| Plan Review Notes For Permit 07030203 |
| Permit Number |
07030203 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-14 10:40:59 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | PLEASE SUBMIT A SITE PLAN INDICATING THE PHYSICAL | | | LOCATION OF THE EQUIPMENT WITH REGARD TO THE SERVICE | | | AND GENERATOR EQUIPMENT. NOTE: DISCONNECT REQUIRED TO | | | BE SERVICE RATED PER 225.36. THIS INCLUDES THE TRANSFER | | | SWITCH IF LOCATED AS A MAIN SERVICE DISCONNECTING | | | MEANS. ALSO 110.9 FOR AIC RATING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|