 OUT OF SPACE WHICH DOES NOT CORRELATE WITH THE LIGHTING
 PLANS, FIXTURES, WATTAGES, NUMBER OF FIXTURES ETC.
 PLEASE SEE THERE ARE SEVERAL LIGHTING FIXTURES WHICH DO
 NOT CORRELATE WITH THE ELECTRICAL PLANS AND FIXTURE
 LEGEND.
  
 PLEASE SEE 13-415.2 AS LIGHTING POWER DENSITIES ARE NOT
 INDICATED FOR ALL AREAS. PLEASE BE SURE TO CORRELATE
 THIS WITH THE ENERGY CALCULATIONS WHICH ARE TO BE
 SUBMITTED.
 * PLEASE SEE ALL OF CHAPTER 13.
 PLEASE BE SURE ALL TO SEE 13-103.1.1.1
  
 14) NOTE: PLEASE SEE 700.12F OF THE 2005 NEC. PLEASE
 PROVIDE MORE INFORMATION ON HOW THIS PROPOSED DESIGN ON
 PLANS FOR SINGLE CIRCUIT OR SEPARATE SPACE AREAS MEETS
 THIS SECTION OF THE NEC.
  
  
 15) NOTE: PLEASE SEE ATTACHED SHEET WITH RESPECT TO FS
 553.80(2)(B). THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-27 07:06:00REVIEW IN PROGRESS
2007-06-26 18:55:01PLANS IN ELECTRIC FOR REVIEW.