| Plan Review Notes For Permit 07030094 |
| Permit Number |
07030094 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-06-07 08:38:28 | ---------------DENIED----------------- | | | | | | FBC 2004 CODE FAMILY W/ 2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLWOING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS FOR CONTINUITY. ADDITIONAL | | | COMMENTS ARE AT THE NED OF THIS REVIEW. | | | | | | 1. PLEASE REMOVE REFERENCE TO CODES WHICH ARE NOT | | | ADOPTED BY THE STATE OF FLORIDA SUCH AS THE IMC ANS | | | STANDARD CODES. | | | | | | 2. PRE-ENGINEERED A/C STANDS ARE STRUCTURAL ELEMNTS AS | | | DEFINED BY FAC 9B-72. PRODUCT APPROVAL IS REQUIRED. | | | PLEASE SEE WWW.FLORIDABUILDING.ORG FOR MORE INFORMATION | | | ON THE FLORIDA PRODUCT APPROVAL SYSTEM. ALSO, ASCE 7-98 | | | IS NO LONGER THE REFERENCE STANDARD UNDER THE 2004 FBC. | | | DESIGN LOADS ARE TO COMPLY WITH ASCE 7-02. | | | | | | 3. OK | | | NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN | | | HOOD, HOOD SUPPRESSION, WALK-IN COOLER/FREEZERS. | | | | | | 4. DRAWINGS STILL DO NOT SHOW COMPLIANCE WITH FBC,M | | | 307.2.3 FOR AUXILIARY DRAIN PROTECTION. | | | | | | 5. OK | | | | | | 6.OK | | | | | | NEW COMMENTS | | | | | | A. ENERGY CALCULATIONS SHOULD BE ON FORM 400B-04R | | | GENERATED BY FLA/COM-2004 V2.5. | | | | | | B. PLANS WHICH ARE SIGNED AND SEALED BY AN ENGINEER OF | | | RECORD SHALL COMPLY WITH FAC 61G1523.002. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | | | | RONALS J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|