Plan Review Notes
Plan Review Notes For Permit 07030261
Permit Number 07030261
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-18 15:08:33 
  
 *** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS ARE STILL
 IN NEED OF ADDRESSING.
 ** PLEASE KNOW AS NOT ALL INFORMATION NEEDED WAS
 SUBMITTED FOR A CODE COMPLIANT REVIEW THERE MAY BE NEW
 COMMENTS ON RE-SUBMITTAL OF PLANS.
  
 1) NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW. A
 NOTE IS NOW PLACED ON PLANS WHICH STATES TWO WAYS OF
 CIRCUITING EMERGENCY LIGHTS WHICH IS NOT PERMITTED.
 PLEASE SEE 700.12F AS THE EM LTS MUST BE CIRCUITED TO
 THE LOCAL LIGHTING BRANCH CIRCUIT IN THAT AREA.
 PLEASE ALSO SEE MISSING LIGHTING PHOTO-METRICS UNDER
 NORMAL AND UNDER EMERGENCY AS PREVIOUSLY REQUESTED.
 PLEASE SEE 7.8.1.3, 7.9.2.2 2003 LS 101.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]