| Date |
Text |
| 2007-03-18 08:20:29 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE PROVIDE ALL MINIMUM LIGHTING LEVELS |
| | UNDER NORMAL AND EMERGENCY CONDITIONS PER LS 101 |
| | 7.8.1.3, 7.9.2.2. |
| | PLEASE INDICATE AND SHOW HOW LIGHTING WILL BE |
| | CONTROLLED AND WHERE LIGHTING WILL BE CIRCUITED. PLEASE |
| | SEE 700.12E FOR CIRCUITING OF ANY EM/EXT LTS. FBC |
| | 106.1.2, 106.3.5.1.2 |
| | |
| | 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES WHICH THIS |
| | PROJECT IS UNDER SHALL BE STATED ON THE PLANS. PLEASE |
| | KNOW THERE MAY BE OTHER CODES WHICH MAY BE MENTIONED BY |
| | OTHER TRADES. |
| | FBC 2004 W/2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 (WHERE/IF APPLICABLE) |
| | 2003 NFPA-101 |
| | FBC ADMIN SECTION 106.1.2, 110.1.2 |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS/LAYOUT. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |