| Plan Review Notes For Permit 07030186 |
| Permit Number |
07030186 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-04-20 18:16:08 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE | | | FBC2004 | | | FACFLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)CHANGES TO THE PLAN ARE TO BE DONE BY THE ENGINEER | | | AND INITIALED AND DATED. | | | | | | 2.)THE NOTES ON THE PLAN AND SURVEY DO NOT SHOW CODE | | | COMPLIANCE.BECAUSE GENERAL SAFETY DESIGN CRITERIA WAS | | | NOT PROVIDED ON THE PLAN, THE DETAILS SPECIFIC TO THIS | | | JOB MUST SHOW CODE COMPLIANCE.PROVIDE A DETAIL FOR | | | THE "EXISTING GATE", INCLUDING SWING, HEIGHT, AND LATCH | | | HEIGHT OR LATCH DETAIL.NOTHING IS SHOWN ON THE REAR | | | PROPERTY LINE OR ON THE WEST SIDE OF THE HOUSE.SEE | | | FBC R 4101.COMPLIANCE IS TO BE SHOWN ON THE PLAN BY | | | THE ENGINEER, FBC106.1. |
|