| Date |
Text |
| 2007-03-21 07:41:57 | DENIED |
| | REFERENCE: FBC-2004 |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 BUILDING |
| | WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS, THE PRINTED NAME OF THE ARCHITECT AND |
| | THE BUSINESS LICENSE NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), ARE REQUIRED IN THE TITLE BLOCK. FAC |
| | 61G1-16.004(2)(6) & FS 481.219, 481.2055. |
| | |
| | 2. THE SIGNATURE OF THE ARCHITECT IS REQUIRED WHEN |
| | SEALING EACH SHEET. IT APPEARS THAT INITIALS HAVE BEEN |
| | USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| | ARCHITECT, PLEASE PROVIDE A SIGNED, SEALED, AND |
| | NOTORIZED LETTER FOR OUR FILES. FAC 61G1-16.003, |
| | 61G1-16.004((5) & FS 481.2055. |
| | |
| | 3. ROUTE PLANS TO THE STATE OF FLORIDA, DEPT OF |
| | BUSINESS REGULATION, HOTEL AND RESTURANT DIVISION FOR |
| | PLAN REVIEW PRIOR TO RESUBMITTING FOR REVIEW. A MINIMUM |
| | OF TWO REVIEWED AND STAMPED PLANS WITH THE "TWO PAGE |
| | WORKSHEETS" ATTACHED TO THE STAMPED SHEET ARE REQUIRED |
| | FOR REVIEW AT THE CITY WPB. SECTION 102.2.1. |
| | |
| | 4. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY |
| | DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY |
| | COMPO, (561) 822-2272, OR BY FAX (561) 822-2287, OR |
| | E-MAIL [email protected]. SECTION III OF THE MUNICIPAL |
| | CODE. |
| | |
| | 5. SHT A2.1 ELEVATIONS A2.1-03, A2.1-05, A2.1-06, & |
| | A2.1-08. WALLS WITHIN 2' OF A W/C OR URINAL SHALL HAVE |
| | A "SMOOTH, HARD, NONABSORBENT SURFACE" TO A HEIGHT OF |
| | 4' ABOVE THE FLOOR. ELEVATIONS INDICATE THE REQUIRED |
| | SURFACE ONLY UP TO 45.5". SECTION 1210.2. PLEASE |
| | CORRECT ELEVATIONS. |
| | |
| | 6. SHT P2.0 PLUMBING PLAN KEY NOTES #21, DOUBLE CHECK |
| | VALVE ASSEMBLY IS NOT APPROVED. PLEASE DELETE FROM |
| | FLOOR PLAN AND KEY NOTES. TABLE 608.1. THE RPZV |
| | BACKFLOW IS REQUIRED AND WILL BE SUFFICIENT.--THE |
| | RPZV BACKFLOW WILL BE REQUIRED TO BE INSTALLED A |
| | MAXIMUM OF 4' ABOVE THE FINISHED FLOOR FOR SERVICING |
| | AND CERTIFICATION. AN INDIRECT WASTE RECEPTOR SHALL BE |
| | PROVIDED FOR THE DRAINAGE OFF THE BACKFLOW. SECTION |
| | 802.1.3. |
| | |
| | 7. SHT P5.0 WATER RISER DIAGRAM & PLUMBING PLAN KEY |
| | NOTES #21 THE DOUBLE CHECK VAVLE ASSEMBLY IS NOT |
| | APPROVED. PLEASE DELETE FROM THE RISER AND THE KEY |
| | NOTES. TABLE 608.1. |
| | |
| | 8. SHT P1.0 KITCHEN EQUIPMENT SCHEDULE INDICATES A |
| | FILTERED WATER SYSTEM. THE FILTER SHALL BE NSF-42 |
| | APPROVED. PLEASE SUBMIT THE MANUF. SPECIFICATION SHEETS |
| | SHOWING APPROVAL. SECTIONS 106.1.1 & 611.1. |
| | |
| | 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE |
| | FOLLOWING INFORMATION: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - SHOW ALL LENGTHS. |
| | |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | 10. SHT P5.0 GAS NOTES INDICATE THE GAS DATA WAS BASED |
| | ON THE INTERNATIONAL FUEL GAS CODE. THE ADOPTED CODE IS |
| | FBC-2004 FUEL GAS CODE. PLEASE CHANGED REFERENCE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |