Plan Review Notes
Plan Review Notes For Permit 07030094
Permit Number 07030094
Review Stop E
Sequence Number 3
Notes
Date Text
2007-08-12 12:20:35 
 ** DENIED 3RD TIME **
  
 2ND REVIEW UNDER PERMIT APPLICATION.
  
 ** PLEASE SEE THAT SOME NOTES FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE LETTERS NOW SUBMITTED FOR
 SIGNATURE VERIFICATION NOT DATED AND SEALED WHEN
 SIGNED. IF THIS WAS THE ONLY ITEM, THESE COULD BE
 MAILED IN TO THIS OFFICE HOWEVER AS THE PLANS HAVE
 OTHER COMMENTS PLEASE SUBMIT.
 FS 481.221, 471.025
  
 2) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 IS STILL IN NEED OF ADDRESSING.
 PLEASE SEE THE LIGHTING REFLECT CEILING PLAN ON SHEET
 A1.4 DOES NOT COORDINATE WITH THE ELECTRICAL LIGHTING
 PLANS?
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED WERE ONCE
 AGAIN NOT SEALED BY THE DESIGN PROFESSIONAL AS STATED
 ON THE TWO PREVIOUS REVIEWS. THIS WAS SPECIFICALLY
 MENTIONED ON THE TWO PREVIOUS REVIEWS AS THIS IS
 REQUIRED PER THE FLORIDA BUILDING CODE AND FLORIDA
 STATUTES. THESE WERE SIGNED BUT WERE NOT SEALED AND
 DATED.
 PLEASE ALSO SEE THE *OWNER AGENT* IS ALSO NOT SIGNED ON
 SHEETS.
 PLEASE SEE THE PREVIOUS NOTE WHICH REQUIRES THE
 DESIGNER(S) OF RECORD RESPONSIBLE FOR SCOPE OF WORK TO
 *SIGN, DATE AND SEAL* SAID DOCUMENTS. THIS IS NOT ONLY
 REQUIRED PER FS 471.025, 481.221, FAC 61G15-23, 61G1-16
 BUT ALSO FBC 13-103.1.1.1.
  
 PLEASE SEE THE FIXTURES AND WATTAGES AS SHOWN ON ENERGY
 CALCULATIONS DO NOT CORRELATE WITH THE SUBMITTED PLANS
 AND FIXTURE LEGEND(S).
 PLEASE SEE THE TWO PREVIOUS REVIEWS WHICH WERE MARKED
 WITH AN ASTERISK ** FOR 13-415.2.ABC.1.2 SPECIFICALLY
 FOR TRACK LIGHTING, HOWEVER THE WATTAGE ON THE ENERGY
 CALCULATIONS NEED TO BE ADJUSTED.
 PLEASE SEE THAT THE WATTAGE USED MUST BE THE WATTAGE OF
 THE TRACK LIGHTING HEADS WITH A *MINIMUM* OF 30VA PER
 FT. THIS MEANS WHICH EVER FIGURE IS HIGHER BASED ON THE
 MINIMUM OF THE TWO.
 EXAMPLE:
 IF THE TOTAL NUMBER OF TRACK FIXTURES WERE 100 AND EACH
 WAS 75WATTS EACH THIS WOULD BE 7500VA.
 IF THE TOTAL LENGTH OF THE TRACK WAS 300FT AND THE
 MINIMUM PER FOOT OF TRACK AS STATED FROM THE FBC WAS
 30VA PER FT, THEN THE TOTAL OF 9000VA WOULD BE
 REQUIRED.
 ** PLEASE SEE THE TOTAL LENGTH OFTRACK PER LINEAR
 FEET ON PLANS WITH THE 30VA MINIMUM PER FOOT EXCEEDS
 THE TOTAL WATTAGE OF THE TRACK HEADS BEING USED IN THE
 CALCULATIONS.(PLEASE ADJUST).
  
 3) NOTE: PLEASE SEE THE TWO PREVIOUS REVIEWS STATED
 THAT *NO**EQUIPMENT GROUNDING CONDUCTOR* IS PERMITTED
 BEFORE THE FIRST MEANS OF DISCONNECT YET THE RISER
 STILL INDICATES THIS CONDUCTOR ON THE LINE SIDE OF THE
 SERVICE MAIN.
 PLEASE SEE 250.6 AND 250.24B. PLEASE KNOW IF THIS
 CONDUCTOR IS INSTALLED ON THE LINE SIDE OF THE MAIN AND
 THE MAIN THE GROUNDED CONDUCTOR IS BONDED AS REQUIRED
 PER 250.24B, THEN THIS WOULD CREATE A PARALLEL PATH
 WITH THE NEUTRAL(GROUNDED) CONDUCTOR AND THEREFORE
 CREATING *OBJECTIONABLE CURRENTS* AS STATED IN 250.6 OF
 THE NEC.
 PLEASE REMOVE.
  
 4) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS AND REPEAT CODE
 COMPLIANT COMMENTS. AS THE PLANS WERE SUBMITTED FOR
 ONLY *PLAN REVIEW* THE FIRST TIME, THIS IS NOT ASSESSED
 AT THIS TIME. PLEASE KNOW IF THE PLANS ARE RESUBMITTED
 WITH OUT THE ABOVE NOTES #2 AND #3 BEING ADDRESSED THIS
 OFFICE WILL BE REQUIRED PER THE ABOVE FLORIDA STATUTES
 TO ASSESS THE FOUR TIMES PLAN REVIEW FEE FOR THE
 PORTION OF THE PERMIT FEE ATTRIBUTED TO PLAN REVIEW.
 THIS ISTO THE DESIGN PROFESSIONAL.
 THIS FEE WOULD NOT BE THE RESPONSIBILITY OF THE OWNER
 OR CONTRACTOR.
 THIS IS ONLY A NOTICE AT THIS TIME.
 PLEASE ALSO KNOW ONE SET OF ELECTRICAL PLANS AND ENERGY
 CALCULATIONS ARE BEING RETAINED BY THIS OFFICE AT THIS
 TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]