Plan Review Notes
Plan Review Notes For Permit 07030154
Permit Number 07030154
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-28 14:32:48DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 7 SANITARY ISOMETRIC RISER DIAGRAM AND FIRST
 AND SECOND FLOOR PLAN:
 IF SORIN POPESCU ARCHITECTURAL SERVICES IS AN
 ARCHITECTURAL FIRM THE FOLLOWING IS REQUIRED.
 FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
  
 2. SHEET 7 SANITARY ISOMETRIC RISER DIAGRAM:
 THE FOLLOWING IS REQUIRED FOR THE WASHING MACHINE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. PLEASE CORRECT THE PIPE SIZING ON THE
 RESUBMITTAL.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL.
  
 3. SHEET 7 SANITARY ISOMETRIC RISER DIAGRAM:
 PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 NOTE: THE 3" SANIARY STACK FOR THE SECOND FLOOR
 BATHROOM MUST CONNECT DOWNSTREAM OF THE FIRST FLOOR
 BATHROOM. PLEASE CORRECT ON THE RESUBMITTAL.
  
 4. SHEET 7 SANITARY ISOMETRIC RISER DIAGRAM: THE FIRST
 AND SECOND FLOOR TUBS REQUIRE VENTS PER FBC-2004
 PLUMBING, SECTION
 901.2.1 VENTING REQUIRED: EVERY TRAP AND
 TRAPPED FIXTURE SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING
 METHODS SPECIFIED IN THIS CHAPTER.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved