| Plan Review Notes For Permit 07030242 |
| Permit Number |
07030242 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-04-21 12:30:45 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FACFLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)OPENING 2, PRESSURE OF 59.9 PSF REQUIRES USE OF | | | THE 73PSF CHART.OPENING 3, SPAN OF 69" REQUIRES USE | | | OF 8' CHART.ANCHORING NOT COMPLIANT FOR EITHER | | | OPENING.CHECK ALL OPENINGS PRIOR TO RESUBMITTAL. | | | | | | 2.)THE APPLICATION IS INCOMPLETE; PARCEL ID REQUIRED. | | | | | | |
|