| Plan Review Notes For Permit 07030094 |
| Permit Number |
07030094 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-05 15:38:29 | ***DENIED*** | | | | | | FROM PREVIOUS FIRE REVIEW | | | | | | 1) OK | | | | | | 2) OK | | | | | | 3) OK | | | | | | 4) OK | | | | | | 5) OK PLEASE ADD NOTE TO PLANS FOR CLARIFICATION AS | | | THIS IS A LOCAL REQUIREMENT. PLEASE CLARIFY IF THERE IS | | | AN EXISTING FULL FIRE ALARM SYSTEM. IT IS NOTED THAT | | | THERE IS AN AUTOMATIC FIRE SPRINKLER SYSTEM THAT AT A | | | MINIMUM SHALL BE MONITORED. | | | | | | 6) OK NOTE 29 DOES NOT MENTION NFPA 96 WHICH IS | | | REFERENCED ON M3.0. PLEASE ADD TO RESPONSE OR PLANS IN | | | COMPLIANCE WITH UL 300 FOR WET CHEMICAL SYSTEMS. | | | | | | 7) OK | | | | | | NEW COMMENT | | | | | | 1) PLEASE SEE NFPA 101, SEC. 12.2.2.2.3 FOR ASSEMBLY | | | OCCUPANCIES REQUIRES PANIC OR FIRE EXIT HARDWARE ON | | | DOORS IN MEANS OF EGRESS WHERE OCCUPANT LOAD IS 100 OR | | | GREATER. NO MENTION IN DOOR SCHEDULE. IF ALREADY | | | PROVIDED AS EXISTING CONDITION, PLEASE ADVISE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | | | | | |
|