Plan Review Notes
Plan Review Notes For Permit 07030094
Permit Number 07030094
Review Stop M
Sequence Number 1
Notes
Date Text
2007-03-28 14:53:15------------------DENIED-------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
  
 1. HVAC GENERAL NOTE 3 AND KEY NOTE 3, PLEASE REFERENCE
 FBC,M 2004.
  
 2. ROOF MOUNTED EQUIPMENT SHALL BE SECURED TO STRUCTURE
 TO MEET 140 MPH WIND LOADS PER FBC,M 301.13 AND FBC
 CH.16. PROVIDE WIND LOAD CALCULATIONS AND STRUCTURAL
 DETAIL DRAWINGS FOR BUILDING PLAN REVIEW.
  
 3. EF SCHEDULE ON M1.0 SHOWS EF 1A,1B FOR THE GREASE
 HOOD. M3.0 SHOWS ONLY ONE FAN. PLEASE CLARIFY PER FBC
 106.1.1.
  
 4. PLEASE SHOW MEANS OF CONDENSATE DISPOSAL WHICH IS IN
 COMPLIANCE WITH FBC,M 307, INCLUDING AUXILIARY OR
 SECONDARY DRAIN PROTECTION PER FBC,M 307.2.3. ALSO SHOW
 COMPLIANCE WITH FBC 1506.3.
  
 5. PG M1.0 SHOWS VOLUME DAMPERS IN GREASE EXHAUST
 DUCTS. IS THIS INTENDED OR A MISTAKE? IF IT IS
 INTENDED, PLEASE PROVIDE SUBMITTAL DATA WITH
 INSTALLATION DETAIL FOR A PRODUCT LISTED AND LABELED
 FOR THIS USE.
  
 6. HVAC GENERAL NOTE 24: OUTER JACKET AND INSULATION ON
 FLEX DUCT CONNECTIONS SHOULD NOT BE COMPRESSED WITH A
 CLAMP PER FBC,M 603.5.6.3. ALSO, FLEXIBLE DUCT SUPPORTS
 SHALL BE MINIMUM 1 1/2" WIDE PER FBC,M 603.5.6.6(6).
  