2007-03-15 16:01:13BUILDING PLAN REVIEW
 PERMIT:07030261
 ADD: 5913 S.DIXIE HWY
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 THIS INFORMATION IS REQUIRED TO DETERM THE WIDTH OF THE
 STAIRS. FBC 1005.1 THE TOTAL WIDTH OF MEANS OF EGRESS
 IN INCHES SHALL NOT BE LESS THAN THE TOTAL OCCUPANT
 LOAD SEVED BY THE MEANS OF EGRESS MULTIPLIED BY THE
 FACTORS IN TABLE 1005.1.
 FBC. 1004.1 IN DETERMINING MEANS OF EGRESS
 REQUIREMENTS,THE MUMBER OF OCCUPANTS FOR WHOM NEANS OF
 EGRESS FACILITIES SHALL BE PROVIDED SHALL BE
 ESTABLISHED BY THE LARGEST NUMBER COMPUTED IN
 ACCORDANCE WITH SECTIONS 1004.1 THROUGH 1004.1.3
  
 4)PROVIDE AN EXISTING AND PROPOSED FLOOR PLAN. SHOW
 THE MEANS OF EGRESS FOR THE SECOND FLOOR ON THE
 EXISTING FLOOR PLAN AND SHOW THE NEW SET OF STAIRS ON
 THE PROPOSED FLOOR PLAN.
  
 5)FBC.1007.1STAIRS REQUIRED TO BE ACCESSIBLE SHALL
 COMPLY WITH SECTIONS FBC 11-4.9
  
 6)FBC. 11-4.9.4STAIRWAYS SHALL HAVE HANDRAILS AT
 BOTH SIDES OF ALL STAIRS, HANDRAILS SHALL COMPLY WITH
 SEC. 11-4.26 AND FIG, 19A AND 19B. THEY SHALL EXTEND AT
 LEAST 12 INCHES BEYOND THE TOP RISER AND 12 INCHES PLUS
 THE WIDTH OF ONE TREAD BEYOND THE BOTTOM RISER.
  
 7)FBC. 11-4.13.6MINIMUM MANEUVERING CLEARANCE AT
 DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25THE FLOOR OR GROUND AREA WITHIN
 THE REQUIRED CLARANCES SHALL BE LEVEL AND CLEAR.
  
 8)THE H/C BATH SHALL BE IN COMPLIANCE WITH FBC
 11-4.17.SHOW THE CLEAR FLOOR SPACE FOR THE TOILET
 STALL. SEE FIG 30A / 30E AND FIG 28 CH.11 FOR MORE
 INFORMATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  