| 2007-03-19 17:22:01 | ** UNSAT ** |
| | |
| | * PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | WILL BE FROM THE ADMINISTRATIVE SECTION OF THE CODE AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | 1) NOTE: PLEASE SUBMIT PLANS INTO TWO COMPLETE SETS |
| | ATTACHED TOGETHER FOR REVIEW. PLEASE DO NOT SUBMIT |
| | LOOSE SHEETS NOT ATTACHED TO EACH OTHER AND NOT BOUND N |
| | ANY FASHION. |
| | FBC 106 |
| | |
| | 2) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS INDICATE |
| | THIS BUILDING AS A 20 STORY BUILDING WHERE AS THE BASE |
| | BUILDING PERMIT IS NOT FOR A 20-STORY BUILDING? PLEASE |
| | CORRELATE AND ADJUST PLANS. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE A PRINT OUT FROM THE STATE OF |
| | FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATION WHICH INDICATES THE ARCHITECT'S LICENSE AS |
| | ON PLANS AS *DELINQUENT* AT THIS TIME. PLEASE KNOW THAT |
| | THIS IS PRINTED WITH DATES OF 3/19/07. |
| | |
| | 4) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS DO NOT |
| | CONTAIN THE RAISED/EMBOSSED TYPE OF SEAL AS REQUIRED |
| | UNDER FAC 61G1-16.003 |
| | PLEASE SEE THESE ARE ACTUALLY A *RUBBER STAMP* FOR THE |
| | RAISED SEAL. |
| | THIS IS NOT PERMITTED IN THE STATE OF FLORIDA. FS |
| | 481.221 |
| | * THIS IS REQUIRED FOR ALL SHEETS WHICH CONTAIN THE |
| | *RUBBER STAMP* WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADE(S). |
| | |
| | 5) NOTE: PLEASE SEE THE MISSING INFORMATION ON THE |
| | TITLE BLOCKS FOR THE ARCHITECTURAL FIRM AS REQUIRED |
| | UNDER THE FAC 61G1-16.004 AND FS 481.219 |
| | * THIS IS REQUIRED FOR ALL SHEETS INCLUDING TRADE |
| | SHEETS WHICH CONTAIN THE SAME TITLE BLOCKS. |
| | |
| | 6) NOTE: PLEASE SEE THE ADDRESS OF THE PROJECT SHALL BE |
| | SPECIFIC ON THE TITLE BLOCKS AND COVER SHEET. THE |
| | STATEMENT WHICH INDICATES LOCATION IN THE *CITY OF WEST |
| | PALM BEACH* DOES NOT PROVIDE THE NEEDED INFORMATION. |
| | PLEASE SEE THE PROPOSED UNIT/SUITE NUMBER IS LISTED ON |
| | SHEETS. |
| | FAC 61G1-16 |
| | FBC ADMIN SECTION 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE THE SEAL WHICH IS BEING USED BY THE |
| | PE FOR THE MEP PLANS IS NO LONGER VALID WITHIN THE |
| | STATE OF FLORIDA. |
| | PLEASE SEE RULE IN THE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.001 WHICH WAS CHANGED IN FEB OF 04 THAT ALL |
| | SEALS FOR ENGINEERS MUST HAVE THE WORDING IN SEALS |
| | CHANGED FROM * CERTIFICATE* TO THE WORDING OF |
| | *LICENSE*. AN EXTENSION WAS GRANTED TO THE DATE OF |
| | DECEMBER 31ST, 2005 HOWEVER AFTER SUCH DATE THE OLDER |
| | SEALS WITH THE PREVIOUS WORDING COULD NOT LONGER BE |
| | USED. PLEASE OBTAIN NEW SEAL AS REQUIRED. |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE(S). |
| | |
| | 8) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | ARE NOT SIGNED, DATED AND SEALED AS REQUIRED. PLEASE |
| | SEE FBC 13-103.1.1.1 |
| | PLEASE ALSO SEE SEVERAL CODE COMMENTS WHICH WILL |
| | REQUIRE THESE TO BE REVISED. |
| | |
| | 9) NOTE: PLEASE SEE THAT ELECTRICAL ROOMS, MECHANICAL |
| | ROOMS, DATA/PHONE AND EMERGENCY ELECTRICAL ROOMS SHALL |
| | BE ACCESSIBLE WITHOUT ENTERING INTO THE TENANT SPACE. |
| | PLEASE EXTEND THE CORRIDORS ON FLOORS AND AREAS WHICH |
| | ARE FED FROM HOUSE POWER AND ANY ROOMS WHICH MAY FEED |
| | OTHER FLOORS. PLEASE SEE THE HALL WAYS ARE ALMOST DOWN |
| | TO THE ELECTRICAL ROOM ON ONE SIDE AND ONLY PART OF THE |
| | NORTH SIDE NEEDS TO BE CORRECTED. PLEASE KNOW THAT THE |
| | HOLD WHICH WAS PLACED ON THE PARCEL AS PART OF THE * |
| | PROVISO* ON THE ORIGINAL PLANS WILL REMAIN. PLEASE ALSO |
| | KNOW THAT ALL ORIGINAL PLANS FOR ISSUANCE OF PERMIT WAS |
| | ISSUED WITH THIS REDLINED ON PLANS AS CONDITIONS FOR |
| | ISSUANCE. |
| | 240.24, 210.25, 90.4. |
| | FBC 104.6 ADMIN SECTION. |
| | |
| | 10) NOTE: PLEASE SEE PLANS ON ARCHITECTURAL MENTIONS |
| | *MAG-LOCKS* OF SOME TYPE HOWEVER NO INFORMATION IS |
| | PROVIDED ON ELECTRICAL PLANS. |
| | PLEASE KNOW THAT ANY ACCESS CONTROL SYSTEMS SHALL MEET |
| | NFPA-101 7.1.9, 7.2.1.5.1 DOORS SHALL BE ARRANGED TO BE |
| | OPENED READILY FROM THE EGRESS SIDE WHENEVER THE |
| | BUILDING IS OCCUPIED. |
| | 7.2.1.5.2 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| | OPERATION FROM THE EGRESS SIDE. |
| | |
| | 11) NOTE: PLEASE SEE PLANS MENTIONS A SERVER ROOM IS |
| | THIS AN IT ROOM? IF SO, PLEASE INCLUDE THE RATING OF |
| | THE WALL CONSTRUCTION AND PLEASE SEE 645.11 FOR MEANS |
| | OF DISCONNECT OF ELECTRICAL EQUIPMENT. PLEASE PROVIDE |
| | MORE INFORMATION ON THIS. |
| | FBC 106.1.2. |
| | |
| | 12) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS |
| | ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS |
| | FOLLOWS. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | * PLEASE SEE THE ARCHITECTURAL SHEETS WHICH STATE SOME |
| | OF THE OLDER CODES. |
| | ** THESE ARE REQUIRED FOR THE REVIEWER AT A MINIMUM AND |
| | OTHER CODES WILL BE REQUIRED FOR OTHER TRADES. |
| | |
| | 13) NOTE: PLEASE SEE 2004 FBC W/2006 REVISIONS FOR |
| | CHAPTER 13. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.PLEASE SEE |
| | SOME AREAS/LOCATIONS WHICH DO NOT SEEM TO INDICATE ANY |
| | LIGHTING CONTROLS. PLEASE SE MAXIMUM LIGHTING CONTROL |
| | OF 25K SQ FT. PLEASE SEE ONLY ONE LIGHTING CONTROL |
| | PANEL IS BEING NOTED. |
| | PLEASE PROVIDE LOCATIONS AND MORE DETAIL OF THE OVER |
| | RIDES DEVICES AND HOW THEY ARE BEING PART OF THE |
| | *SYSTEM*. |
| | PLEASE PROVIDE ESTIMATED SCHEDULING. |
| | PLEASE SEE THE ENERGY CALCULATIONS INDICATES MANUAL |
| | CONTROLS FOR ALL LIGHTING CONTROL WHERE THIS SHOULD |
| | INDICATE THE ACTUAL DEVICES/SYSTEM ON PLANS. PLEASE SEE |
| | THATTHE LOCATIONS FOR ALL OVER RIDES DEVICES SHALL BE |
| | LOCATED SO THAT THE OCCUPANT CAN VISUALLY SEE THE |
| | LIGHTING WHICH IS BEING CONTROLLED. PLEASE PROVIDE MORE |
| | INFORMATION. |
| | PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. PLEASE SEE |
| | 13-415.1.AB.1; PLEASE SEE ENERGY CALCULATIONS FOR BUILD |
| | OUT OF SPACE WHICH DOES NOT CORRELATE WITH THE LIGHTING |
| | PLANS, FIXTURES, WATTAGES, NUMBER OF FIXTURES ETC. |
| | PLEASE SEE THERE ARE SEVERAL LIGHTING FIXTURES WHICH DO |
| | NOT CORRELATE WITH THE ELECTRICAL PLANS AND FIXTURE |
| | LEGEND. |
| | |
| | PLEASE SEE 13-415.2 AS LIGHTING POWER DENSITIES ARE NOT |
| | INDICATED FOR ALL AREAS. PLEASE BE SURE TO CORRELATE |
| | THIS WITH THE ENERGY CALCULATIONS WHICH ARE TO BE |
| | SUBMITTED. |
| | * PLEASE SEE ALL OF CHAPTER 13. |
| | PLEASE BE SURE ALL TO SEE 13-103.1.1.1 |
| | |
| | 14) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PANEL |
| | SCHEDULES FOR ALL ROOMS AND AREAS WHICH THE CIRCUIT |
| | FEEDS. PLEASE SEE 408.4 AND COMMENTARY WHICH IS TAKEN |
| | FROM THE CODE. |
| | * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4, |
| | 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 15) NOTE: PLEASE SEE NOTE ON SHEET A05.12 WHICH |
| | MENTIONS TO SEE SHEET A05.00 FOR DETAILS OF SERVER/IT |
| | ROOM AND YET THERE IS NO SHEET 05.00 SUBMITTED. |
| | |
| | 16) NOTE: PLEASE PROVIDE GROUNDING DETAIL FOR ALL |
| | TRANSFORMERS PER 250.20,250.30,250.66. |
| | PLEASE SHOW SIZE AND ATTACHMENT LOCATIONS. |
| | |
| | 17) NOTE: PLEASE CLARIFY THE RISER AND THE BASE |
| | BUILDING PLANS INDICATE METERING DEVICES OFF OF THE |
| | BUS-DUCT RISER YET THE RISER SUBMITTED DOES NOT SHOW |
| | ANY OF THIS? |
| | IF THERE ARE METERING DEVICES AND THEY ARE AFTER THE |
| | FIRST MEANS OF DISCONNECT FOR THE BUILDING, PLEASE |
| | INDICATE A *FLOATING NEUTRAL* AT THAT METERING DEVICE. |
| | FBC 106.1.2 |
| | |
| | 18) NOTE: PLEASE CLARIFY DP1, AS THIS SEEMS TO INDICATE |
| | A MAIN , YET ALSO SHOWS THIS AS BEING A MAIN LUG ONLY |
| | PANEL? |
| | FBC 106.1.2 |
| | |
| | 19) NOTE: PLEASE SEE SCHEDULE FOR THE OVER CURRENT |
| | PROTECTION ON THE SECONDARY SIDE OF THE TRANSFORMER T7A |
| | INDICATES 500AMP, YET THE EQUIPMENT WHICH IS ON THE |
| | SECONDARY SIDE IS 400A RATED. |
| | PLEASE ALSO SEE THAT THE PANELS ON THE SECONDARY SIDE |
| | OF THE TRANSFORMER DO NOT INDICATE ANY MAIN BREAKERS IN |
| | EQUIPMENT. |
| | PLEASE SEE THAT A MAIN IS REQUIRED. 408.36, 240.21 |
| | |
| | 20) NOTE: PLEASE SEE THAT ALL LOADS WHICH ARE |
| | CONTINUOUS ARE TO BE SHOWN AT 125%. 215.3, 230.42 ETC. |
| | |
| | 21) NOTE: PLEASE SEE THERE ARE TWO SECTIONS #3 FOR THE |
| | PANELS ON THE SECONDARY SIDE OF THE TRANSFORMER T7A. |
| | PLEASE CORRELATE. |
| | FBC 106.1.2 |
| | |
| | 22) NOTE: PLEASE SEE PANEL BOARD EL212A WHICH IS SHOWN |
| | CONTAINING A 15AMP MAIN CIRCUIT BREAKER WHICH IS OK, |
| | HOWEVER PLEASE SEE THAT THE PANEL IS ALSO BE SHOWN AS |
| | 15AMP RATED. |
| | PLEASE ADJUST AND INDEED VERIFY THAT THIS PANEL |
| | CONTAINS A 15AMP RATED MAIN CIRCUIT BREAKER. IS THIS A |
| | BACK FED BREAKER? IF SO, PLEASE INDICATE THE REJECTION |
| | CLIP. |
| | |
| | 23) NOTE: PLEASE INCLUDE ALL BRANCH CIRCUIT CONDUCTOR |
| | SIZES ON THE PANEL BOARD SCHEDULES. |
| | 310.16, 240.4. |
| | FBC106.3.5.1.2, 106.1.2 |
| | |
| | 24) NOTE: PLEASE SEE THE EGRESS LIGHTING LEVELS WERE |
| | SUBMITTED UNDER NORMAL HOWEVER NO UNDER EMERGENCY COULD |
| | BE FOUND. |
| | PLEASE SUBMIT. |
| | NFPA-101 7.9 |
| | |
| | 25) NOTE: PLEASE SEE THE ENLARGED ELECTRICAL ROOM |
| | PLANS. PLEASE INCLUDE THE DESIGNATION OF THE 600AMP MCB |
| | AS SHOWN ON RISER ON LAYOUT. |
| | FBC106.1.2, 106.3.5.1.2 |
| | |
| | 26) NOTE: PLEASE SEE ANY COMMENTS FROM OTHER TRADES |
| | (FIRE) WHICH MAY AFFECT THE ELECTRICAL PLANS. PLEASE |
| | ALSO SEE THAT BASED ON THE ELECTRICAL COMMENTS THE |
| | POWER AND REFLECTED CEILING PLANS FOR THE ARCHITECTURAL |
| | SHEETS WILL NEED TO BE REVISED. |
| | |
| | 27) NOTE: PLEASE VERIFY ALL NON-LINEAR LOADS ON THE |
| | NEUTRAL CONDUCTORS FOR BRANCH CIRCUITS. PLEASE PROVIDE |
| | INFORMATION WHETHER OR NOT EACH CIRCUIT WILL CONTAIN |
| | ITS OWN NEUTRAL OR IF THER WILL BE ANY MULTI-WIRE |
| | CIRCUITS WHICH SHARE A NEUTRAL? PLEAS EKNOW BASED ON |
| | SUBSTANTIAL INFORMATION FROM MANY COMPUTER MANUFACTURES |
| | THE HARMONIC LOADS CAN BE VERY HIGH ON SHARED NEUTRALS |
| | TO THE POIN OG FIRE ETC. THIS IS A FIRE AND LEFE SAFETY |
| | ISSUE. IT WAS NOTED THAT THE TRANSFORMERS TO PANELS |
| | CONTAIN 200% NEUTRALS AND TRANSFORMERS ARE K-RATED. |
| | QUESTION IS ON BRNACH CIRCUIT CONDUCTORS. |
| | PLEASE PROVIDE MORE INFORMATION. |
| | FBC 106.1.2 |
| | |
| | ** PLEASE KNOW BASED ON THE PLANS SUBMITTED THERE IS |
| | SOME INFORMATION NOT YET SUBMITTED OR WILL BE REQUIRED |
| | TO BE CHANGED. PLEASE KNOW THERE MAY BE COMMENTS ON THE |
| | FOLLOWING REVIEW NOT YET MADE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |