| 2007-03-10 17:08:43 | ** UNSAT ** |
| | |
| | |
| | 1)NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| | ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| | PLANS/LEGEND. |
| | |
| | 3) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC |
| | CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1, |
| | .1.2 AND .1.3. SOME IS SHOWN, HOWEVER NOT ALL AREAS FOR |
| | CONTROL ARE CLEAR OR SHOWN MEETING THESE SECTIONS. |
| | PLEASE SUBMIT LIGHTING POWER DENSITIES PER THE 2004 FBC |
| | W/ 2006 REVISION. PLEASE SEE 13-415.1.AB.1.1, 13-415.2 |
| | FOR LIGHTING PERFORMANCE CALCULATIONS ALONG WITH ENERGY |
| | CALCULATIONS. |
| | PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC |
| | FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE |
| | LPD/CALCULATIONS IS REVIEWED FOR COMPLIANCE. PLEASE BE |
| | SURE TO HAVE THE DESIGNER OF RECORD FOR THE ENERGY |
| | CALCULATIONS SIGN, DATE AND SEAL THESE AS REQUIRED PER |
| | 13-103.1.1.1 |
| | |
| | 4) NOTE: PLEASE CORRELATE RISER AND PANEL LP-5, ONE |
| | SHOWS MCB AND THE MLO. |
| | |
| | 5) NOTE: PLEASE SEE BOTH BATHROOMS MEN'S AND WOMEN'S |
| | WILL REQUIRE BATTERY BACK UP FIXTURES OF SOME TYPE. |
| | PLEASE SEE THE FIXTURE *D*, AS TWO SYMBOLS ARE SHOWN |
| | FOR THE SAME TYPE OF FIXTURE ON PLANS THEFIXTURE |
| | LEGEND DOES INDICATE BUT ONLY ONE TYPE. |
| | PLEASE INDICATE A BATTERY BACK UP FIXTURE. |
| | LS 101 7.8 AND 7.9. |
| | PLEASE SEE 700.12E FOR CIRCUITING TO LOCAL LIGHTING |
| | CIRCUIT IN EACH ROOM. |
| | |
| | 6) NOTE: PLEASE ADJUST NOTED FOR * LOCK-ON/OFF* DEVICE |
| | AS NOTED ON PANEL SCHEDULE. |
| | PLEASE STATE/NOTE THAT THE *LOCK OFF/ON DEVICE SHALL BE |
| | AN INTEGRAL PART OF THE BREAKER* THIS DEVICE MAY NOT BE |
| | OF THE TYPE WHICH *SNAPS/CLIPS* ON THE BREAKER. (OR |
| | WORDS TO THE AFFECT). |
| | 110.3. |
| | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. |
| | |
| | ** PLEASE KNOW AS ENERGY CALCULATIONS/LIGHTING |
| | PERFORMANCE CALCULATIONS AND INFORMATION FOR LIGHTING |
| | CONTROL SYSTEM/CONTROLS ARE NOT COMPLETE AT THIS TIME |
| | FOR REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH HAVE NOT YET BEEN MADE |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |