| 2007-03-18 08:34:51 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE MISSING * GROUNDING ELECTRODE |
| | SYSTEM* DETAIL FROM PLANS. ATTACHMENT TO FOUNDATION OR |
| | IN THIS FOOTER STEEL IS REQUIRED. THE PERMIT |
| | APPLICATION IS FOR FOOTERS ONLY AND THIS IS NOT FOR ANY |
| | FOUNDATION WORK AS APPLIED. |
| | PLEASE SUBMIT A DETAIL FOR THE GROUNDING ELECTRODE |
| | SYSTEM PER NEC 250.50. |
| | * THIS CAN BE A DETAIL PROVIDED ON AN 8 1/2 BY 11 BY |
| | THE ENGINEER OF RECORD FOR THE PROJECT. PLEASE BE SURE |
| | ALL TITLE BLOCK INFORMATION FOR SAID FIRM/ENGINEER IS |
| | STATED ON SHEETS ALONG WITH ORIGINAL SIGNATURES, DATES |
| | AND SEALS. FAC 61G15-23.002, FS 471.025, 471.023 |
| | |
| | 2) NOTE: PLEASE SEE THE GEOTECHNICAL REPORT CONTAINS A |
| | RAISED SEAL OVER A *PHOTO-COPIED* SIGNATURE WHICH IS |
| | NOT PERMITTED UNDER FAC 61G15-23.002 AND FS471.025. |
| | THIS IS REQUIRED TO BE AN ORIGINAL SIGNATURE AND IS |
| | REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE |
| | REVIEWERS. |
| | |
| | 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES WHICH THIS |
| | PROJECT IS UNDER SHALL BE STATED ON THE PLANS. |
| | PLEASE KNOW THERE MAY BE OTHER CODES WHICH MAY BE |
| | MENTIONED BY OTHER TRADES. |
| | FBC 2004 W/2006 REVISIONS |
| | 2005 NFPA-70 |
| | |
| | FBC ADMIN SECTION 106.1.2, 110.1.2 |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS/LAYOUT. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-03-09 10:37:32 | PLANS TO BE REVIEWED FOR ELECTRIC |