| Plan Review Notes For Permit 07030094 |
| Permit Number |
07030094 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-12 11:54:16 | *****DENIED***** | | | | | | | | | | | | 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.IT IS NOT INDICATED WHETHER THE TENANT SPACE HAS A | | | FIRE SPRINKLER AND/OR A FIRE ALARM SYSTEM.IF SO, ANY | | | MODIFICATIONS TO THESE SYSTEMS AS A RESULT OF THE SCOPE | | | OF WORK, WILL REQUIRE SEPARATE PLANS AND PERMIT FOR THE | | | REMODEL. | | | | | | 4. THEINTERIOR WALL AND CEILING FINISH CLASSIFICATION | | | SHALL BE CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS | | | HAVING AN OCCUPANT LOAD OF 300 OR FEWER.PLEASE | | | SPECIFY. | | | | | | 5.AS PER WEST PALM BEACH FIRE PREVENTION, DUCT SMOKE | | | DETECTOR SHALL INITIATE A GENERAL ALARM. | | | | | | 6.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE | | | WITH NFPA 96 (2001 EDIITION);SEPARATE PLANS AND PEMI | | | WILL BE REQUIRED FOR THE HOOD INSTALLATION AND THE HOOD | | | SUPPRESSION SYSTEM. | | | | | | 7.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE | | | REQUIREMENT. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE (IN THE PLANS) EACH COMMENT | | | WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|