| 2007-03-22 14:41:38 | ----------------DENIED------------------ |
| | |
| | FBC 2004 W/2006 AMENDMENTS |
| | FBC,M 2004 |
| | FBC CHAPTER 1 W/LOCALLY ADOPTED AMENDMENTS |
| | |
| | 1. PG H-1.1: NOTE 2 STATES MAXIMUM LENGTH OF FLEX DUCT |
| | AT 7'. DETAIL 6 ON PG H-0.2 SHOWS THE MAX. LENGTH AT |
| | 5'. DETAIL 4 ON PAGE H-0.2 SHOWS A MAX. LENGTH OF 3'. |
| | PLEASE CLARIFY. FBC 106.1.1. |
| | |
| | 2. PG H-0.3: DETAIL 4, FIRE DAMPERS ARE TO BE INSTALLED |
| | IN ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS PER FBC,M 607.2. THE |
| | INSTRUCTIONS ARE REQUIRED IN FIELD FOR INSPECTION. |
| | |
| | 3. PG H-1.1 NOTE AT BOTTOM OF PAGE FOR PLENUMS, PLEASE |
| | REFERENCE FBC 2004 AND FBC,M 2004. CORRECT AND |
| | RESUBMIT. |
| | |
| | 4. PG H-1.1 NOTE 3: REFERENCES HP-5-1. THIS UNIT IS NOT |
| | ON THE EQUIPMENT SCHEDULE AND DOES NOT APPEAR ON PLANS. |
| | PLEASE CLARIFY PER FBC 106.1.1. |
| | |
| | 5. PG H-1.1 FPT-12-11 IS NOT SHOWN AS BEING CONNECTED |
| | TO ANY DUCT ON THE DISCHARGE SIDE. PLEASE CORRECT AND |
| | RESUBMIT. |
| | |
| | 6. PG H1.1: ROOM 1206, FED BY FPT-12-3 IS MISSING THE |
| | DIFFUSER TYPE AND CFM TO BE SUPPLIED TO THIS SPACE. |
| | PLEASE CORRECT AND RESUBMIT. |
| | |
| | 7. PG H-1.1 SHOWS FPT-12-5 PROVIDING 840 CFM OF SUPPLY |
| | AIR AT DIFFUSERS. EQUIPMENT SCHEDULE SHOWS FPT-12-5 |
| | WITH A MAXIMUM OF 830 CFM. PLEASE CLARIFY PER FBC |
| | 106.1.1. |
| | |
| | 8. PG H-0.1 VAV TERMINAL SCHEDULE: THE MAXIMUM AND |
| | MINIMUM CFM APPEAR TO HAVE BEEN REVERSED. PLEASE |
| | CORRECT AND RESUBMIT. |
| | |
| | 9. PG H-1.1 ROOM 1259 SHOWS ONE DIFFUSER BUT IS LABELED |
| | FOR TWO. IS THIS ROOM TO GET 140 OR 280 CFM? |
| | |
| | 10. PG H-3.1 NOTE IV-A: PLEASE PROVIDE SUBMITTAL DATA |
| | SHOWING THE PLASTIC LABELS AS SPECIFIED MEET THE 25/50 |
| | REQUIREMENTS OF FBC,M 602.2.1. IF NOT, PLEASE SUBMIT AN |
| | ALTERNATE METHOD OF LABELING THAT CONFORMS TO THE |
| | REQUIREMENTS OF THIS SECTION. |
| | |
| | 11. PLEASE SUBMIT TWO COMPLETE SETS OF PLANS, EACH SET |
| | BOUND TOGETHER WITHOUT LOOSE SHEETS TO FACILITATE THE |
| | PROPER EXAMINATION OF DOCUMENTS AS REQUIRED UNDER FBC |
| | 106.1. |
| | |
| | 12. ENERGY CALCULATIONS ARE TO BE SIGNED AND SEALED BY |
| | A FLORIDA LICENSED ARCHITECT OR ENGINEER PER FBC |
| | 13-103.1.1.1. |
| | |
| | 13. PLEASE NOTE THAT THE ENGINEER'S SEAL ON THE MEP |
| | DRAWINGS IS OUT OF DATE AND NO LONGER VALID PER FAC 61G |
| | 15-23.001 |
| | |
| | PLEASE FEEL FREE TO CONTACY ME OF YOU HAVE ANY |
| | QUESTIONS. |
| | |