| 2007-03-20 09:05:07 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 2} THE EQUIPMENT GROUND BETWEEN THE METER AND |
| | DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH |
| | TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN |
| | ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN |
| | FROM THE FIRST MEANS OF DISCONNECT. 250.6. |
| | |
| | 3} NOTE #1 REFERS TO "IAW" PLEASE NOTE THAT THE STATE |
| | OF FLORIDA HAS ADOPTED NFPA 70 OR THE NEC. IF |
| | REFERENCING ANOTHER CODE TO USE FOR WIRING COMPLIANCE, |
| | INDICATE WHERE IT IS REFERENCED AS REPLACING THE |
| | BUILDING CODE REFERENCES. |
| | |
| | 4} NOTE #6: SEE THE DEFINITION OF "SMOKE DETECTORS" |
| | 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, |
| | TO AVOID CONFUSION IN THE FIELD. |
| | |
| | 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| | FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE |
| | DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES |
| | ARE APPLICABLE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | WILLIAM R. TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |