Plan Review Notes
Plan Review Notes For Permit 07030280
Permit Number 07030280
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-18 08:34:51** UNSAT **
  
 1) NOTE: PLEASE SEE MISSING * GROUNDING ELECTRODE
 SYSTEM* DETAIL FROM PLANS. ATTACHMENT TO FOUNDATION OR
 IN THIS FOOTER STEEL IS REQUIRED. THE PERMIT
 APPLICATION IS FOR FOOTERS ONLY AND THIS IS NOT FOR ANY
 FOUNDATION WORK AS APPLIED.
 PLEASE SUBMIT A DETAIL FOR THE GROUNDING ELECTRODE
 SYSTEM PER NEC 250.50.
 * THIS CAN BE A DETAIL PROVIDED ON AN 8 1/2 BY 11 BY
 THE ENGINEER OF RECORD FOR THE PROJECT. PLEASE BE SURE
 ALL TITLE BLOCK INFORMATION FOR SAID FIRM/ENGINEER IS
 STATED ON SHEETS ALONG WITH ORIGINAL SIGNATURES, DATES
 AND SEALS. FAC 61G15-23.002, FS 471.025, 471.023
  
 2) NOTE: PLEASE SEE THE GEOTECHNICAL REPORT CONTAINS A
 RAISED SEAL OVER A *PHOTO-COPIED* SIGNATURE WHICH IS
 NOT PERMITTED UNDER FAC 61G15-23.002 AND FS471.025.
 THIS IS REQUIRED TO BE AN ORIGINAL SIGNATURE AND IS
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWERS.
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES WHICH THIS
 PROJECT IS UNDER SHALL BE STATED ON THE PLANS.
 PLEASE KNOW THERE MAY BE OTHER CODES WHICH MAY BE
 MENTIONED BY OTHER TRADES.
 FBC 2004 W/2006 REVISIONS
 2005 NFPA-70
  
 FBC ADMIN SECTION 106.1.2, 110.1.2
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS/LAYOUT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]