Plan Review Notes
Plan Review Notes For Permit 07030159
Permit Number 07030159
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-21 14:41:57DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA STATUTES
  
 1. AN IRRIGATION CONTRACTOR IS REQUIRED FOR THE
 IRRIGATION WORK. (CONNECTING THE PUMP TO THE EXISTING
 IRRIGATION PIPE).
  
 2. SEE ELECTRICAL COMMENT NUMBER 2 WITH RESPECT TO FS
 471.003(2)(H)(2A).
  
 3. SUBMIT MANUF. SPECIFICATION SHEETS FOR THE
 IRRIGATION PUMP. MUST SHOW LISTING. SECTION 303.4.
  
 4. SUBMIT PIPING INFORMATION FOR THE CONNECTION TO THE
 PUMP. IS THIS A NEW SYSTEM OR ALTERED SYSTEM?SHOW THE
 LOCATION OF THE CONTROLLER AND THE RAIN SENSOR.
 INDICATE EXISTING PIPING AND NEW PIPING ON THE PLANS.
 PLEASE INDICATE THE PREVIOUS SOURCE OF WATER FOR THIS
 IRRIGATION SYSTEM. IF THE SOURCE WAS CITY WATER,
 (POTABLE), THEN THE SOURCE OF WATER SHALL BE CAPPED OFF
 BY A PLUMBING CONTRACTOR. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]