Plan Review Notes
Plan Review Notes For Permit 07030159
Permit Number 07030159
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-10 16:42:59** UNSAT **
  
 ** REVIEW BASED ON 2ND ELECTRICAL RISER ATTACHED ON
 PLANS WITH PRODUCT APPROVALS WHICH WAS NOT REVIEWED
 WITH THE ARCHITECTURAL PLANS.
 PLEASE BE SURE TO HAVE ALL ELECTRICAL AS REFERENCE ON
 THE ARCHITECTURAL SHEETS REMOVED. DO NOT CROSS OUT,
 THIS MUST BE REMOVED.
 PLANS ARE COMING BACK FOR CORRECTIONS.
 ** PLEASE SEE SOME COMMENTS ON THE NOTES FROM 3/9 ARE
 STILL VALID WITH RESPECT TO LOCATIONS OF ALL EQUIPMENT
 TO BE SHOWN ON PLANS ETC.
  
 1) NOTE: PLANS MISSING TITLE BLOCK INFORMATION AS
 REQUIRED PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002,
 AND FLORIDA STATUTES 471.023.
 PLEASE SEE THAT PLANS ARE NOT SIGNED, DATED OR SEALED
 BY THE ENGINEER. FS 471.025, FAC 61G15-23.001
 PLEASE SEE THAT THE LICENSE NUMBER OF ENGINEER IS NOT
 VISIBLE. VERIFICATION CAN NOT BE DONE.
 PLEASE COMPLETE ALL INFORMATION AS REQUIRED.
  
 2) NOTE: PLEASE SEE MISSING COLD WATER AS PART OF THE
 GROUNDING ELECTRODE SYSTEM. 250.50
  
 3) NOTE: PLEASE SEE THAT NOT ENOUGH INFORMATION IS
 SUBMITTED FOR THE TRANSFORMER WHICH IS BEING NOTED AS
 PART OF THE LISTED PUMP CONTROL BOARD. PLEASE KNOW AS
 THIS IS SHOWING A TRANSFORMER FOR 120/240V USE, WHERE
 IS THE GROUNDING FOR THE SEPARATELY DERIVED SYSTEM PER
 250.20, 250.30, AND 250.66?
 PLEASE SEE NOT NEUTRAL IS BEING BROUGHT TO THE
 EQUIPMENT AND IS NOT REQUIRED AS PLANS SEEM TO SHOW
 ONLY MOTOR LOADS, ALTHOUGH THE SD SYSTEM WILL REQUIRE
 NEUTRAL.
 PLEASE SUBMIT THIS INFORMATION ALONG WITH THE EQUIPMENT
 SPECS/DOCUMENTS FOR REVIEW. 110.3, 90.7
 * PLEASE KNOW AT THIS TIME TAP CONDUCTORS AND HOW THIS
 TRANSFORMER IS BEING FED AND THE OVER-CURRENT
 PROTECTION IS NOT SHOWN AND REVIEW OF THESE ITEMS ALONG
 WITH TERMINATION OF THE TAPS IN OCP WHICH LIMITS THE
 LOAD ON THE CONDUCTORS NOT SHOWN CAN NOT BE VERIFIED.
 240.21. 408.36?
  
 ***********
  
  
  
2007-03-09 07:45:56** UNSAT **
  
 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN
 SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
  
 2) NOTE: PLEASE SEE FS 471.003(2)H(2A) WHERE AS THE
 277/480V SERVICE MUST BE DESIGNED AND SIGNED AND SEALED
 BY A PE.
  
 3) NOTE: PLEASE SEE THE SITE PLAN SHEETS WHICH CONTAIN
 TITLE BLOCKS FROM THE ARCHITECT SHALL BE SIGNED, DATED
 AND SEALED PER FS 481.221
  
 ** PLEASE SEE SOME OF THE FOLLOWING NOTES ARE BASED ON
 THE ELECTRICAL PLANS SUBMITTED EVEN THOUGH THESE WILL
 BE REQUIRED TO BE RE-DONE BY AN ENGINEER.
  
 4) NOTE: PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR
 IS NOT LARGE ENOUGH PER 250.66.
  
 5) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS AND
 FEEDERS ARE NOT LARGE ENOUGH PER 310.16. (MAY NOT USE
 310.15B6 FOR COMMERCIAL)
  
 6) NOTE: PLEASE SEE 250.6 AND 250.24B FOR OBJECTIONABLE
 CURRENTS ON NEUTRAL AS SHOWN.
  
 7) NOTE: PLEASE SUBMIT ALL EQUIPMENT ON THE NEW PANEL
 AND LOADS. PUMPS , CONTINUOUS LOADS, SIZES ETC NEED TO
 BE VERIFIED WHICH CAN NOT BED DONE AT THIS TIME. 220,
 310.16, 430, 240 ETC
 FBC 106.1.2 ADMIN SECTION.
  
 8) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 FOR THE NEW PUMP CONTROL PANEL. 110.3, 90.7.
 FBC 106.1.2
  
 9) NOTE: PLEASE INDICATE THE LOCATION OF PANEL ON
 PLANS.
 110.26 NEEDS TO BE VERIFIED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]