| 2007-04-17 13:14:16 | *****DENIED***** | | | | | | | | | 1.THE NUMERICAL ADDRESS OF WHERE THE SCOPE OF WORK | | | WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | 2.CLARIFY WHETHER THE SCOPE OF WORK IS FOR THE ENTIRE | | | 12TH FLOOR OR A PARTICULAR SUITE ON THAT FLOOR. | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 4.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR | | | THIS SCOPE OF WORK. | | | | | | | | | PLEASE BE ADVISED THAT POSITIVE RESPONSES TO OTHER PLAN | | | REVIEW COMMENTS WILL FURTHER ASSIST IN THIS FIRE PLAN | | | REVIEW | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-6722 |
|