| Plan Review Notes For Permit 07030070 |
| Permit Number |
07030070 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-19 08:47:43 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, SEE | | | FBC 13-600.3.A, 12-8-06 REV. | | | | | | 2) COOLING LOAD CALCULATIONS FOR A/C #3 ARE CALLING FOR | | | 25,246 SENSIBLE BTU'S, MECHANICAL PLANS FOR A/C #3 ARE | | | CALLING FOR 43,700 SENSIBLE BTU'S, THE PLANS CAN ONLY | | | CALL FOR 15% MORE THAN THE COOLING LOAD CAL'S, SEE 2004 | | | FBC13-607.1.ABC.1.1, 12-8-06 REV. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|