Plan Review Notes
Plan Review Notes For Permit 07030094
Permit Number 07030094
Review Stop M
Sequence Number 2
Notes
Date Text
2007-06-07 08:38:28---------------DENIED-----------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLWOING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR CONTINUITY. ADDITIONAL
 COMMENTS ARE AT THE NED OF THIS REVIEW.
  
 1. PLEASE REMOVE REFERENCE TO CODES WHICH ARE NOT
 ADOPTED BY THE STATE OF FLORIDA SUCH AS THE IMC ANS
 STANDARD CODES.
  
 2. PRE-ENGINEERED A/C STANDS ARE STRUCTURAL ELEMNTS AS
 DEFINED BY FAC 9B-72. PRODUCT APPROVAL IS REQUIRED.
 PLEASE SEE WWW.FLORIDABUILDING.ORG FOR MORE INFORMATION
 ON THE FLORIDA PRODUCT APPROVAL SYSTEM. ALSO, ASCE 7-98
 IS NO LONGER THE REFERENCE STANDARD UNDER THE 2004 FBC.
 DESIGN LOADS ARE TO COMPLY WITH ASCE 7-02.
  
 3. OK
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 HOOD, HOOD SUPPRESSION, WALK-IN COOLER/FREEZERS.
  
 4. DRAWINGS STILL DO NOT SHOW COMPLIANCE WITH FBC,M
 307.2.3 FOR AUXILIARY DRAIN PROTECTION.
  
 5. OK
  
 6.OK
  
 NEW COMMENTS
  
 A. ENERGY CALCULATIONS SHOULD BE ON FORM 400B-04R
 GENERATED BY FLA/COM-2004 V2.5.
  
 B. PLANS WHICH ARE SIGNED AND SEALED BY AN ENGINEER OF
 RECORD SHALL COMPLY WITH FAC 61G1523.002.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
  
 RONALS J REGUEIRO
 561.805.6719
 [email protected]