Plan Review Notes
Plan Review Notes For Permit 07030281
Permit Number 07030281
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-19 17:22:01** UNSAT **
  
 * PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 WILL BE FROM THE ADMINISTRATIVE SECTION OF THE CODE AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SUBMIT PLANS INTO TWO COMPLETE SETS
 ATTACHED TOGETHER FOR REVIEW. PLEASE DO NOT SUBMIT
 LOOSE SHEETS NOT ATTACHED TO EACH OTHER AND NOT BOUND N
 ANY FASHION.
 FBC 106
  
 2) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS INDICATE
 THIS BUILDING AS A 20 STORY BUILDING WHERE AS THE BASE
 BUILDING PERMIT IS NOT FOR A 20-STORY BUILDING? PLEASE
 CORRELATE AND ADJUST PLANS.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE A PRINT OUT FROM THE STATE OF
 FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION WHICH INDICATES THE ARCHITECT'S LICENSE AS
 ON PLANS AS *DELINQUENT* AT THIS TIME. PLEASE KNOW THAT
 THIS IS PRINTED WITH DATES OF 3/19/07.
  
 4) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS DO NOT
 CONTAIN THE RAISED/EMBOSSED TYPE OF SEAL AS REQUIRED
 UNDER FAC 61G1-16.003
 PLEASE SEE THESE ARE ACTUALLY A *RUBBER STAMP* FOR THE
 RAISED SEAL.
 THIS IS NOT PERMITTED IN THE STATE OF FLORIDA. FS
 481.221
 * THIS IS REQUIRED FOR ALL SHEETS WHICH CONTAIN THE
 *RUBBER STAMP* WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE(S).
  
 5) NOTE: PLEASE SEE THE MISSING INFORMATION ON THE
 TITLE BLOCKS FOR THE ARCHITECTURAL FIRM AS REQUIRED
 UNDER THE FAC 61G1-16.004 AND FS 481.219
 * THIS IS REQUIRED FOR ALL SHEETS INCLUDING TRADE
 SHEETS WHICH CONTAIN THE SAME TITLE BLOCKS.
  
 6) NOTE: PLEASE SEE THE ADDRESS OF THE PROJECT SHALL BE
 SPECIFIC ON THE TITLE BLOCKS AND COVER SHEET. THE
 STATEMENT WHICH INDICATES LOCATION IN THE *CITY OF WEST
 PALM BEACH* DOES NOT PROVIDE THE NEEDED INFORMATION.
 PLEASE SEE THE PROPOSED UNIT/SUITE NUMBER IS LISTED ON
 SHEETS.
 FAC 61G1-16
 FBC ADMIN SECTION 106.1.2
  
 7) NOTE: PLEASE SEE THE SEAL WHICH IS BEING USED BY THE
 PE FOR THE MEP PLANS IS NO LONGER VALID WITHIN THE
 STATE OF FLORIDA.
 PLEASE SEE RULE IN THE FLORIDA ADMINISTRATIVE CODE
 61G15-23.001 WHICH WAS CHANGED IN FEB OF 04 THAT ALL
 SEALS FOR ENGINEERS MUST HAVE THE WORDING IN SEALS
 CHANGED FROM * CERTIFICATE* TO THE WORDING OF
 *LICENSE*. AN EXTENSION WAS GRANTED TO THE DATE OF
 DECEMBER 31ST, 2005 HOWEVER AFTER SUCH DATE THE OLDER
 SEALS WITH THE PREVIOUS WORDING COULD NOT LONGER BE
 USED. PLEASE OBTAIN NEW SEAL AS REQUIRED.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE(S).
  
 8) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 ARE NOT SIGNED, DATED AND SEALED AS REQUIRED. PLEASE
 SEE FBC 13-103.1.1.1
 PLEASE ALSO SEE SEVERAL CODE COMMENTS WHICH WILL
 REQUIRE THESE TO BE REVISED.
  
 9) NOTE: PLEASE SEE THAT ELECTRICAL ROOMS, MECHANICAL
 ROOMS, DATA/PHONE AND EMERGENCY ELECTRICAL ROOMS SHALL
 BE ACCESSIBLE WITHOUT ENTERING INTO THE TENANT SPACE.
 PLEASE EXTEND THE CORRIDORS ON FLOORS AND AREAS WHICH
 ARE FED FROM HOUSE POWER AND ANY ROOMS WHICH MAY FEED
 OTHER FLOORS. PLEASE SEE THE HALL WAYS ARE ALMOST DOWN
 TO THE ELECTRICAL ROOM ON ONE SIDE AND ONLY PART OF THE
 NORTH SIDE NEEDS TO BE CORRECTED. PLEASE KNOW THAT THE
 HOLD WHICH WAS PLACED ON THE PARCEL AS PART OF THE *
 PROVISO* ON THE ORIGINAL PLANS WILL REMAIN. PLEASE ALSO
 KNOW THAT ALL ORIGINAL PLANS FOR ISSUANCE OF PERMIT WAS
 ISSUED WITH THIS REDLINED ON PLANS AS CONDITIONS FOR
 ISSUANCE.
 240.24, 210.25, 90.4.
 FBC 104.6 ADMIN SECTION.
  
 10) NOTE: PLEASE SEE PLANS ON ARCHITECTURAL MENTIONS
 *MAG-LOCKS* OF SOME TYPE HOWEVER NO INFORMATION IS
 PROVIDED ON ELECTRICAL PLANS.
 PLEASE KNOW THAT ANY ACCESS CONTROL SYSTEMS SHALL MEET
 NFPA-101 7.1.9, 7.2.1.5.1 DOORS SHALL BE ARRANGED TO BE
 OPENED READILY FROM THE EGRESS SIDE WHENEVER THE
 BUILDING IS OCCUPIED.
 7.2.1.5.2 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 11) NOTE: PLEASE SEE PLANS MENTIONS A SERVER ROOM IS
 THIS AN IT ROOM? IF SO, PLEASE INCLUDE THE RATING OF
 THE WALL CONSTRUCTION AND PLEASE SEE 645.11 FOR MEANS
 OF DISCONNECT OF ELECTRICAL EQUIPMENT. PLEASE PROVIDE
 MORE INFORMATION ON THIS.
 FBC 106.1.2.
  
 12) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS
 ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS
 FOLLOWS.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 * PLEASE SEE THE ARCHITECTURAL SHEETS WHICH STATE SOME
 OF THE OLDER CODES.
 ** THESE ARE REQUIRED FOR THE REVIEWER AT A MINIMUM AND
 OTHER CODES WILL BE REQUIRED FOR OTHER TRADES.
  
 13) NOTE: PLEASE SEE 2004 FBC W/2006 REVISIONS FOR
 CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.PLEASE SEE
 SOME AREAS/LOCATIONS WHICH DO NOT SEEM TO INDICATE ANY
 LIGHTING CONTROLS. PLEASE SE MAXIMUM LIGHTING CONTROL
 OF 25K SQ FT. PLEASE SEE ONLY ONE LIGHTING CONTROL
 PANEL IS BEING NOTED.
 PLEASE PROVIDE LOCATIONS AND MORE DETAIL OF THE OVER
 RIDES DEVICES AND HOW THEY ARE BEING PART OF THE
 *SYSTEM*.
 PLEASE PROVIDE ESTIMATED SCHEDULING.
 PLEASE SEE THE ENERGY CALCULATIONS INDICATES MANUAL
 CONTROLS FOR ALL LIGHTING CONTROL WHERE THIS SHOULD
 INDICATE THE ACTUAL DEVICES/SYSTEM ON PLANS. PLEASE SEE
 THATTHE LOCATIONS FOR ALL OVER RIDES DEVICES SHALL BE
 LOCATED SO THAT THE OCCUPANT CAN VISUALLY SEE THE
 LIGHTING WHICH IS BEING CONTROLLED. PLEASE PROVIDE MORE
 INFORMATION.
 PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. PLEASE SEE
 13-415.1.AB.1; PLEASE SEE ENERGY CALCULATIONS FOR BUILD
 OUT OF SPACE WHICH DOES NOT CORRELATE WITH THE LIGHTING
 PLANS, FIXTURES, WATTAGES, NUMBER OF FIXTURES ETC.
 PLEASE SEE THERE ARE SEVERAL LIGHTING FIXTURES WHICH DO
 NOT CORRELATE WITH THE ELECTRICAL PLANS AND FIXTURE
 LEGEND.
  
 PLEASE SEE 13-415.2 AS LIGHTING POWER DENSITIES ARE NOT
 INDICATED FOR ALL AREAS. PLEASE BE SURE TO CORRELATE
 THIS WITH THE ENERGY CALCULATIONS WHICH ARE TO BE
 SUBMITTED.
 * PLEASE SEE ALL OF CHAPTER 13.
 PLEASE BE SURE ALL TO SEE 13-103.1.1.1
  
 14) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PANEL
 SCHEDULES FOR ALL ROOMS AND AREAS WHICH THE CIRCUIT
 FEEDS. PLEASE SEE 408.4 AND COMMENTARY WHICH IS TAKEN
 FROM THE CODE.
 * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4,
 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 15) NOTE: PLEASE SEE NOTE ON SHEET A05.12 WHICH
 MENTIONS TO SEE SHEET A05.00 FOR DETAILS OF SERVER/IT
 ROOM AND YET THERE IS NO SHEET 05.00 SUBMITTED.
  
 16) NOTE: PLEASE PROVIDE GROUNDING DETAIL FOR ALL
 TRANSFORMERS PER 250.20,250.30,250.66.
 PLEASE SHOW SIZE AND ATTACHMENT LOCATIONS.
  
 17) NOTE: PLEASE CLARIFY THE RISER AND THE BASE
 BUILDING PLANS INDICATE METERING DEVICES OFF OF THE
 BUS-DUCT RISER YET THE RISER SUBMITTED DOES NOT SHOW
 ANY OF THIS?
 IF THERE ARE METERING DEVICES AND THEY ARE AFTER THE
 FIRST MEANS OF DISCONNECT FOR THE BUILDING, PLEASE
 INDICATE A *FLOATING NEUTRAL* AT THAT METERING DEVICE.
 FBC 106.1.2
  
 18) NOTE: PLEASE CLARIFY DP1, AS THIS SEEMS TO INDICATE
 A MAIN , YET ALSO SHOWS THIS AS BEING A MAIN LUG ONLY
 PANEL?
 FBC 106.1.2
  
 19) NOTE: PLEASE SEE SCHEDULE FOR THE OVER CURRENT
 PROTECTION ON THE SECONDARY SIDE OF THE TRANSFORMER T7A
 INDICATES 500AMP, YET THE EQUIPMENT WHICH IS ON THE
 SECONDARY SIDE IS 400A RATED.
 PLEASE ALSO SEE THAT THE PANELS ON THE SECONDARY SIDE
 OF THE TRANSFORMER DO NOT INDICATE ANY MAIN BREAKERS IN
 EQUIPMENT.
 PLEASE SEE THAT A MAIN IS REQUIRED. 408.36, 240.21
  
 20) NOTE: PLEASE SEE THAT ALL LOADS WHICH ARE
 CONTINUOUS ARE TO BE SHOWN AT 125%. 215.3, 230.42 ETC.
  
 21) NOTE: PLEASE SEE THERE ARE TWO SECTIONS #3 FOR THE
 PANELS ON THE SECONDARY SIDE OF THE TRANSFORMER T7A.
 PLEASE CORRELATE.
 FBC 106.1.2
  
 22) NOTE: PLEASE SEE PANEL BOARD EL212A WHICH IS SHOWN
 CONTAINING A 15AMP MAIN CIRCUIT BREAKER WHICH IS OK,
 HOWEVER PLEASE SEE THAT THE PANEL IS ALSO BE SHOWN AS
 15AMP RATED.
 PLEASE ADJUST AND INDEED VERIFY THAT THIS PANEL
 CONTAINS A 15AMP RATED MAIN CIRCUIT BREAKER. IS THIS A
 BACK FED BREAKER? IF SO, PLEASE INDICATE THE REJECTION
 CLIP.
  
 23) NOTE: PLEASE INCLUDE ALL BRANCH CIRCUIT CONDUCTOR
 SIZES ON THE PANEL BOARD SCHEDULES.
 310.16, 240.4.
 FBC106.3.5.1.2, 106.1.2
  
 24) NOTE: PLEASE SEE THE EGRESS LIGHTING LEVELS WERE
 SUBMITTED UNDER NORMAL HOWEVER NO UNDER EMERGENCY COULD
 BE FOUND.
 PLEASE SUBMIT.
 NFPA-101 7.9
  
 25) NOTE: PLEASE SEE THE ENLARGED ELECTRICAL ROOM
 PLANS. PLEASE INCLUDE THE DESIGNATION OF THE 600AMP MCB
 AS SHOWN ON RISER ON LAYOUT.
 FBC106.1.2, 106.3.5.1.2
  
 26) NOTE: PLEASE SEE ANY COMMENTS FROM OTHER TRADES
 (FIRE) WHICH MAY AFFECT THE ELECTRICAL PLANS. PLEASE
 ALSO SEE THAT BASED ON THE ELECTRICAL COMMENTS THE
 POWER AND REFLECTED CEILING PLANS FOR THE ARCHITECTURAL
 SHEETS WILL NEED TO BE REVISED.
  
 27) NOTE: PLEASE VERIFY ALL NON-LINEAR LOADS ON THE
 NEUTRAL CONDUCTORS FOR BRANCH CIRCUITS. PLEASE PROVIDE
 INFORMATION WHETHER OR NOT EACH CIRCUIT WILL CONTAIN
 ITS OWN NEUTRAL OR IF THER WILL BE ANY MULTI-WIRE
 CIRCUITS WHICH SHARE A NEUTRAL? PLEAS EKNOW BASED ON
 SUBSTANTIAL INFORMATION FROM MANY COMPUTER MANUFACTURES
 THE HARMONIC LOADS CAN BE VERY HIGH ON SHARED NEUTRALS
 TO THE POIN OG FIRE ETC. THIS IS A FIRE AND LEFE SAFETY
 ISSUE. IT WAS NOTED THAT THE TRANSFORMERS TO PANELS
 CONTAIN 200% NEUTRALS AND TRANSFORMERS ARE K-RATED.
 QUESTION IS ON BRNACH CIRCUIT CONDUCTORS.
 PLEASE PROVIDE MORE INFORMATION.
 FBC 106.1.2
  
 ** PLEASE KNOW BASED ON THE PLANS SUBMITTED THERE IS
 SOME INFORMATION NOT YET SUBMITTED OR WILL BE REQUIRED
 TO BE CHANGED. PLEASE KNOW THERE MAY BE COMMENTS ON THE
 FOLLOWING REVIEW NOT YET MADE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-19 06:58:102007-03-18 06:58:10
 REVIEW IN PROGRESS
2007-03-18 17:01:422007-03-18 17:01:42
 NOTES TO FOLLOW ONCE REVIEW IS COMPLETE.
2007-03-18 16:43:40IN ELEC FOR REVIEW.