Text |
| 2007-08-01 15:06:18 | ** UNSAT 3RD REVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE SOME AREAS OF PLANS WHERE APPEARS |
| | ONLY STANDARD ELECTRICAL SWITCHES ARE BEING SHOWN. |
| | PLEASE SEE REDLINED PLANS. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR ACCENT |
| | LIGHTING/DECRETIVE LIGHTING. |
| | PLEASE SEE 13-415.2ABC.1.2 (3) FOR TRACK LIGHTING. |
| | PLEASE CLARIFY AS THE LOADS ARE BASED ON VA OF THE |
| | AMOUNT OF FIXTURES OR LINEAR FT OF TRACK PER MIN VA IN |
| | THE CODE WHICH EVER IS GREATER. |
| | PLEASE SEE THERE ARE A FEW *SEPARATE SPACES* AND WHAT |
| | APPEARS AS ACCENT LIGHTING IN ONE ROOM. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |