| 2007-08-16 07:14:34 | DENIED |
| | REFERENCE: FBC-2004 |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 BUILDING |
| | WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ******FROM PREVIOUS REVIEW: |
| | ****FROM PREVIOUS REVIEWS: |
| | |
| | |
| | 1. OK |
| | |
| | 2. THE SIGNATURE OF THE ARCHITECT IS REQUIRED WHEN |
| | SEALING EACH SHEET. IT APPEARS THAT INITIALS HAVE BEEN |
| | USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| | ARCHITECT, PLEASE PROVIDE A SIGNED, SEALED, AND |
| | NOTORIZED LETTER FOR OUR FILES. FAC 61G1-16.003, |
| | 61G1-16.004((5) & FS 481.2055. |
| | ******RESPONSE NOTED, BUT MULTIPLE LEGAL SIGNATURES ARE |
| | NOT APPROVED. ONLY THE RECOGNIZED LEGAL SIGNATURE OF |
| | THE ARCHITECT OF RECORD WILL BE ACCEPTED. ****RESPONSE |
| | NOTED, BUT LETTER NOT SEALED/DATED. |
| | |
| | 3. OK - REVIEWER ATTACHED SHEETS. |
| | |
| | 4. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY |
| | DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY |
| | COMPO, (561) 822-2272, OR BY FAX (561) 822-2287, OR |
| | E-MAIL [email protected]. SECTION III OF THE MUNICIPAL |
| | CODE. |
| | ******RESPONSE NOTED, BUT NO ATTACHED LETTER SHOWING |
| | APROVAL FOUND IN RESUBMITTAL OF PLANS. ****RESPONSE |
| | NOTED, BUT STILL NO REFERENCE TO CONTACTING |
| | ENVIRONMENTAL COMPLIANCE FOR SIZING OF GREASE |
| | INTERCEPTOR. |
| | |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | |
| | 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE |
| | FOLLOWING INFORMATION: |
| | |
| | A. OK |
| | |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ******RESPONSE NOTED, BUT MANUF. SHEETS FOR ITEM #41 |
| | INDICATES 50,000 BTU'S AND THE RISER DIAGRAM INDICATES |
| | 100,000 BTU'S. ALSO SUBMIT THE UL LISTING FOR THIS |
| | PRODUCT.--ITEM 38 MANUF. SPECIFICATION SHEETS ARE |
| | NOT LEGIBLE AND DO NOT INDICATE BTU OR CFH INPUT |
| | RATING.--ITEM 47 (7), NOT SUBMITTED. (NUMBER 47 NOT |
| | IN LEGEND). PLEASE SUBMIT MANUF SPECIFICATION SHEETS |
| | FOR THE TANKLESS WATER HEATERS.--TWO COPIES OF THE |
| | GAS MANUF SPECIFICATION SHEETS REQUIRED FOR REVIEW. |
| | ONLY ONE SUBMITTED. SECTION 106.1. |
| | ****RESPONSE NOTED, BUT ITEMS #41 & #38 ARE INDICATED |
| | AS "KEY NOTES" BUT ARE SHOWN ON THE GAS RISER DIAGRAM. |
| | THIS CAUSED CONFUSION ON MY PART BECAUSE THE NUMBERS |
| | ARE INDICATED ON THE RISER DIAGRAM. BOTH NUMBERS ARE |
| | INDICATED IN THE KEY NOTES ALSO. BE THAT AS IT MAY, THE |
| | COMMENTS STILL STAND. KEY NOTE 41, ITEM STILL INDICATES |
| | 50,000BTU ON THE MANUF. SPECIFICATION SHEETS, BUT IS |
| | INDICATED AS 100,000BTU ON THE RISER DIAGRAM. ALSO KEY |
| | NOTE 38, ITEM 18 DOES NOT SHOW BTU"S ON THE MANUF. |
| | SHEET. THIS WAS WRITTEN ON THE SHEETS AND BTU'S CAN NOT |
| | BE VERIFIED.ITEM 47 LISTING CAN NOT BE VERIFIED ON A |
| | QUESTION AND ANSWER SHEET. PLEASE SEE CSA PRODUCT |
| | LISTING SEARCH SHEET ATTACHED TO COMMENTS. FILL OUT |
| | REQUIRED SECTIONS OR SUBMIT LISTING INFORMATION FROM |
| | CSA TO VERIFY LISTING. |
| | |
| | 10. OK |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. ALL ELEC., MECH., & PLUMBING SHEETS. ENGINEERS |
| | SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS, AND LICENSE |
| | NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION |
| | NUMBER ON THE ENGINEERING BUSINESS ON EACH SHEET. FAC |
| | 61G15-23.002(2) & FS 471.025 |
| | ****RESPONSE NOTED, BUT THE ADDRESS FOR THE ENGINEER IS |
| | NOT BEEN INCLUDED AS INDICATED. (SEE ATTACHED SHEET |
| | FROM FLORIDA STATE DBPR WEBSITE LISTING ENGINEER'S |
| | ADDRESS). |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1C. SHT P5.0 INDICATE THE PIPE SIZE FOR ALL STUB OUTS |
| | FOR EACH GAS APPLIANCE. PIPE SIZE SHALL BE FULL SIZE |
| | THRU THE SHUT OFF VALVE TO EACH APPLIANCE. |
| | (SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |