| 2008-04-04 18:25:32 | SLIDING GLASS DOOR SUBMITTAL, BUILDING REVIEW |
| | CHECKLIST. |
| | REVIEW UNDER FBC2004. |
| | |
| | 1- PROVIDE COPIES OF PRODUCT APPROVAL FOR SLIDING GLASS |
| | DOORS AS REQUIRED BY DCA RULE 9B-72AS REQUESTED ON |
| | PREVIOUS COMMENTS.PACKAGE SUBMITTED NOW DOESN'T |
| | INCLUDE THE PRODUCT APPROVAL AND THERE IS NOT PRODUCT |
| | APPROVAL IN FILE. |
| | |
| | 2- ENGINEER LETTER BY LUCAS A. TURNER, P.E. REGARDING |
| | DOOR ASSEMBLY TO INCLUDE THREE PANELS NEEDS TO PROVIDE |
| | ENGINEERING ANALYSIS SHOWING HOW THE MIDDLE PANEL IS |
| | TAKEN INTO CONSIDERATION TO RESIST THE DESIGN LOADS. |
| | PRODUCT APPROVAL SHOWS THAT TESTED UNIT HAD ONLY TWO |
| | PANELS ON EACH SIDE. ASSEMBLYWITH TWO PANELS SHOWS |
| | THAT BOTH PANELS MAY BESUPPORTED ON THREE SIDES, |
| | WHILEASSEMBLY WITH THREE PANELS SHOWS THAT MIDDLE |
| | PANEL MAY BE SUPPORTED ONLY ON TWO SIDES (TOP AND |
| | BOTTOM).PLEASE, PROVIDE ENGINEERING ANALYSIS TO SHOW |
| | HOW IS THIS ISSUE ADDRESSED. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH SEC. |
| | R301 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | ***NOTE: IF YOU HAVE ANY QUESTIONS REGARDING THIS |
| | ISSUE, PLEASE CONTACT ROBERT BROWN AT (561)805-6652, |
| | SINCE I SHARED THIS ISSUE WITH HIM BECAUSEI AM GOING |
| | TO BE AWAY FROMTHE OFFICE UNTIL APRIL 14TH. |
| | |
| | 3- REMAINDER: |
| | PLEASE PROVIDE ALL INFORMATION REQUESTED ON PROVISO |
| | DATED 7/27/07TO AVOID UNNECESSARY DELAYS IN THE |
| | CERTIFICATE OF OCCUPANCY PROCESS.SEE ATTACHED COPY OR |
| | REVIEWIT ON-LINE. |
| | |
| | JULIO GOMEZ |
| | BUILDING REVIEW CHECKLIST |
| | (561)805-6712 |