| 2007-04-13 19:07:51 | BUILDING REVIEW CHECKLIST: |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD. |
| | (561)233-5115) TO PAY IMPACT FEES. BRING BACK STAMPED |
| | PLANS AND COPY OF PAID RECEIPT. |
| | |
| | 3- VALUE DECLARED ON THE PERMIT APPLICATION WAS TOO |
| | LOW. IT WAS UPDATED TO $222,730. THEREFORE, OWES |
| | $1261.49 FOR UPDATED VALUE AND RADON FEES. SEC. 108.3 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 4- NEED TO SPECIFY TWO LAYERS OF UNDERLAYMENT FOR ROOF |
| | PITCH OF 3.36:12 AS REQUIRED BY SEC. R905.3.3.1 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 5- SPECIFY TILE FASTENING AS REQUIRED BY SEC. 106.1.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | ***NOTE: MAKE SURE PROPOSED FASTENING MEETS THE |
| | CALCULATED UPLIFT LOADS. |
| | |
| | 6- SHEET 5 OF 7: UPDATE ALLSTANDARDS REFERENCED IN |
| | THE GENERAL NOTES.SEE CHAPTER 43 OF 2004 FLORIDA |
| | RESIDENTIAL CODE FOR CORRECT STANDARD AND YEAR TO BE |
| | USED AND REVISE ALL NOTES AS REQUIRED. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| | FOR: |
| | A) PRECAST LINTELS. |
| | B) ALL TRUSSCONNECTORS SPECIFIED ON PLANS AND |
| | DETAILS. |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 9- REVISE ROOF SHEATHING TYPE OF FASTENER.SEE SEC. |
| | R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE AND REVISE |
| | AS REQUIRED. |
| | |
| | 10- SOIL TEST REPORT: |
| | A) REPORT SUBMITTED IS FOR ONE STORY ADDITION. PLANS |
| | SHOW TWO STORY ADDITION. REVISE AS REQUIRED. |
| | B) REPORT NEEDS TO HAVE THE ENGINEERING FIRM |
| | CERTIFICATE OF AUTHORIZATION NUMBER IN ALL SHEETS AS |
| | REQUIRED BY SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE |
| | CODE. |
| | |
| | 11- STORM SHUTTERS: PROVIDE KEY PLAN AND COMPLETE |
| | INSTALLATION SCHEDULE. SEE ATTACHED COPY OF |
| | INSTALLATION SCHEDULE AND COMPLETE ALL INFORMATION. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 12- OWNER/AGENT TO SIGN AND DATE THE ENERGY |
| | CALCULATIONS AT THE BOTTOM OF FORM. |
| | |
| | 13- ROOF SHEATHING SPECS ON SHEET 5 OF 7 DON'TMATCH |
| | SPECS SHOWN ON TYPICAL WALL SECTIONS.REVISE |
| | THICKNESS OF PLYWOOD AND MAKE SURE REVISED INFORMATION |
| | IS ADDRESSING ITEM #9 ABOVE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |