Plan Review Notes
Plan Review Notes For Permit 07030159
Permit Number 07030159
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-21 14:40:26** NOTES REDLINED/ PROVISO **
  
 1) NOTE: PLEASE SEE PLANS HAVE BEEN REDLINED AS NO
 INFORMATION WAS PROVIDED ON RISER OR IS PROVIDED IN
 MANUFACTURES SPECS/CUT SHEETS ATTACHED FOR HOW THE SD
 SYSTEM WILL BE DETERMINED.
 250.20,250.30,250.50,250.66
  
 2) NOTE: PLEASE ALSO SPECIFICATIONDO NOTE THAT A
 SECONDARY MAIN IS REQUIRED , BUT ONLY ONE OF THE TWO
 PICTURES IN SPECS INDICATE THIS.THE SPECS/OR PLANS DO
 NOT INDICATE. THE NOTES ONLY MENTION ONE IS TO BE
 INSTALLED PER NEC. HOWEVER SIZE OF OCP AND CONDUCTOR
 SIZES ARE TO BE VERIFIED IN FIELD. ANY CHANGES IN
 EQUIPMENT OR CODE COMPLIANCE MUST BE SUBMITTED.
  
 ** PLEASE SUBMIT THIS INFORMATION BEFORE FINAL TO CLEAR
 UP INFORMATION FOR ELECTRICAL AS NOTED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  