2007-04-12 11:54:16*****DENIED*****
  
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.IT IS NOT INDICATED WHETHER THE TENANT SPACE HAS A
 FIRE SPRINKLER AND/OR A FIRE ALARM SYSTEM.IF SO, ANY
 MODIFICATIONS TO THESE SYSTEMS AS A RESULT OF THE SCOPE
 OF WORK, WILL REQUIRE SEPARATE PLANS AND PERMIT FOR THE
 REMODEL.
  
 4. THEINTERIOR WALL AND CEILING FINISH CLASSIFICATION
 SHALL BE CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS
 HAVING AN OCCUPANT LOAD OF 300 OR FEWER.PLEASE
 SPECIFY.
  
 5.AS PER WEST PALM BEACH FIRE PREVENTION, DUCT SMOKE
 DETECTOR SHALL INITIATE A GENERAL ALARM.
  
 6.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE
 WITH NFPA 96 (2001 EDIITION);SEPARATE PLANS AND PEMI
 WILL BE REQUIRED FOR THE HOOD INSTALLATION AND THE HOOD
 SUPPRESSION SYSTEM.
  
 7.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (IN THE PLANS) EACH COMMENT
 WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722