Plan Review Notes
Plan Review Notes For Permit 07030094
Permit Number 07030094
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-05 18:57:10** UNSAT **
  
 *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR
 CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT
 YET ABLE TO BE MADE.
  
 ** PLEASE ALSO SEE THERE ARE SEVERAL ITEMS FROM
 PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING AND NEW
 COMMENTS BASED ON REVISED SHEETS OR SUBMITTED DOCUMENTS
 WHICH WERE NOT THE SAME AS PREVIUS SUBMITTED PLANS.
  
 ** PLANS HAVE NOW BEEN SUBMITTED FOR PERMIT.
  
 1) NOTE:PLEASE SEE THE CODES AS STATED ON THE COVER
 SHEETS INDICATE 2004 FBC WITH 2006 WPB AND PB
 AMENDMENTS WHICH SHOULD INDICATE THE *2006 REVISIONS*.
 THESE 2006 REVISIONS ARE REVISIONS ADOPTED BY THE STATE
 FOR THE FLORIDA BUILDING CODE AS OF DECEMBER 8TH, 2006.
 PLEASE SEE WPB AND PB IS TWO SEPARATE MUNICIPALITIES.
 PLEASE SEE THE ADA IS REFERENCING A 2006 FBC ? SHOULD
 NOT THIS ALSO READ THE2004 FBC W/ 2006 REVISIONS.
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM OTHER TRADES.
  
  
 2) NOTE: PLEASE SEE THE LETTER INDICATING THE USE OF
 MULTIPLE SIGNATURES AS THE LEGAL SIGNATURE OF THE
 SINGLE ARCHITECT OF RECORD FOR FILE IS NOT ACCEPTABLE.
 THIS MAY ONLY BE THE LEGAL SIGNATURE OF THE DESIGNER.
 PLEASE SEE THE COMMENT WITH RESPECT TO THE ENERGY
 CALCULATIONS AS THESE ARE SIGNED AND SEALED HOWEVER ARE
 NOT SIGNED WITH EITHER OF THE SIGNATURES ON LETTER AND
 IN FACT THIS *SIGNATURE* IS COMPLETELY DIFFERENT.
 PLEASE SEE THE FLORIDA STATUTES WHICH REQUIRES THE
 ORIGINAL SIGNATURE, DATE AND SEAL ON DOCUMENTS. THIS
 WAS NOT DONE AND DOCUMENTS WILL BE RETAINED BY THIS
 OFFICE.
  
 3) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 AS REQUIRED UNDER FLORIDA ADMINISTRATIVE CODE
 61G1523.002 FOR THE ENGINEER OF RECORD. PLEASE SEE THE
 MISSING PRINTED NAME AND PRINTED LICENSE NUMBER.
  
 4) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1,
 .1.2 AND .1.3.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT
 CONTAIN THE MOST RECENT ADOPTED VERSION PER THE FBC.
 PLEASE SEE THE PREVIOUS NOTE WHICH REQUIRES THE
 DESIGNER(S) OF RECORD RESPONSIBLE FOR SCOPE OF WORK TO
 *SIGN, DATE AND SEAL* SAID DOCUMENTS. THIS IS NOT ONLY
 REQUIRED PER FS 471.025, 481.221, FAC 61G15-23, 61G1-16
 BUT ALSO FBC 13-103.1.1.1.
 PLEASE SEE THE FIXTURES AND WATTAGES AS SHOWN ON ENERGY
 CALCULATIONS DO NOT CORRELATE WITH THE SUBMITTED PLANS
 AND FIXTURE LEGEND(S).
 PLEASE SEE THE TWO FIXTURE LEGENDS AS SUBMITTED ON THE
 ARCHITECTURAL AND ELECTRICAL PLANS DO NOT CORRELATE.
 PLEASE SEE THE LIGHTING CONTROL METHODS ON THE ENERGY
 CALCULATIONS DOES NOT CORRELATE WITH PLANS AS THESE ARE
 INDICATING *MANUAL ON/OFF8 WHICH IS NOT POSSIBLE WHEN
 THE PLANS INDICATE *AUTOMATED* MEANS. PLEASE ADJUST AND
 COORDINATE.
 PLEASE SUBMIT THE TIME SCHEDULING.
 PLEASE INDICATE THE REQUIRED OVER RIDE DEVICES AND
 LOCATION PER CODE.
 PLEASE INDICATE AND SHOW LOCATIONS OF DEVICES FOR
 SEPARATE SPACES.
 PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES CHOSEN
 IN THE DESIGN. THE TIMES FOR OVER RIDES CAN NOT BE
 REVIEWED UNTIL A DEVICE IS SHOWN. PLEASE INDICATE
 OCCUPANCY TYPE DEVICES OR TIMER OVER RIDES. PLEASE
 INDICATE THE TIMES AS CODE PERMITS 4HRS MAXIMUM ON
 TIMER/MANUAL OVER RIDES AND 30 MINS FOR OS TYPE
 DEVICES.
 PLEASE SEE THE TYPE OF FIXTURES ON PLANS NEED TO
 COORDINATE WITH THE ENERGY CALCULATIONS.
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING MINIMUM
 TO BE FIGURED.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2
 *** PLEASE BE SURE TO SEE 13-415.2.ABC.1.2**
  
 5) NOTE: PLEASE SEE AS MENTIONED ON THE PREVIOUS
 REVIEW, THE APPLIED VALUE MUST INCLUDE ALL LABOR,
 MATERIALS AND EQUIPMENT PERMANENTLY INSTALLED EVEN IF
 ANY OF THE ABOVE IS OWNER SUPPLIED. THE VALUE FOR SCOPE
 OF WORK IS LOW.
 PLEASE SEE FBC 108.
  
 6) NOTE: PLEASE KNOW THAT ANY PHONE/CATV LOW VOLTAGE
 WILL BE UNDER SEPARATE PERMIT. THESE PLANS MAY BE
 REFERENCED FOR A TURN AROUND PERMIT. THE FEES FOR THE
 LV PERMIT ARE SEPARATE.
  
 7) NOTE: PLEASE SEE RISER STILL SHOWS AN *EQUIPMENT
 GROUNDING CONDUCTOR* BEING INSTALLED BEFORE THE FIRST
 MEANS OF DISCONNECT WHICH WILL CAUSE OBJECTIONABLE
 CURRENTS. PLEASE SEE 250.6 AND 250.24B. PLEASE REMOVE.
  
 8) NOTE: PLEASE SEE THE CIRCUITING FOR THE SHOW WINDOW
 RECEPTACLES AS THE CIRCUITS TO PANEL INDICATE 14 AND
 16, YET THE PLANS INDICATE CIRCUITS 16 AT BOTH
 LOCATIONS.
 PLEASE COORDINATE.
 FBC 106.1.2
  
 9) NOTE: PLEASE PROVIDE THE LOAD ANALYSIS/LOAD SUMMARY
 OF THE LOADS SHOWN FOR THE SERVICE FOR SPACE #502.
 PLEASE SEE THE LOADS FOR TRACK LIGHTING, NORMAL
 LIGHTING AND OTHER LIGHTING DO NOT ADD UP TO THE
 FIGURES ACCORDING TO THE NEC FOR MINIMUM LOADS TO BE
 FIGURED.
 PLEASE SEE THE CODE SECTIONS GIVEN ON PREVIOUS REVIEW
 AND SHOW A BREAKDOWN ON HOW LOADS WERE DERIVED. THIS
 REVIEWER WENT THROUGH THE CALCULATIONS TWICE AND CAME
 UP WITH FIGURES WHICH ARE LARGER THAN SHOWN. PLEASE
 INCLUDE THE KW RATINGS FOR A/C. PLEASE ALSO SEE 424.3B
 AS THE OCP FOR EACH OF THESE UNITS WHICH CONTAIN HEAT
 WILL REQUIRE THE SIZING AT 125% FOR MINIMUM OCP. PLEASE
 SEE THE LOAD FOR THE UNOCCUPIED SPACE MUST BE FIGURED
 INTO THE SPACE. THIS IS A MINIMUM LOAD FOR SERVICE. IT
 HAS NO RELEVANCE THAT THE SPACE IS NOT OCCUPIED, AS IT
 MAY BE BY NOW, NEXT WEEK OR ANYTIME THERE AFTER. IF THE
 SPACE IS FED FROM THE SAME SERVICE THEN THE SERVICE
 MUST INCLUDE THE MINIMUM LOADS PER CODE. PLEASE
 ADJUST.
 PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43
 B.ETC.
 215.5, FBC 106.3.5.1.2, 106.1.2
  
 10) NOTE: PLEASE PROVIDE AIC RATING FOR NEW MAIN.
 110.9. THIS IS THE SAME NOTE. THE RATINGS ARE SHOWN FOR
 PANELS, BUT NOT FOR MAINS. (PLEASE VERIFY THE 65K
 RATING SHOWN FOR THE EXISTING AND NEW PANELS AND BRANCH
 BREAKERS. AS THERE IS A RATING ABOVE THE 29K OF COMMON
 SIZE WHICH HAS A SUBSTANTIALLY LESS EXPENSE) (THIS IS
 ONLY NOTED AS THE HIGHER RATING MAY BE INSTALLED AND
 DOES NOT VIOLATE THE CODE IN ANY WAY). PLEASE KNOW IF
 THE PLANS CALL FOR THIS RATING, THEN THIS WILL BE
 REQUIRED.)
 FBC 106.3.5.1.2
  
 11) NOTE: PLEASE SEE 210.8B2 AS ALL RECEPTACLES IN
 KITCHENS AND AREAS OF THE LIKE ALONG WITH FOOD PREP
 SHALL BE GFI/ GFI PROTECTED.
 NO CHANGES COULD BE LOCATED ON PLANS FOR THIS.
  
 12) NOTE:PLEASE LABEL ALL MAINS FOR SERVICE. ( 1OF 5,
 3 OF 5 ETC).
 FBC 106.1.2 , NEC 230.2E
 PLEASE INDICATE THE LOCATION OF THE NEW PROPOSED MAIN.
 THIS IS REQUIRED TO BE GROUPED PER 230.72
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]