| 2007-06-19 19:43:55 | *** UNSAT 2ND REVIEW ** |
| | |
| | |
| | ** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL NOT ADDRESSED. |
| | ** PLEASE SEE AS NOTED AND STATED ON PREVIOUS REVIEW AS |
| | INFORMATION IS ONLY JUST NOW BEING SUBMITTED FOR REVIEW |
| | THERE ARE NEW COMMENTS. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC |
| | CHAPTER 13HAS NOT BEEN ACHIEVED ON PLANS FOR CODE |
| | COMPLIANCE. PLEASE SEE PLANS NOW INDICATE A LIGHTING |
| | CONTROL PANEL/SYSTEM IS NOW GOING TO BE INSTALLED WHICH |
| | IS OK, HOWEVER NOT TIME OF SCHEDULING, NO DEVICES FOR |
| | OVER RIDE OF SYSTEM AT SEPARATE SPACES CONTAINING FLOOR |
| | TO CEILING HEIGHT PARTITIONS. |
| | NO TIMES ON OVER RIDES.(MAXIMUM AS STATED PER CODE) |
| | NO LOCATIONS ON PLANS FOR THESE TYPE(S) OF DEVICES. |
| | PLEASE SEE THE DEVICES ON LEGEND DO NOT COORDINATE WITH |
| | PLANS. PLEASE SEE SOME DEVICES ARE SHOWN ON PLANS FOR |
| | OS TYPE DEVICES YET RESPONSE LETTER MENTIONS THESE ARE |
| | ALL TO BE REMOVED. IF REMOVED, PLEASE MEET CODE FOR |
| | DEVICES WHICH ARE REQUIRED. |
| | PLEASE SEE 13-415.1ABC.1.1, .1.2 AND .1.3. |
| | ** PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE NOT |
| | CODE COMPLIANT. PLEASE KNOW AS THE WAS APPLIED FOR |
| | PERMIT AFTER DECEMBER 8TH, 2006 THE FLA-COM PROGRAMS |
| | RELEASED FROM THE STATE CONTAINS THE VERSION 3.0 WHICH |
| | STATES AT THE TOP OF THE SHEET *EFFECTIVE DATE OF |
| | DECEMBER 8TH, 2006*. |
| | PLEASE SEE THE NUMBER OF FIXTURES DO NOT CORRELATE WITH |
| | PLANS. |
| | PLEASE SEE THE TYPE OF FIXTURES DO NOT CORRELATE WITH |
| | PLANS. |
| | PLEASE SEE THE WATTAGE OF FIXTURES DOES NOT CORRELATE |
| | WITH PLANS. |
| | PLEASE SEE THE METHOD OF CONTROLS FOR LIGHTING DOES NOT |
| | CORRELATE. |
| | PLEASE SEE THE OWNER AGENT IS NOT SIGNED. |
| | *PLEASE SEE THE FOLLOWING COMMENT #2 WITH RESPECT TO |
| | SIGNATURE. |
| | PLEASE SEE AS MOST THE REQUIRED SYSTEM, DEVICES AND |
| | ENERGY CALCULATIONS ARE NOT COMPLETE OR COMPLIANT A |
| | REVIEW CAN ONLY BE DONE ON PLANS SUBMITTED. |
| | 13-415.1.AB.1.1, 13.415.2 |
| | |
| | 2) NOTE: AS STATED ON PREVIOUS REVIEW TO PLEASE BE SURE |
| | TO HAVE THE DESIGNER OF RECORD FOR THE ENERGY |
| | CALCULATIONS SIGN, DATE AND SEAL THESE AS REQUIRED PER |
| | 13-103.1.1.1 |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED IN FACT |
| | CONTAIN A RAISED SEAL OVER A PHOTO-COPIED SIGNATURE ON |
| | BOTH SETS SUBMITTED. ONE SET IS BEING RETAINED BY THIS |
| | OFFICE. |
| | PLEASE SEE FS 471.025, FAC 61G15-23.002 |
| | |
| | 3) NOTE: PLEASE SEE FS 471.025 AS NO SHEETS IN EITHER |
| | SET OF ELECTRICAL PLANS CONTAINS ANY SIGNATURE, DATE OR |
| | RAISED SEAL. |
| | PLEASE SEE FAC 61G15-23.002 |
| | |
| | 4) NOTE: PLEASE SEE PLANS DO NOT INDICATE SUFFICIENT |
| | LIGHTING FIXTURES WITH BATTERY BACK UP FOR MINIMUM |
| | LIGHTING LEVELS PER LS 7.8, 7.9. |
| | PLEASE SEE PLANS APPEARS TO SHOW SOME 2X4 LAY-IN |
| | FIXTURES WITH A LINE WHICH ARE TYPICALLY THE BATTERY |
| | BACK UP TYPE FIXTURE HOWEVER THE SYMBOL AND FIXTURE |
| | LEGEND DOES NOT SHOW A DIFFERENCE BETWEEN THE TWO. |
| | PLEASE SEE OTHER AREAS WHICH SHOW THE WALL MOUNTED |
| | BATTERY BACK UP FIXTURES WHICH ARE OK. |
| | PLEASE SEE COMMENTS FROM THE FIRE MARSHAL. |
| | |
| | 5) NOTE: PLEASE CLARIFY WHY CONTINUOUS LOADS ARE NOT |
| | SHOWN ON TRANSFORMER/SERVICE LOADS? |
| | 215.3, 230.42, 220. |
| | |
| | 6) NOTE: PLEASE CLARIFY ANY METERING DEVICES ARE |
| | LOCATED ON RISER/SERVICE. |
| | |
| | 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. SETS OF PLANS HAVE |
| | BEEN RETAINED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |