2007-08-16 07:14:34DENIED
 REFERENCE: FBC-2004
 FBC-2004 CHAPTER 1
 FBC-2004 BUILDING
 WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ******FROM PREVIOUS REVIEW:
 ****FROM PREVIOUS REVIEWS:
  
  
 1. OK
  
 2. THE SIGNATURE OF THE ARCHITECT IS REQUIRED WHEN
 SEALING EACH SHEET. IT APPEARS THAT INITIALS HAVE BEEN
 USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ARCHITECT, PLEASE PROVIDE A SIGNED, SEALED, AND
 NOTORIZED LETTER FOR OUR FILES. FAC 61G1-16.003,
 61G1-16.004((5) & FS 481.2055.
 ******RESPONSE NOTED, BUT MULTIPLE LEGAL SIGNATURES ARE
 NOT APPROVED. ONLY THE RECOGNIZED LEGAL SIGNATURE OF
 THE ARCHITECT OF RECORD WILL BE ACCEPTED. ****RESPONSE
 NOTED, BUT LETTER NOT SEALED/DATED.
  
 3. OK - REVIEWER ATTACHED SHEETS.
  
 4. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY
 DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY
 COMPO, (561) 822-2272, OR BY FAX (561) 822-2287, OR
 E-MAIL [email protected]. SECTION III OF THE MUNICIPAL
 CODE.
 ******RESPONSE NOTED, BUT NO ATTACHED LETTER SHOWING
 APROVAL FOUND IN RESUBMITTAL OF PLANS. ****RESPONSE
 NOTED, BUT STILL NO REFERENCE TO CONTACTING
 ENVIRONMENTAL COMPLIANCE FOR SIZING OF GREASE
 INTERCEPTOR.
  
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ******RESPONSE NOTED, BUT MANUF. SHEETS FOR ITEM #41
 INDICATES 50,000 BTU'S AND THE RISER DIAGRAM INDICATES
 100,000 BTU'S. ALSO SUBMIT THE UL LISTING FOR THIS
 PRODUCT.--ITEM 38 MANUF. SPECIFICATION SHEETS ARE
 NOT LEGIBLE AND DO NOT INDICATE BTU OR CFH INPUT
 RATING.--ITEM 47 (7), NOT SUBMITTED. (NUMBER 47 NOT
 IN LEGEND). PLEASE SUBMIT MANUF SPECIFICATION SHEETS
 FOR THE TANKLESS WATER HEATERS.--TWO COPIES OF THE
 GAS MANUF SPECIFICATION SHEETS REQUIRED FOR REVIEW.
 ONLY ONE SUBMITTED. SECTION 106.1.
 ****RESPONSE NOTED, BUT ITEMS #41 & #38 ARE INDICATED
 AS "KEY NOTES" BUT ARE SHOWN ON THE GAS RISER DIAGRAM.
 THIS CAUSED CONFUSION ON MY PART BECAUSE THE NUMBERS
 ARE INDICATED ON THE RISER DIAGRAM. BOTH NUMBERS ARE
 INDICATED IN THE KEY NOTES ALSO. BE THAT AS IT MAY, THE
 COMMENTS STILL STAND. KEY NOTE 41, ITEM STILL INDICATES
 50,000BTU ON THE MANUF. SPECIFICATION SHEETS, BUT IS
 INDICATED AS 100,000BTU ON THE RISER DIAGRAM. ALSO KEY
 NOTE 38, ITEM 18 DOES NOT SHOW BTU"S ON THE MANUF.
 SHEET. THIS WAS WRITTEN ON THE SHEETS AND BTU'S CAN NOT
 BE VERIFIED.ITEM 47 LISTING CAN NOT BE VERIFIED ON A
 QUESTION AND ANSWER SHEET. PLEASE SEE CSA PRODUCT
 LISTING SEARCH SHEET ATTACHED TO COMMENTS. FILL OUT
 REQUIRED SECTIONS OR SUBMIT LISTING INFORMATION FROM
 CSA TO VERIFY LISTING.
  
 10. OK
  
 **********NEW COMMENT**********
  
 1B. ALL ELEC., MECH., & PLUMBING SHEETS. ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS, AND LICENSE
 NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER ON THE ENGINEERING BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025
 ****RESPONSE NOTED, BUT THE ADDRESS FOR THE ENGINEER IS
 NOT BEEN INCLUDED AS INDICATED. (SEE ATTACHED SHEET
 FROM FLORIDA STATE DBPR WEBSITE LISTING ENGINEER'S
 ADDRESS).
  
 **********NEW COMMENT**********
  
 1C. SHT P5.0 INDICATE THE PIPE SIZE FOR ALL STUB OUTS
 FOR EACH GAS APPLIANCE. PIPE SIZE SHALL BE FULL SIZE
 THRU THE SHUT OFF VALVE TO EACH APPLIANCE.
 (SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]