| 2007-04-04 16:54:42 | BUILDING PLAN REVIEW |
| | PERMIT: 07030281 |
| | ADD: 525 OKEECHOBEE BLVD/SUITE 1200 |
| | CONT: CENTEX CONSTRUCTION |
| | TEL: (954)214-9415 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS |
| | NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE |
| | OF COMMENCEMENT |
| | AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) SHEET A00-00 |
| | 3A)ARCHITECTS JOVA/ DANIELS/ BUSBY ARCHITECTURAL FIRM |
| | IS MISSING THEIR CERTIFICATE OF AUTHORIZATION: 481.219 |
| | F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK |
| | FOR ANY |
| | SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER |
| | A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL |
| | SERVICES, SHALL INCLUDE |
| | THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE |
| | NUMBER TO EACH SHEET. |
| | THIS MAY BE ADDED BY HAND. |
| | |
| | 3B)ARCHITECTS SEAL IS A RUBBER SEAL NOT A EMBOSSED |
| | RAISED SEAL.FL S S 481.221 |
| | |
| | 3C) PROJECT INFORMATION INDICATES THIS TO BE A 20 STORY |
| | BUILDING PLEASE CORRECT. |
| | |
| | 3D) PLANS SUBMITTED AFTER DEC.8 2006 WILL BE REVIEWED |
| | UNDER THE 2004 FBC BUILDING WITH THE 2006 AMENDMENTS |
| | (REVISIONS). |
| | |
| | 3E) TITLE BLOCK:MISSING THE LOCATION OF THE |
| | PROJECT. |
| | 61G1-16.004 TITLE BLOCK. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | SPECIFIC AUTHORITY 481.2055 FS. LAW IMPLEMENTED |
| | 481.203(6), 481.203(8), 481.2131(1), |
| | 481.219(3),(4),(5), 481.221, 481.225(1)(E),(G), |
| | 481.2251(1)(H) FS. HISTORY?NEW 9-7-00. |
| | |
| | 4) SHEET A03.12 THIS SHEET INDICATES VARIOUS BREAKROOMS |
| | WITH SINKS, SEE CABINET ELEVATION SHEET A13.01: SINKS: |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| | BE MOUNTED WITH THE COUNTER NO HIGHER |
| | THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT |
| | LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| | SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| | (760 MM BY 1219 MM) COMPLYING WITH |
| | SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK |
| | TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES |
| | (485 MM) UNDERNEATH THE SINK. |
| | |
| | 5)SHEET A14.01DETAILS 10& 11 BOTH INDICATE A WOOD |
| | FINISH ON WALLS, UNDETERMINED WHAT IF THERE IS A BACKER |
| | BOARD? |
| | 803.4.2 SET-OUT CONSTRUCTION. |
| | WHERE WALLS AND CEILINGS ARE REQUIRED TO BE OF |
| | FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE CONSTRUCTION |
| | AND WALLS ARE SET OUT OR CEILINGS ARE DROPPED DISTANCES |
| | GREATER THAN SPECIFIED IN SECTION 803.4.1 , CLASS A |
| | FINISH MATERIALS SHALL BE USED EXCEPT WHERE INTERIOR |
| | FINISH MATERIALS ARE PROTECTED ON BOTH SIDES BY AN |
| | AUTOMATIC SPRINKLER SYSTEM OR ATTACHED TO |
| | NONCOMBUSTIBLE BACKING OR FURRING STRIPS INSTALLED AS |
| | SPECIFIED IN SECTION 803.4.1 . THE HANGERS AND ASSEMBLY |
| | MEMBERS OF SUCH DROPPED CEILINGS THAT ARE BELOW THE |
| | MAIN CEILING LINE SHALL BE OF NONCOMBUSTIBLE MATERIALS, |
| | EXCEPT THAT IN TYPE III AND V CONSTRUCTION, |
| | FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED. THE |
| | CONSTRUCTION OF EACH SET-OUT WALL SHALL BE OF |
| | FIRE-RESISTANCE-RATED CONSTRUCTION AS REQUIRED |
| | ELSEWHERE IN THIS CODE. |
| | |
| | 6)SHEET A0.12 & S00-01 BOTH INDICATE HEAVY LOADS |
| | (DENSE FILING) IN THE TWO FILE ROOMS. NEITHER SHEET |
| | INDICATES WHAT LIVE LOADS SEE TABLE 1607.1 PROVIDE |
| | MINIMUM CONCENTRATED LIVE LOADS. |
| | |
| | 7) NOTE; COMMENT# 6 REQUIRES A THRESHOLD INSPECTOR ON |
| | SITE SINCE THIS IS A THRESHOLD BUILDING. |
| | WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 8) FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | STRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE |
| | ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| | OF A BUILDING PERMIT FOR THE |
| | CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURL INSPECTION |
| | PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE |
| | BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 9)W.P.B. AMENDMENT 105.13.4.4 ALL |
| | PLANS FOR THE BUILDING WHICH ARE |
| | REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CON- |
| | TAIN A STATEMENT THAT, TO THE BEST OF |
| | THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, |
| | THE PLANS AND SPECIFICATIONS COMPLY WITH |
| | THE APPLICABLE FIRE-SAFETY STANDARDS AS |
| | DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 10) SINCE WORK ON THE STRUCTURAL FRAME (FLOOR FRAMING) |
| | MAKES THIS BUILDING A |
| | THRESHOLD BUILDING, (3) SETS OF ALL DOCUMENTS, PLANS |
| | SUBMITTALS AND OR REPORTS WILL BE REQUIRED. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |