| Plan Review Notes For Permit 07030094 |
| Permit Number |
07030094 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-28 14:53:15 | ------------------DENIED------------------- | | | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | | | | | 1. HVAC GENERAL NOTE 3 AND KEY NOTE 3, PLEASE REFERENCE | | | FBC,M 2004. | | | | | | 2. ROOF MOUNTED EQUIPMENT SHALL BE SECURED TO STRUCTURE | | | TO MEET 140 MPH WIND LOADS PER FBC,M 301.13 AND FBC | | | CH.16. PROVIDE WIND LOAD CALCULATIONS AND STRUCTURAL | | | DETAIL DRAWINGS FOR BUILDING PLAN REVIEW. | | | | | | 3. EF SCHEDULE ON M1.0 SHOWS EF 1A,1B FOR THE GREASE | | | HOOD. M3.0 SHOWS ONLY ONE FAN. PLEASE CLARIFY PER FBC | | | 106.1.1. | | | | | | 4. PLEASE SHOW MEANS OF CONDENSATE DISPOSAL WHICH IS IN | | | COMPLIANCE WITH FBC,M 307, INCLUDING AUXILIARY OR | | | SECONDARY DRAIN PROTECTION PER FBC,M 307.2.3. ALSO SHOW | | | COMPLIANCE WITH FBC 1506.3. | | | | | | 5. PG M1.0 SHOWS VOLUME DAMPERS IN GREASE EXHAUST | | | DUCTS. IS THIS INTENDED OR A MISTAKE? IF IT IS | | | INTENDED, PLEASE PROVIDE SUBMITTAL DATA WITH | | | INSTALLATION DETAIL FOR A PRODUCT LISTED AND LABELED | | | FOR THIS USE. | | | | | | 6. HVAC GENERAL NOTE 24: OUTER JACKET AND INSULATION ON | | | FLEX DUCT CONNECTIONS SHOULD NOT BE COMPRESSED WITH A | | | CLAMP PER FBC,M 603.5.6.3. ALSO, FLEXIBLE DUCT SUPPORTS | | | SHALL BE MINIMUM 1 1/2" WIDE PER FBC,M 603.5.6.6(6). | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE FEEL FREE TO CONTACT: | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|