| Date |
Text |
| 2007-06-05 18:57:10 | ** UNSAT ** |
| | |
| | *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR |
| | CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW, |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT |
| | YET ABLE TO BE MADE. |
| | |
| | ** PLEASE ALSO SEE THERE ARE SEVERAL ITEMS FROM |
| | PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING AND NEW |
| | COMMENTS BASED ON REVISED SHEETS OR SUBMITTED DOCUMENTS |
| | WHICH WERE NOT THE SAME AS PREVIUS SUBMITTED PLANS. |
| | |
| | ** PLANS HAVE NOW BEEN SUBMITTED FOR PERMIT. |
| | |
| | 1) NOTE:PLEASE SEE THE CODES AS STATED ON THE COVER |
| | SHEETS INDICATE 2004 FBC WITH 2006 WPB AND PB |
| | AMENDMENTS WHICH SHOULD INDICATE THE *2006 REVISIONS*. |
| | THESE 2006 REVISIONS ARE REVISIONS ADOPTED BY THE STATE |
| | FOR THE FLORIDA BUILDING CODE AS OF DECEMBER 8TH, 2006. |
| | PLEASE SEE WPB AND PB IS TWO SEPARATE MUNICIPALITIES. |
| | PLEASE SEE THE ADA IS REFERENCING A 2006 FBC ? SHOULD |
| | NOT THIS ALSO READ THE2004 FBC W/ 2006 REVISIONS. |
| | PLEASE SEE OTHER POSSIBLE COMMENTS FROM OTHER TRADES. |
| | |
| | |
| | 2) NOTE: PLEASE SEE THE LETTER INDICATING THE USE OF |
| | MULTIPLE SIGNATURES AS THE LEGAL SIGNATURE OF THE |
| | SINGLE ARCHITECT OF RECORD FOR FILE IS NOT ACCEPTABLE. |
| | THIS MAY ONLY BE THE LEGAL SIGNATURE OF THE DESIGNER. |
| | PLEASE SEE THE COMMENT WITH RESPECT TO THE ENERGY |
| | CALCULATIONS AS THESE ARE SIGNED AND SEALED HOWEVER ARE |
| | NOT SIGNED WITH EITHER OF THE SIGNATURES ON LETTER AND |
| | IN FACT THIS *SIGNATURE* IS COMPLETELY DIFFERENT. |
| | PLEASE SEE THE FLORIDA STATUTES WHICH REQUIRES THE |
| | ORIGINAL SIGNATURE, DATE AND SEAL ON DOCUMENTS. THIS |
| | WAS NOT DONE AND DOCUMENTS WILL BE RETAINED BY THIS |
| | OFFICE. |
| | |
| | 3) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| | AS REQUIRED UNDER FLORIDA ADMINISTRATIVE CODE |
| | 61G1523.002 FOR THE ENGINEER OF RECORD. PLEASE SEE THE |
| | MISSING PRINTED NAME AND PRINTED LICENSE NUMBER. |
| | |
| | 4) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC |
| | CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1, |
| | .1.2 AND .1.3. |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT |
| | CONTAIN THE MOST RECENT ADOPTED VERSION PER THE FBC. |
| | PLEASE SEE THE PREVIOUS NOTE WHICH REQUIRES THE |
| | DESIGNER(S) OF RECORD RESPONSIBLE FOR SCOPE OF WORK TO |
| | *SIGN, DATE AND SEAL* SAID DOCUMENTS. THIS IS NOT ONLY |
| | REQUIRED PER FS 471.025, 481.221, FAC 61G15-23, 61G1-16 |
| | BUT ALSO FBC 13-103.1.1.1. |
| | PLEASE SEE THE FIXTURES AND WATTAGES AS SHOWN ON ENERGY |
| | CALCULATIONS DO NOT CORRELATE WITH THE SUBMITTED PLANS |
| | AND FIXTURE LEGEND(S). |
| | PLEASE SEE THE TWO FIXTURE LEGENDS AS SUBMITTED ON THE |
| | ARCHITECTURAL AND ELECTRICAL PLANS DO NOT CORRELATE. |
| | PLEASE SEE THE LIGHTING CONTROL METHODS ON THE ENERGY |
| | CALCULATIONS DOES NOT CORRELATE WITH PLANS AS THESE ARE |
| | INDICATING *MANUAL ON/OFF8 WHICH IS NOT POSSIBLE WHEN |
| | THE PLANS INDICATE *AUTOMATED* MEANS. PLEASE ADJUST AND |
| | COORDINATE. |
| | PLEASE SUBMIT THE TIME SCHEDULING. |
| | PLEASE INDICATE THE REQUIRED OVER RIDE DEVICES AND |
| | LOCATION PER CODE. |
| | PLEASE INDICATE AND SHOW LOCATIONS OF DEVICES FOR |
| | SEPARATE SPACES. |
| | PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES CHOSEN |
| | IN THE DESIGN. THE TIMES FOR OVER RIDES CAN NOT BE |
| | REVIEWED UNTIL A DEVICE IS SHOWN. PLEASE INDICATE |
| | OCCUPANCY TYPE DEVICES OR TIMER OVER RIDES. PLEASE |
| | INDICATE THE TIMES AS CODE PERMITS 4HRS MAXIMUM ON |
| | TIMER/MANUAL OVER RIDES AND 30 MINS FOR OS TYPE |
| | DEVICES. |
| | PLEASE SEE THE TYPE OF FIXTURES ON PLANS NEED TO |
| | COORDINATE WITH THE ENERGY CALCULATIONS. |
| | PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING MINIMUM |
| | TO BE FIGURED. |
| | PLEASE SEE 13-415.1.AB.1.1, 13-415.2 |
| | *** PLEASE BE SURE TO SEE 13-415.2.ABC.1.2** |
| | |
| | 5) NOTE: PLEASE SEE AS MENTIONED ON THE PREVIOUS |
| | REVIEW, THE APPLIED VALUE MUST INCLUDE ALL LABOR, |
| | MATERIALS AND EQUIPMENT PERMANENTLY INSTALLED EVEN IF |
| | ANY OF THE ABOVE IS OWNER SUPPLIED. THE VALUE FOR SCOPE |
| | OF WORK IS LOW. |
| | PLEASE SEE FBC 108. |
| | |
| | 6) NOTE: PLEASE KNOW THAT ANY PHONE/CATV LOW VOLTAGE |
| | WILL BE UNDER SEPARATE PERMIT. THESE PLANS MAY BE |
| | REFERENCED FOR A TURN AROUND PERMIT. THE FEES FOR THE |
| | LV PERMIT ARE SEPARATE. |
| | |
| | 7) NOTE: PLEASE SEE RISER STILL SHOWS AN *EQUIPMENT |
| | GROUNDING CONDUCTOR* BEING INSTALLED BEFORE THE FIRST |
| | MEANS OF DISCONNECT WHICH WILL CAUSE OBJECTIONABLE |
| | CURRENTS. PLEASE SEE 250.6 AND 250.24B. PLEASE REMOVE. |
| | |
| | 8) NOTE: PLEASE SEE THE CIRCUITING FOR THE SHOW WINDOW |
| | RECEPTACLES AS THE CIRCUITS TO PANEL INDICATE 14 AND |
| | 16, YET THE PLANS INDICATE CIRCUITS 16 AT BOTH |
| | LOCATIONS. |
| | PLEASE COORDINATE. |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE PROVIDE THE LOAD ANALYSIS/LOAD SUMMARY |
| | OF THE LOADS SHOWN FOR THE SERVICE FOR SPACE #502. |
| | PLEASE SEE THE LOADS FOR TRACK LIGHTING, NORMAL |
| | LIGHTING AND OTHER LIGHTING DO NOT ADD UP TO THE |
| | FIGURES ACCORDING TO THE NEC FOR MINIMUM LOADS TO BE |
| | FIGURED. |
| | PLEASE SEE THE CODE SECTIONS GIVEN ON PREVIOUS REVIEW |
| | AND SHOW A BREAKDOWN ON HOW LOADS WERE DERIVED. THIS |
| | REVIEWER WENT THROUGH THE CALCULATIONS TWICE AND CAME |
| | UP WITH FIGURES WHICH ARE LARGER THAN SHOWN. PLEASE |
| | INCLUDE THE KW RATINGS FOR A/C. PLEASE ALSO SEE 424.3B |
| | AS THE OCP FOR EACH OF THESE UNITS WHICH CONTAIN HEAT |
| | WILL REQUIRE THE SIZING AT 125% FOR MINIMUM OCP. PLEASE |
| | SEE THE LOAD FOR THE UNOCCUPIED SPACE MUST BE FIGURED |
| | INTO THE SPACE. THIS IS A MINIMUM LOAD FOR SERVICE. IT |
| | HAS NO RELEVANCE THAT THE SPACE IS NOT OCCUPIED, AS IT |
| | MAY BE BY NOW, NEXT WEEK OR ANYTIME THERE AFTER. IF THE |
| | SPACE IS FED FROM THE SAME SERVICE THEN THE SERVICE |
| | MUST INCLUDE THE MINIMUM LOADS PER CODE. PLEASE |
| | ADJUST. |
| | PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43 |
| | B.ETC. |
| | 215.5, FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 10) NOTE: PLEASE PROVIDE AIC RATING FOR NEW MAIN. |
| | 110.9. THIS IS THE SAME NOTE. THE RATINGS ARE SHOWN FOR |
| | PANELS, BUT NOT FOR MAINS. (PLEASE VERIFY THE 65K |
| | RATING SHOWN FOR THE EXISTING AND NEW PANELS AND BRANCH |
| | BREAKERS. AS THERE IS A RATING ABOVE THE 29K OF COMMON |
| | SIZE WHICH HAS A SUBSTANTIALLY LESS EXPENSE) (THIS IS |
| | ONLY NOTED AS THE HIGHER RATING MAY BE INSTALLED AND |
| | DOES NOT VIOLATE THE CODE IN ANY WAY). PLEASE KNOW IF |
| | THE PLANS CALL FOR THIS RATING, THEN THIS WILL BE |
| | REQUIRED.) |
| | FBC 106.3.5.1.2 |
| | |
| | 11) NOTE: PLEASE SEE 210.8B2 AS ALL RECEPTACLES IN |
| | KITCHENS AND AREAS OF THE LIKE ALONG WITH FOOD PREP |
| | SHALL BE GFI/ GFI PROTECTED. |
| | NO CHANGES COULD BE LOCATED ON PLANS FOR THIS. |
| | |
| | 12) NOTE:PLEASE LABEL ALL MAINS FOR SERVICE. ( 1OF 5, |
| | 3 OF 5 ETC). |
| | FBC 106.1.2 , NEC 230.2E |
| | PLEASE INDICATE THE LOCATION OF THE NEW PROPOSED MAIN. |
| | THIS IS REQUIRED TO BE GROUPED PER 230.72 |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |