| 2007-08-28 15:25:59 | *** DENIED 5TH TIME** |
| | |
| | 1) NOTE: REVISED SHEET E-2 AND ENERGY CALCULATIONS WERE |
| | SENT VIA FED EX TO THIS OFFICE. THIS REVIEWER IN ORDER |
| | TO PROCESS PERMITTING REMOVED OLD SHEETS AND INSERTED |
| | NEW SHEETS INTO THE SETS OF PLANS. |
| | THE SHEET E-2 WAS STILL MISSING ONE EM LT HOWEVER THIS |
| | IS BEING REDLINED ON PLANS AND NO CHANGES ARE NEEDED. |
| | ** PLEASE SEE HOWEVER ALL THREE COPIES OF THE ENERGY |
| | CALCULATIONS WERE NOT SIGNED, DATED AND SEALED AS |
| | REQUIRED UNDER FAC 61G15-23.002 AND FS471.025. PLEASE |
| | KNOW IN-FACT THESE ACTUALLY CONTAINED A RAISED SEAL |
| | OVER *PHOTO-COPIED* SIGNATURE AND DATE. |
| | THESE SUBMITTED WERE NOT ORIGINAL. THIS REVIEWER HAS |
| | CALLED OCI AND SPOKE TO MR. RICHARD CREAVELLE WHO IS |
| | THE ELECTRICAL ENGINEER. HE IS GOING TO GET WITH THE |
| | MECHANICAL ENGINEER AND FED-EX ONCE AGAIN NEW ENERGY |
| | CALCULATIONS TO THIS OFFICE FOR AM DELIVERY ON 8/29. |
| | THIS OFFICE CAN ONLY REQUEST FOR ITEMS TO BE DONE PER |
| | CODE AND REGULATED STATUTES AND ADMINISTRATIVE CODES. |
| | UNDER FLORIDA STATUTES, THIS OFFICE AND SPECIFICALLY |
| | THIS REVIEWER IS BOUND BY THE LAWS AND RULES OF THE |
| | STATE NOT TO ISSUE PERMIT UNTIL FOUND COMPLIANT WITH |
| | THE ADOPTED CODES AND ALL OTHER RULES AND ORDINANCES |
| | ADOPTED BY THE STATE. |
| | PERMIT IS READY TO ISSUE ONCE THESE ARE IN THIS OFFICE |
| | AND FOUND TO BE CORRECT. |
| | PLANS WILL BE OUT-FRONT ONCE AGAIN ON HOLD WAITING FOR |
| | NEW CALCULATIONS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |