| Plan Review Notes For Permit 07030070 |
| Permit Number |
07030070 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-06-18 14:30:09 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- ARCHITECT TO PROVIDE BUILDING CONSTRUCTION TYPE ON | | | SHEET T1 AND A4 AS REQUIRED BY SEC. 602.1OF FBC | | | 2004. | | | 2- PROVIDE REVISED DRAINAGE PLAN SHOWING WATER BEING | | | DIVERTED AWAY FROM NEIGHBOR'S PROPERTY. | | | 3- REVISE TYPE OF NAIL USED FOR ROOF SHEATHING. NEED | | | "RING SHANK NAILS" AS REQUIRED BY SEC. R803.2.3.12004 | | | FLORIDA RESIDENTIAL CODE. | | | 4- SOIL TEST REPORT NEED TO HAVE THE CERTIFICATEOF | | | AUTHORIZATION NUMBER AS REQUIRED BY SEC. 61G15-23.002 | | | FLORIDA ADMINISTRATIVE CODE. | | | 5- ARCHITECT TO REVIEW AND APPROVE IN WRITING PRODUCT | | | APPROVAL SUBMITED FOR: | | | A) ALUMINUM SLIDING GLASS DOORS NOA 05-1121.08. | | | ARCHITECT APPROVED THE FLORIDA PRODUCT APPROVAL COVER | | | PAGE FL2038, BUT NOA AND FLORIDA APPROVAL DON'T | | | CORRESPOND TO EACH OTHER. | | | B) 8" PRECAST LINTELS. SAME THING FROM PREVIOUS | | | COMMENT. NOA AND FLORIDA APPROVAL DON'T CORRESPOND TO | | | EACH OTHER. | | | 6- REVISE ROOF FRAMING PLAN SHOWING WHERE ARE LINTELS | | | LB-2 USED. NONE SHOWN ON PLAN. |
|