Plan Review Notes
Plan Review Notes For Permit 07030154
Permit Number 07030154
Review Stop P
Sequence Number 2
Notes
Date Text
2007-05-14 14:50:30 
 ****************PROVISO****************
 FBC-2004 PLUMBING
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR WASHING MACHINE TO BE THREE INCH
 (3").
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR WASHING MACHINE TO BE FOUR FEET
 ABOVE FINNISH FLOOR (4' A.F.F.)
  
 (E) 802.1.6 DOMESTIC DISHWASHING MACHINES SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK
 INTO A STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH
 SECTION 802.2 OR DISCHARGE INTO A WYE-BRANCH FITTING ON
 THE TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER.
  
  