Plan Review Notes
Plan Review Notes For Permit 07030272
Permit Number 07030272
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-03-20 13:30:58*****UUNSAT*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.PLEASE INDICATE IF THE BUILDING OR POTIONS OF THE
 BUILDING WILL BE OCCUPIED DURING THE SCOPE OF WORK.IF
 SO, THIS WILL BE PERMITTED ONLY WHERE REQUIRED MEANS OF
 EGRESS AND REQUIRED FIRE PROTECTION FEATURES ARE
 INPLACE AND MAINTAINED.
  
 4.BE SPECIFIC IN INDICATING THE WALL AND CEILING
 CLASSIFICATION FOR THE SCOPE OF WORK BEING PROPOSED.
 PLEASE BE ADVISED THAT CLASS A OR CLASS BARE REQUIRED
 IN EXITS AND EXIT ACCESS CORRIDORS, AND CLASS A, CLASS
 B, OR CLASS C IN ALL OTHER AREAS.
  
 5.WILL THE SCOPE OF WORK CAUSE THE LOCATION OF FIRE
 SPRINKLER HEADS/DEVICES (IF SO EQUIPPED) TO BE
 MODIFIED?IF SO, SEPARATE PERMIT AND SHOP DRAWINGS
 WILL BE REQUIRED FOR THE FIRE SPRINKLER REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REQPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722