| 2007-06-15 16:33:58 | DENIED 2ND TIME |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | 1. SHEET A6 SANITARY RISER: THE FOLLOWING CORRECTIONS |
| | ARE REQUIRED FOR THE RESUBMITTED SANITARY ISOMETRIC |
| | RISER DIAGRAM TO MEET CODE COMPLIANCE. |
| | A} UTILITY: PLEASE DELETE THE "48" A.F.F." |
| | INDICATED BELOW THE WASHER, AND CORRECTLY SIZE THE |
| | STANDPIPE AND TRAP AS BEING 2". PLEASE DELETE THE |
| | INCORRECTLY IDENTIFIED FIXTURE AS BEING AN 1-1/4" LAV |
| | AND CORRECTLY IDENTIFY THE FIXTURE AS BEING AN 1-1/2" |
| | LAUNDRY TRAY (1-1/2" L.T.) |
| | B} HER BATH: CORRECTLY SIZE THE BRANCH DRAIN TO |
| | THE BIDET AS BEING TWO INCH AND THE TRAP TO THE BIDET |
| | AS BEING 1-1/4" |
| | C} HER BATH: A VENT IS REQUIRED FOR THE SHOWER |
| | PER FBC-2004 PLUMBING, TABLE 906.1, A TWO INCH TRAP CAN |
| | NOT BE MORE THAN SIX FEET FROM THE VENT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |