Plan Review Notes
Plan Review Notes For Permit 07030154
Permit Number 07030154
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-20 09:05:07 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 3} NOTE #1 REFERS TO "IAW" PLEASE NOTE THAT THE STATE
 OF FLORIDA HAS ADOPTED NFPA 70 OR THE NEC. IF
 REFERENCING ANOTHER CODE TO USE FOR WIRING COMPLIANCE,
 INDICATE WHERE IT IS REFERENCED AS REPLACING THE
 BUILDING CODE REFERENCES.
  
 4} NOTE #6: SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD.
  
 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES
 ARE APPLICABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718