| Plan Review Notes For Permit 07030272 |
| Permit Number |
07030272 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-20 13:30:58 | *****UUNSAT***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.PLEASE INDICATE IF THE BUILDING OR POTIONS OF THE | | | BUILDING WILL BE OCCUPIED DURING THE SCOPE OF WORK.IF | | | SO, THIS WILL BE PERMITTED ONLY WHERE REQUIRED MEANS OF | | | EGRESS AND REQUIRED FIRE PROTECTION FEATURES ARE | | | INPLACE AND MAINTAINED. | | | | | | 4.BE SPECIFIC IN INDICATING THE WALL AND CEILING | | | CLASSIFICATION FOR THE SCOPE OF WORK BEING PROPOSED. | | | PLEASE BE ADVISED THAT CLASS A OR CLASS BARE REQUIRED | | | IN EXITS AND EXIT ACCESS CORRIDORS, AND CLASS A, CLASS | | | B, OR CLASS C IN ALL OTHER AREAS. | | | | | | 5.WILL THE SCOPE OF WORK CAUSE THE LOCATION OF FIRE | | | SPRINKLER HEADS/DEVICES (IF SO EQUIPPED) TO BE | | | MODIFIED?IF SO, SEPARATE PERMIT AND SHOP DRAWINGS | | | WILL BE REQUIRED FOR THE FIRE SPRINKLER REMODEL. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REQPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|