| Date |
Text |
| 2007-03-28 14:32:48 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET 7 SANITARY ISOMETRIC RISER DIAGRAM AND FIRST |
| | AND SECOND FLOOR PLAN: |
| | IF SORIN POPESCU ARCHITECTURAL SERVICES IS AN |
| | ARCHITECTURAL FIRM THE FOLLOWING IS REQUIRED. |
| | FAC-61G1-16.004 TITLE BLOCK: |
| | A TITLE BLOCK MUST APPEAR ON ALL |
| | ARCHITECTURAL OR INTERIOR DESIGN |
| | DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK |
| | MUST, AT A MINIMUM, CONTAIN THE |
| | FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE |
| | NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED |
| | SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT. |
| | |
| | 2. SHEET 7 SANITARY ISOMETRIC RISER DIAGRAM: |
| | THE FOLLOWING IS REQUIRED FOR THE WASHING MACHINE. |
| | |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. PLEASE CORRECT THE PIPE SIZING ON THE |
| | RESUBMITTAL. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE |
| | RESUBMITTAL. |
| | |
| | 3. SHEET 7 SANITARY ISOMETRIC RISER DIAGRAM: |
| | PER FBC-2004, PLUMBING, SECTION 909.1 |
| | WET VENT PERMITTED: ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | NOTE: THE 3" SANIARY STACK FOR THE SECOND FLOOR |
| | BATHROOM MUST CONNECT DOWNSTREAM OF THE FIRST FLOOR |
| | BATHROOM. PLEASE CORRECT ON THE RESUBMITTAL. |
| | |
| | 4. SHEET 7 SANITARY ISOMETRIC RISER DIAGRAM: THE FIRST |
| | AND SECOND FLOOR TUBS REQUIRE VENTS PER FBC-2004 |
| | PLUMBING, SECTION |
| | 901.2.1 VENTING REQUIRED: EVERY TRAP AND |
| | TRAPPED FIXTURE SHALL BE VENTED IN |
| | ACCORDANCE WITH ONE OF THE VENTING |
| | METHODS SPECIFIED IN THIS CHAPTER. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |