| Plan Review Notes For Permit 07030094 |
| Permit Number |
07030094 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-08-10 13:21:48 | ***********PROVISO************ | | | 1) REVISE ENERGY CALCULATIONS TO SHOW CORRECT ROOF | | | ASSEMBLY AND R-VALUE PRIOR TO INSPECTION. | | | 2) PROVIDE AUXILIARY DRAIN PROTECTION (INTERNAL FLOAT | | | SWITCH, NOT SECONDARY DRAIN ON ROOF) ON RTU'S. | | | 3) RTU'S TO BE FASTENED PER SUBMITTED STRUCTURAL | | | CALCULATIONS, NOT DETAIL ON PLAN. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|