Plan Review Notes
Plan Review Notes For Permit 07030154
Permit Number 07030154
Review Stop B
Sequence Number 1
Notes
Date Text
2007-04-13 19:07:51BUILDING REVIEW CHECKLIST:
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.
 (561)233-5115) TO PAY IMPACT FEES. BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT.
  
 3- VALUE DECLARED ON THE PERMIT APPLICATION WAS TOO
 LOW. IT WAS UPDATED TO $222,730. THEREFORE, OWES
 $1261.49 FOR UPDATED VALUE AND RADON FEES. SEC. 108.3
 CITY AMENDMENTS TO FBC 2004.
  
 4- NEED TO SPECIFY TWO LAYERS OF UNDERLAYMENT FOR ROOF
 PITCH OF 3.36:12 AS REQUIRED BY SEC. R905.3.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 5- SPECIFY TILE FASTENING AS REQUIRED BY SEC. 106.1.1.2
 CITY AMENDMENTS TO FBC 2004.
 ***NOTE: MAKE SURE PROPOSED FASTENING MEETS THE
 CALCULATED UPLIFT LOADS.
  
 6- SHEET 5 OF 7: UPDATE ALLSTANDARDS REFERENCED IN
 THE GENERAL NOTES.SEE CHAPTER 43 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR CORRECT STANDARD AND YEAR TO BE
 USED AND REVISE ALL NOTES AS REQUIRED.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) PRECAST LINTELS.
 B) ALL TRUSSCONNECTORS SPECIFIED ON PLANS AND
 DETAILS.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 9- REVISE ROOF SHEATHING TYPE OF FASTENER.SEE SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE AND REVISE
 AS REQUIRED.
  
 10- SOIL TEST REPORT:
 A) REPORT SUBMITTED IS FOR ONE STORY ADDITION. PLANS
 SHOW TWO STORY ADDITION. REVISE AS REQUIRED.
 B) REPORT NEEDS TO HAVE THE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER IN ALL SHEETS AS
 REQUIRED BY SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE
 CODE.
  
 11- STORM SHUTTERS: PROVIDE KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED COPY OF
 INSTALLATION SCHEDULE AND COMPLETE ALL INFORMATION.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 12- OWNER/AGENT TO SIGN AND DATE THE ENERGY
 CALCULATIONS AT THE BOTTOM OF FORM.
  
 13- ROOF SHEATHING SPECS ON SHEET 5 OF 7 DON'TMATCH
 SPECS SHOWN ON TYPICAL WALL SECTIONS.REVISE
 THICKNESS OF PLYWOOD AND MAKE SURE REVISED INFORMATION
 IS ADDRESSING ITEM #9 ABOVE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712