Plan Review Notes
Plan Review Notes For Permit 07030261
Permit Number 07030261
Review Stop E
Sequence Number 3
Notes
Date Text
2007-12-10 08:53:11** NOTE ADDED,
  
 NO 2ND SET OF BUILDING SHEETS WERE SUBMITTED BACK ONLY
 ONE SET FO A-SHEETS WITH THE TWO SETS OF ELECTRICAL.
 SHEETS WERE NOT ATTACHED INTO TWO SETS WHICH WAS DONE
 BY THIS REVIEWER WITH THE SHEETS SUBMITTED.
2007-12-10 08:51:46**** PROVISO/ REVISION NEEDED ****
  
 1) NOTE: PLEASE SEE THE NOTE AS TYPEWRITTEN ON SHEET E1
 OF 2 WITH RESPECT TO MINIMUM LEVELS OF LIGHTING UNDER
 EMERGENCY CONDITIONS IS NOT STATED CORRECTLY AS PER
 CODE SECTION GIVEN.
 PLEASE SEE 7.8.1.3 WHICH REQUIRES 10FT CANDLES MINIMUM
 UNDER NORMAL LIGHTING CONDITIONS AND 7.9.2.2 WHICH
 PERMITS THE LEVELS TO GO DOWN TO 1FT CANDLE UNDER
 EMERGENCY CONDITIONS.
 THESE CODES ARE UNDER THE ADOPTED LIFE SAFETY CODE 101,
 2003.
 THE NOTE AS TYPED IS OF ANOTHER CODE SECTION WITH
 RESPECT TO THE POSSIBLE BURNING OUT OF THE EMERGENCY
 LIGHT FIXTURE(S).
  
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  