| 2007-03-11 12:55:27 | ** UNSAT** |
| | |
| | ** PLEASE KNOW THAT PLANS HAVE ONLY BEEN SUBMITTED FOR |
| | A *PLAN REVIEW* ONLY AND HAVE NOT BEEN SUBMITTED FOR |
| | PERMIT. |
| | PLEASE KNOW THAT EVEN IF AND WHEN PLANS ARE CODE |
| | COMPLIANT, PLANS WILL STILL REMAIN IN A *FAILED* STATUS |
| | UNTIL PERMIT APPLICATION, FEES ETC HAVE BEEN DONE. |
| | |
| | ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT YET |
| | SUBMITTED FOR REVIEW, NEW COMMENTS MAY BE POSSIBLE ON |
| | THE FOLLOW UP REVIEW AS REVIEW OF MANY OF THESE ITEMS |
| | CAN NOT BE DONE AT THIS TIME. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. THIS WOULD INCLUDE A-SHEETS AS |
| | WELL AS E-SHEETS. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| | AS REQUIRED UNDER FLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.004 AND FLORIDA STATUTES 481.219 |
| | PLEASE SEE MISSING PRINTED NAME AND MISSING FIRM |
| | LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF |
| | AUTHORIZATION. |
| | THIS OFFICE IS AWARE THAT APPLICATION HAS BEEN MADE TO |
| | THE STATE HOWEVER MAY NOT POSSESS THE TITLE BLOCK AS |
| | SHOWN UNTIL SUCH TIME A CA # FOR THE FIRM HAS BEEN |
| | ISSUED. |
| | *PLEASE ALSO SEE THE STATE ALSO HAS THE ADDRESS LISTED |
| | IN CINCINNATI, OHIO. |
| | |
| | 3) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH WHAT |
| | APPEARS TO BE INITIALS? IF THIS IS INDEED THE LEGAL |
| | SIGNATURE, PLEASE SUBMIT A LETTER FOR SIGNATURE |
| | VERIFICATION. THE LETTER WILL NEED TO BE SIGNED, DATED |
| | AND SEALED ALONG WITH BEING NOTARIZED.PLEASE KNOW |
| | THAT THIS LETTER MUST BE ORIGINAL. |
| | PLEASE KNOW THIS WILL BE PLACED IN OUR SIGNATURE FILE |
| | FOR FUTURE REFERENCE. |
| | |
| | 4) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC |
| | CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1, |
| | .1.2 AND .1.3. |
| | PLEASE SEE BY DEFINITION THIS SPACE IS IN A BUILDING |
| | GREATER THAN 5K SQ FT. |
| | PLEASE SHOW COMPLIANCE WITH THIS AND IF THERE ARE ANY |
| | QUESTIONS, PLEASE CALL TO GO OVER THIS. |
| | PLEASE SUBMIT LIGHTING POWER DENSITIES PER THE 2004 FBC |
| | W/ 2006 REVISION. PLEASE SEE 13-415.1.AB.1.1, 13-415.2 |
| | FOR LIGHTING PERFORMANCE CALCULATIONS ALONG WITH ENERGY |
| | CALCULATIONS. PLEASE SEE THE CALCULATIONS SUBMITTED ARE |
| | NOT COMPLIANT AT THIS TIME ABSE DON THE INFORMATION |
| | SHOWN. |
| | PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC |
| | FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE |
| | LPD/CALCULATIONSWHICH IS TO BE REVIEWED FOR |
| | COMPLIANCE. |
| | *** PLEASE BE SURE TO SEE 13-415.2.ABC.1.2** PLEASE BE |
| | SURE TO HAVE THE DESIGNER OF RECORD FOR THE ENERGY |
| | CALCULATIONS SIGN, DATE AND SEAL THESE AS REQUIRED PER |
| | 13-103.1.1.1 THESE ARE NOT SEALED WIHT RAISED SEAL AAS |
| | REQUIRED PER SECTION AS STATED. |
| | |
| | **PLEASE SEE NOTES ON PLANS MENTIONS SOME OF THESE |
| | AREAS AS EXISTING FOR NO WORK, YET PLANS INDICATE WORK |
| | BEING DONE IN THESE AREAS. |
| | |
| | 5) NOTE: PLEASE SEE THE VALUE WHEN APPLYING FOR PERMIT |
| | SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF |
| | MATERIALS/EQUIPMENT IS OWNER SUPPLIED. |
| | FBC ADMIN SECTION 108.3 |
| | |
| | 6) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| | ADA REQUIRED AREAS. ANY DEVICE SHALL BE SHOWN ON BASE |
| | PLANS EVEN THOUGH THE SCOPE OF WORK FOR ANY FIRE |
| | SPRINKLER AND FIRE ALARM SYSTEMS WILL BE DONE UNDER |
| | SEPARATE PERMIT. |
| | **DEVICES ARE BEING SHOWN ON PLANS/LEGEND. |
| | |
| | 7) NOTE: PLEASE SEE RISER SHOWS AN *EQUIPMENT GROUNDING |
| | CONDUCTOR* BEING INSTALLED WHICH WILL CAUSE |
| | OBJECTIONABLE CURRENTS. PLEASE SEE 250.6 AND 250.24B. |
| | |
| | 8) NOTE: PLEASE VERIFY THE SERVICE ENTRANCE CONDUCTORS |
| | AND PLACE THE INFORMATION ON RISER. PLEASE SEE THAT THE |
| | RISER MAKES NOTE TO VERIFY, YET THIS INFORMATION SHALL |
| | BE KNOWN AND STATED ON PLANS AT THIS TIME. |
| | PLEASE ALSO SUBMIT COMPLETE LOAD CALCULATIONS ON THE |
| | EXISTING SERVICE AS SHOWN WITH NEW LOAD ADDED TO |
| | SERVICE. |
| | PLEASE SEENEC 2005 220. |
| | NEED TO VERIFY 310.16, 240.4 ETC. |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| | |
| | 9) NOTE: PLEASE SEE THE LOAD ANALYSIS WHICH STATES THE |
| | 2002 NEC FOR CALCULATIONS. |
| | PLEASE KNOW WE ARE UNDER THE 2005. |
| | PLEASE ALSO CLARIFY ON THE LOAD CALCULATIONS FOR SPACE |
| | HOW THE FOLLOWING LOADS WERE DERIVED. |
| | LIGHTING? |
| | TRACK LIGHTS? |
| | RECEPTACLES? |
| | PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43 B. |
| | |
| | 10) NOTE: PLEASE PROVIDE AIC RATING FOR NEW MAIN. |
| | 110.9. |
| | FBC 106.3.5.1.2 |
| | |
| | 11) NOTE: PLEASE SEE 210.8B2 AS ALL RECEPTACLES IN |
| | KITCHENS AND AREAS OF THE LIKE ALONG WITH FOOD PREP |
| | SHALL BE GFI/ GFI PROTECTED. |
| | |
| | 12) NOTE: PLEASE PLACE THE SIZING OF THE BRANCH CIRCUIT |
| | CONDUCTORS ON PANEL SCHEDULES. PLEASE SEE 310.16, |
| | 240.4 |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 13) NOTE: PLEASE LABEL ALL MAINS FOR SERVICE. ( 1OF 5, |
| | 3 OF 5 ETC). |
| | PLEASE PLACE NOTE ON PLANS WHICH WILL REQUIRE THE |
| | REMOVAL OF THE EXISTING METER AND MAIN FOR THE SPACE |
| | SERVICE WHICH IS BEING REPLACED. |
| | THE OLD METER AND MAIN WILL BE REQUIRED BY THIS AHJ TO |
| | BE REMOVED COMPLETELY. |
| | FBC 106.1.2 ADDITIONAL INFORMATION. |
| | 104.6 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |