Plan Review Notes
Plan Review Notes For Permit 07030094
Permit Number 07030094
Review Stop P
Sequence Number 2
Notes
Date Text
2007-06-15 16:55:13DENIED
 REFERENCE: FBC-2004
 FBC-2004 CHAPTER 1
 FBC-2004 BUILDING
 WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. THE SIGNATURE OF THE ARCHITECT IS REQUIRED WHEN
 SEALING EACH SHEET. IT APPEARS THAT INITIALS HAVE BEEN
 USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ARCHITECT, PLEASE PROVIDE A SIGNED, SEALED, AND
 NOTORIZED LETTER FOR OUR FILES. FAC 61G1-16.003,
 61G1-16.004((5) & FS 481.2055.
 ******RESPONSE NOTED, BUT MULTIPLE LEGAL SIGNATURES ARE
 NOT APPROVED. ONLY THE RECOGNIZED LEGAL SIGNATURE OF
 THE ARCHITECT OF RECORD WILL BE ACCEPTED.
  
 3. ROUTE PLANS TO THE STATE OF FLORIDA, DEPT OF
 BUSINESS REGULATION, HOTEL AND RESTAURANT DIVISION FOR
 PLAN REVIEW PRIOR TO RESUBMITTING FOR REVIEW. A MINIMUM
 OF TWO REVIEWED AND STAMPED PLANS WITH THE "TWO PAGE
 WORKSHEETS" ATTACHED TO THE STAMPED SHEET ARE REQUIRED
 FOR REVIEW AT THE CITY WPB. SECTION 102.2.1.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED
 COMPLETLY. ONLY ONE SET OF PLANS IS STAMPED, AND THE
 TWO PAGE "WORKSHEETS" ARE NOT ATTACHED TO THE STAMPED
 SHEET.
  
 4. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY
 DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY
 COMPO, (561) 822-2272, OR BY FAX (561) 822-2287, OR
 E-MAIL [email protected]. SECTION III OF THE MUNICIPAL
 CODE.
 ******RESPONSE NOTED, BUT NO ATTACHED LETTER SHOWING
 APROVAL FOUND IN RESUBMITTAL OF PLANS.
  
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ******RESPONSE NOTED, BUT MANUF. SHEETS FOR ITEM #41
 INDICATES 50,000 BTU'S AND THE RISER DIAGRAM INDICATES
 100,000 BTU'S. ALSO SUBMIT THE UL LISTING FOR THIS
 PRODUCT.--ITEM 38 MANUF. SPECIFICATION SHEETS ARE
 NOT LEGIBLE AND DO NOT INDICATE BTU OR CFH INPUT
 RATING.--ITEM 47 (7), NOT SUBMITTED. (NUMBER 47 NOT
 IN LEGEND). PLEASE SUBMIT MANUF SPECIFICATION SHEETS
 FOR THE TANKLESS WATER HEATERS.--TWO COPIES OF THE
 GAS MANUF SPECIFICATION SHEETS REQUIRED FOR REVIEW.
 ONLY ONE SUBMITTED. SECTION 106.1.
  
 10. OK
  
 **********NEW COMMENT**********
  
 1B. ALL ELEC., MECH., & PLUMBING SHEETS. ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS, AND LICENSE
 NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER ON THE ENGINEERING BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]