Plan Review Notes
Plan Review Notes For Permit 07030281
Permit Number 07030281
Review Stop E
Sequence Number 11
Notes
Date Text
2008-07-15 15:49:54** DENIEDREVISIONS **
  
  
 1) NOTE:PLEASE SEE REVISION LABELED 7, 8 AND 9 ON
 DP11 LOAD SUMMARY DO NOT ACTUALLY REVISE THE LOADS.
 THESE ARE THE SAME AS SUBMITTED ON REVISIONS DATED
 3/27/08. THE LOADS HAVE NOT CHANGED.
 PLEASE BE SURE THE DP11 SCHEDULE REFLECT M411 NOT M412.
 THIS WAS CORRECTED ON THE RISER SEVERAL REVISIONS AGO
 HOWEVER NOT REVISED ON SCHEDULE.
 PLEASE EXPLAIN WHY THE LOAD ON M411 HAS NOW INCREASED
 BUT THE LOADS SHOWN ON DP11 ARE THE SAME AS PREVIOUS
 REVISIONS IN WHICH LOAD ON M411 WERE LOWER.
 NEC 220.
  
 FBC 106.1.1, 106.1.2, 106.5 FOR CLARITY, ADDITIONAL
 INFORMATION AND RECORD COORDINATION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]