| Date |
Text |
| 2007-06-15 16:55:13 | DENIED |
| | REFERENCE: FBC-2004 |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 BUILDING |
| | WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. THE SIGNATURE OF THE ARCHITECT IS REQUIRED WHEN |
| | SEALING EACH SHEET. IT APPEARS THAT INITIALS HAVE BEEN |
| | USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| | ARCHITECT, PLEASE PROVIDE A SIGNED, SEALED, AND |
| | NOTORIZED LETTER FOR OUR FILES. FAC 61G1-16.003, |
| | 61G1-16.004((5) & FS 481.2055. |
| | ******RESPONSE NOTED, BUT MULTIPLE LEGAL SIGNATURES ARE |
| | NOT APPROVED. ONLY THE RECOGNIZED LEGAL SIGNATURE OF |
| | THE ARCHITECT OF RECORD WILL BE ACCEPTED. |
| | |
| | 3. ROUTE PLANS TO THE STATE OF FLORIDA, DEPT OF |
| | BUSINESS REGULATION, HOTEL AND RESTAURANT DIVISION FOR |
| | PLAN REVIEW PRIOR TO RESUBMITTING FOR REVIEW. A MINIMUM |
| | OF TWO REVIEWED AND STAMPED PLANS WITH THE "TWO PAGE |
| | WORKSHEETS" ATTACHED TO THE STAMPED SHEET ARE REQUIRED |
| | FOR REVIEW AT THE CITY WPB. SECTION 102.2.1. |
| | ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED |
| | COMPLETLY. ONLY ONE SET OF PLANS IS STAMPED, AND THE |
| | TWO PAGE "WORKSHEETS" ARE NOT ATTACHED TO THE STAMPED |
| | SHEET. |
| | |
| | 4. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY |
| | DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY |
| | COMPO, (561) 822-2272, OR BY FAX (561) 822-2287, OR |
| | E-MAIL [email protected]. SECTION III OF THE MUNICIPAL |
| | CODE. |
| | ******RESPONSE NOTED, BUT NO ATTACHED LETTER SHOWING |
| | APROVAL FOUND IN RESUBMITTAL OF PLANS. |
| | |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | |
| | 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE |
| | FOLLOWING INFORMATION: |
| | |
| | A. OK |
| | |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ******RESPONSE NOTED, BUT MANUF. SHEETS FOR ITEM #41 |
| | INDICATES 50,000 BTU'S AND THE RISER DIAGRAM INDICATES |
| | 100,000 BTU'S. ALSO SUBMIT THE UL LISTING FOR THIS |
| | PRODUCT.--ITEM 38 MANUF. SPECIFICATION SHEETS ARE |
| | NOT LEGIBLE AND DO NOT INDICATE BTU OR CFH INPUT |
| | RATING.--ITEM 47 (7), NOT SUBMITTED. (NUMBER 47 NOT |
| | IN LEGEND). PLEASE SUBMIT MANUF SPECIFICATION SHEETS |
| | FOR THE TANKLESS WATER HEATERS.--TWO COPIES OF THE |
| | GAS MANUF SPECIFICATION SHEETS REQUIRED FOR REVIEW. |
| | ONLY ONE SUBMITTED. SECTION 106.1. |
| | |
| | 10. OK |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. ALL ELEC., MECH., & PLUMBING SHEETS. ENGINEERS |
| | SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS, AND LICENSE |
| | NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION |
| | NUMBER ON THE ENGINEERING BUSINESS ON EACH SHEET. FAC |
| | 61G15-23.002(2) & FS 471.025 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |