| Plan Review Notes For Permit 07030281 |
| Permit Number |
07030281 |
|
| Review Stop |
E |
| Sequence Number |
11 |
|
| Notes |
| Date |
Text |
| 2008-07-15 15:49:54 | ** DENIEDREVISIONS ** | | | | | | | | | 1) NOTE:PLEASE SEE REVISION LABELED 7, 8 AND 9 ON | | | DP11 LOAD SUMMARY DO NOT ACTUALLY REVISE THE LOADS. | | | THESE ARE THE SAME AS SUBMITTED ON REVISIONS DATED | | | 3/27/08. THE LOADS HAVE NOT CHANGED. | | | PLEASE BE SURE THE DP11 SCHEDULE REFLECT M411 NOT M412. | | | THIS WAS CORRECTED ON THE RISER SEVERAL REVISIONS AGO | | | HOWEVER NOT REVISED ON SCHEDULE. | | | PLEASE EXPLAIN WHY THE LOAD ON M411 HAS NOW INCREASED | | | BUT THE LOADS SHOWN ON DP11 ARE THE SAME AS PREVIOUS | | | REVISIONS IN WHICH LOAD ON M411 WERE LOWER. | | | NEC 220. | | | | | | FBC 106.1.1, 106.1.2, 106.5 FOR CLARITY, ADDITIONAL | | | INFORMATION AND RECORD COORDINATION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|