| Date |
Text |
| 2007-03-10 16:42:59 | ** UNSAT ** |
| | |
| | ** REVIEW BASED ON 2ND ELECTRICAL RISER ATTACHED ON |
| | PLANS WITH PRODUCT APPROVALS WHICH WAS NOT REVIEWED |
| | WITH THE ARCHITECTURAL PLANS. |
| | PLEASE BE SURE TO HAVE ALL ELECTRICAL AS REFERENCE ON |
| | THE ARCHITECTURAL SHEETS REMOVED. DO NOT CROSS OUT, |
| | THIS MUST BE REMOVED. |
| | PLANS ARE COMING BACK FOR CORRECTIONS. |
| | ** PLEASE SEE SOME COMMENTS ON THE NOTES FROM 3/9 ARE |
| | STILL VALID WITH RESPECT TO LOCATIONS OF ALL EQUIPMENT |
| | TO BE SHOWN ON PLANS ETC. |
| | |
| | 1) NOTE: PLANS MISSING TITLE BLOCK INFORMATION AS |
| | REQUIRED PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002, |
| | AND FLORIDA STATUTES 471.023. |
| | PLEASE SEE THAT PLANS ARE NOT SIGNED, DATED OR SEALED |
| | BY THE ENGINEER. FS 471.025, FAC 61G15-23.001 |
| | PLEASE SEE THAT THE LICENSE NUMBER OF ENGINEER IS NOT |
| | VISIBLE. VERIFICATION CAN NOT BE DONE. |
| | PLEASE COMPLETE ALL INFORMATION AS REQUIRED. |
| | |
| | 2) NOTE: PLEASE SEE MISSING COLD WATER AS PART OF THE |
| | GROUNDING ELECTRODE SYSTEM. 250.50 |
| | |
| | 3) NOTE: PLEASE SEE THAT NOT ENOUGH INFORMATION IS |
| | SUBMITTED FOR THE TRANSFORMER WHICH IS BEING NOTED AS |
| | PART OF THE LISTED PUMP CONTROL BOARD. PLEASE KNOW AS |
| | THIS IS SHOWING A TRANSFORMER FOR 120/240V USE, WHERE |
| | IS THE GROUNDING FOR THE SEPARATELY DERIVED SYSTEM PER |
| | 250.20, 250.30, AND 250.66? |
| | PLEASE SEE NOT NEUTRAL IS BEING BROUGHT TO THE |
| | EQUIPMENT AND IS NOT REQUIRED AS PLANS SEEM TO SHOW |
| | ONLY MOTOR LOADS, ALTHOUGH THE SD SYSTEM WILL REQUIRE |
| | NEUTRAL. |
| | PLEASE SUBMIT THIS INFORMATION ALONG WITH THE EQUIPMENT |
| | SPECS/DOCUMENTS FOR REVIEW. 110.3, 90.7 |
| | * PLEASE KNOW AT THIS TIME TAP CONDUCTORS AND HOW THIS |
| | TRANSFORMER IS BEING FED AND THE OVER-CURRENT |
| | PROTECTION IS NOT SHOWN AND REVIEW OF THESE ITEMS ALONG |
| | WITH TERMINATION OF THE TAPS IN OCP WHICH LIMITS THE |
| | LOAD ON THE CONDUCTORS NOT SHOWN CAN NOT BE VERIFIED. |
| | 240.21. 408.36? |
| | |
| | *********** |
| | |
| | |
| | |
| 2007-03-09 07:45:56 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN |
| | SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | |
| | 2) NOTE: PLEASE SEE FS 471.003(2)H(2A) WHERE AS THE |
| | 277/480V SERVICE MUST BE DESIGNED AND SIGNED AND SEALED |
| | BY A PE. |
| | |
| | 3) NOTE: PLEASE SEE THE SITE PLAN SHEETS WHICH CONTAIN |
| | TITLE BLOCKS FROM THE ARCHITECT SHALL BE SIGNED, DATED |
| | AND SEALED PER FS 481.221 |
| | |
| | ** PLEASE SEE SOME OF THE FOLLOWING NOTES ARE BASED ON |
| | THE ELECTRICAL PLANS SUBMITTED EVEN THOUGH THESE WILL |
| | BE REQUIRED TO BE RE-DONE BY AN ENGINEER. |
| | |
| | 4) NOTE: PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR |
| | IS NOT LARGE ENOUGH PER 250.66. |
| | |
| | 5) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS AND |
| | FEEDERS ARE NOT LARGE ENOUGH PER 310.16. (MAY NOT USE |
| | 310.15B6 FOR COMMERCIAL) |
| | |
| | 6) NOTE: PLEASE SEE 250.6 AND 250.24B FOR OBJECTIONABLE |
| | CURRENTS ON NEUTRAL AS SHOWN. |
| | |
| | 7) NOTE: PLEASE SUBMIT ALL EQUIPMENT ON THE NEW PANEL |
| | AND LOADS. PUMPS , CONTINUOUS LOADS, SIZES ETC NEED TO |
| | BE VERIFIED WHICH CAN NOT BED DONE AT THIS TIME. 220, |
| | 310.16, 430, 240 ETC |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 8) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS |
| | FOR THE NEW PUMP CONTROL PANEL. 110.3, 90.7. |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE INDICATE THE LOCATION OF PANEL ON |
| | PLANS. |
| | 110.26 NEEDS TO BE VERIFIED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |