Plan Review Notes
Plan Review Notes For Permit 07030094
Permit Number 07030094
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-07-05 15:38:29***DENIED***
  
 FROM PREVIOUS FIRE REVIEW
  
 1) OK
  
 2) OK
  
 3) OK
  
 4) OK
  
 5) OK PLEASE ADD NOTE TO PLANS FOR CLARIFICATION AS
 THIS IS A LOCAL REQUIREMENT. PLEASE CLARIFY IF THERE IS
 AN EXISTING FULL FIRE ALARM SYSTEM. IT IS NOTED THAT
 THERE IS AN AUTOMATIC FIRE SPRINKLER SYSTEM THAT AT A
 MINIMUM SHALL BE MONITORED.
  
 6) OK NOTE 29 DOES NOT MENTION NFPA 96 WHICH IS
 REFERENCED ON M3.0. PLEASE ADD TO RESPONSE OR PLANS IN
 COMPLIANCE WITH UL 300 FOR WET CHEMICAL SYSTEMS.
  
 7) OK
  
 NEW COMMENT
  
 1) PLEASE SEE NFPA 101, SEC. 12.2.2.2.3 FOR ASSEMBLY
 OCCUPANCIES REQUIRES PANIC OR FIRE EXIT HARDWARE ON
 DOORS IN MEANS OF EGRESS WHERE OCCUPANT LOAD IS 100 OR
 GREATER. NO MENTION IN DOOR SCHEDULE. IF ALREADY
 PROVIDED AS EXISTING CONDITION, PLEASE ADVISE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  